Loading...
HomeMy WebLinkAbout2020 Ordinance No. 046 1 BY AUTHORITY ORDINANCE NO. 46 COUNCIL BILL NO. 47 SERIES OF 2020 INTRODUCED BY COUNCIL MEMBER SIERRA AN ORDINANCE CONCERNING THE AMENDMENT OF TITLE 8, CHAPTER 2, ARTICLE E, OF THE ENGLEWOOD MUNICIPAL CODE, IN CONNECTION WITH ADOPTION OF THE INTERNATIONAL FIRE CODE, 2018 EDITION, AND SUCH AMENDMENTS AS SET FORTH WITHIN ATTACHMENT A, ALL WITHIN THE CITY OF ENGLEWOOD, ARAPAHOE COUNTY, COLORADO. WHEREAS, the City of Englewood has adopted Uniform Building Safety Codes, and subsequent updates as promulgated by the publisher, as the model construction and safety codes for the City since 1971; WHEREAS, Section 4.2 of the 2015 Intergovernmental Agreement by and between the City of Englewood and the City of Denver regarding fire protection services provides that “Englewood agrees within one (1) year of the Effective Date of this Agreement to adopt the 2015 International Building and Fires Codes and to adopt any subsequent versions of the building and fire codes within six (6) months of Denver’s adoption of said subsequent versions of said codes”; WHEREAS, Section 4.2 of the 2015 Intergovernmental Agreement by and between the City of Englewood and the City of Denver regarding fire protection services provides that “Englewood agrees not to adopt any laws or amendments to said codes that conflict with or are materially inconsistent with the applicable uniform building and fire codes without obtaining the prior, written approval of the Denver Fire Chief (which approval will not be unreasonably withheld); WHEREAS, the Chief Building Official for the City of Englewood has determined that none of the proposed amendments to the International Fire Code, 2018, conflict with or are materially inconsistent with the applicable uniform building and fire codes; WHEREAS, in the spirit of interlocal cooperation, Englewood’s proposed modifications to the Fire Code have been provided to the Denver Fire Chief, and the Denver Fire Chief has provided a letter of support; and WHEREAS, the Fire Marshal for the City of Englewood has thoroughly reviewed the International Fire Code 2018 and recommends adoption thereof subject to certain exceptions, modifications and amendments as set forth within Attachment A to this Ordinance. NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF ENGLEWOOD, COLORADO, THAT: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 2 Section 1. Adoption of the International Fire Code, 2018 Edition, as the Fire Code, with certain additions and deletions. Title 8, Chapter 2, Article E shall be amended as follows: 8-2E-1: CODE ADOPTED: There is hereby adopted by reference by the City of Englewood, Colorado, for the purpose of establishing standards for the safety, health, and public welfare, the International Fire Code, 2018 Edition, as the Fire Code for the City, as published by the International Code Council, 4051 Flossmoor Road Country Club Hills, IL 60478, as Title 8, Chapter 2, Article E, of the Englewood Municipal Code, and such amendments, exceptions, modifications, and appendices as set forth within such Code and within Attachment A of this Ordinance. The City Clerk shall maintain a copy of the Code, Attachment A setting forth specific modifications to the Code, and errata updates and all of which will be available for inspection during regular business hours. 8-2E-2: SPECIFIC MODIFICATIONS TO ADOPTED CODE: Specific changes, modifications and amendments are hereby made to the provisions of the International Fire Code 2018, as hereinabove adopted as Attachment A of this Ordinance, with all such changes, modifications and amendments as fully set forth within Attachment A to this Ordinance, and all are hereby incorporated into this Ordinance as if fully set forth herein, and such Attachment A shall be known and cited as Section 8-2E-2 of the Englewood Municipal Code. Section 2. Notice of general provisions and findings applicable to interpretation and application of this Ordinance: Applicability of Title 1, Chapter 2, Saving Clause. The provisions of E.M.C. Title 1, Chapter 2, Saving Clause apply to interpretation and application of this Ordinance, unless otherwise set forth above, including, but not limited to, the provisions regarding severability, inconsistent ordinances or code provisions, effect of repeal or modification, and legislation not affected by repeal. Enforcement. E.M.C. Title 1, Chapter 4, “General Penalty” provisions mandate that except as otherwise provided within specific Titles, Chapters, or Sections of the Englewood Municipal Code, the violation of any provisions of the Code, or of any secondary code adopted therein, shall be punished by a fine not exceeding two thousand six hundred and fifty dollars ($2,650.00) or imprisonment for a term not exceeding three hundred sixty (360) days or by both such fine and imprisonment. Safety Clauses. The City Council hereby finds, determines, and declares that this Ordinance is promulgated under the general police power of the City of Englewood, that it is promulgated for the health, safety, and welfare of the public, and that this Ordinance is necessary for the preservation of health and safety and for the protection of public convenience and welfare. The City Council further determines that the Ordinance bears a rational relation to the proper legislative object sought to be obtained. Introduced, read in full, and passed on first reading on the 5th day of October, 2020. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 3 Published by title as a Bill for an Ordinance in the City’s official newspaper on the 8th day of October, 2020. Published as a Bill for an Ordinance on the City’s official website beginning on the 7th day of October, 2020 for thirty (30) days. Read by title and passed on final reading on the 19th day of October, 2020. Published by title in the City’s official newspaper as Ordinance No.46, Series of 2020, on the 22nd day of October, 2020 Published by title on the City’s official website beginning on the 21st day of October, 2020 for thirty (30) days. This Ordinance shall take effect thirty (30) days after publication following final passage. Linda Olson, Mayor ATTEST: Stephanie Carlile, City Clerk I, Stephanie Carlile, City Clerk of the City of Englewood, Colorado, hereby certify that the above and foregoing is a true copy of the Ordinance passed on final reading and published by title as Ordinance No. 46, Series of 2020. Stephanie Carlile DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 ATTACHMENT A CITY OF ENGLEWOOD 2020 AMENDMENTS TO THE 2018 EDITION OF THE INTERNATIONAL FIRE CODE AND APPENDICES AS PUBLISHED BY INTERNATIONAL CODE COUNCIL (ICC) DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-1 TABLE OF CONTENTS CHAPTER 1 SCOPE AND ADMINISTRATION SECTION 101 SCOPE AND GENERAL REQUIREMENTS PAGE 1 SECTION 102 APPLICABILITY 2 SECTION 103 DEPARTMENT OF FIRE PREVENTION – FIRE MARSHAL’S OFFICE 3 SECTION 104 GENERAL AUTHORITY AND RESPONSIBILITIES 3 SECTION 105 PERMITS 7 SECTION 106 FEES 24 SECTION 107 INSPECTIONS 25 SECTION 108 MAINTENANCE 26 SECTION 109 BOARD OF APPEALS 27 SECTION 110 VIOLATIONS 27 SECTION 111 UNSAFE BUILDINGS 28 SECTION 114 LICENSES 29 SECTION 115 PUBLIC FIRE EDUCATION 30 SECTION 116 EMERGENCY PLANS AND PROCEDURES 30 SECTION 117 FIRE ALARM MONITORING – PERMITS AND LICENSES 30 CHAPTER 2 DEFINITIONS SECTION 202 GENERAL DEFINITIONS 32 CHAPTER 3 GENERAL REQUIREMENTS SECTION 301 GENERAL 40 SECTION 302 DEFINITIONS 40 SECTION 304 COMBUSTIBLE WASTE MATERIAL 40 SECTION 307 OPEN BURNING, RECREATIONAL FIRES AND PORTABLE OUTDOOR FIRES 41 SECTION 308 OPEN FLAMES 41 SECTION 309 POWERED INDUSTRIAL TRUCKS 42 SECTION 311 VACANT PREMISES 43 SECTION 315 GENERAL STORAGE 43 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-2 SECTION 316 HAZARDS TO FIREFIGHTERS 43 SECTION 317 ROOFTOP GARDENS AND LANDSCAPED ROOFS 44 SECTION 319 MOBILE FOOD PREPARATION VEHICLES 45 CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL 47 SECTION 402 DEFINITIONS 48 SECTION 403 EMERGENCY PREPAREDNESS REQUIREMENTS 48 SECTION 404 FIRE SAFETY EVACUATION AND LOCKDOWN PLANS 49 SECTION 405 EMERGENCY EVACUATION DRILLS 49 CHAPTER 5 FIRE SERVICE FEATURES SECTION 502 DEFINITIONS 50 SECTION 503 FIRE APPARATUS ACCESS 51 SECTION 504 ACCESS TO BUILDING OPENINGS AND ROOFS 53 SECTION 505 PREMISES IDENTIFICATION 54 SECTION 507 FIRE PROTECTION WATER SUPPLIES 54 SECTION 508 FIRE COMMAND CENTER 55 SECTION 509 FIRE PROTECTION UTILITY EQUIPMENT AND ACCESS 57 SECTION 510 EMERGENCY RESPONDER RADIO ENHANCEMENT COVERAGE SYSTEM (RES) 58 CHAPTER 6 BUILDING SERVICES AND SYSTEMS SECTION 603 FUEL-FIRED APPLIANCES 62 SECTION 605 MECHANICAL REFRIGERATION 62 SECTION 606 ELEVATOR OPERATION, MAINTENANCE AND FIRE SERVICE KEYS 62 CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 806 DECORATIVE VEGETATION IN NEW AND EXISTING BUILDINGS 66 SECTION 807 DECORATIVE MATERIALS NOT DECORATIVE VEGETATION-/NEW/EXISITING BUILDINGS 66 CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 69 SECTION 902 DEFINITIONS 69 SECTION 903 AUTOMATIC SPRINKLER SYSTEMS 70 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-3 SECTION 904 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS 73 SECTION 905 STANDPIPE SYSTEMS 74 SECTION 906 PORTABLE FIRE EXTINGUISHERS 76 SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 77 SECTION 908 EMERGENCY ALARM SYSTEMS 93 SECTION 909 SMOKE CONTROL SYSTEMS 94 SECTION 910 SMOKE AND HEAT REMOVAL 108 SECTION 912 FIRE DEPARTMENT CONNECTIONS 108 SECTION 913 FIRE PUMPS 109 SECTION 915 CARBON MONOXIDE DETECTION 110 SECTION 916 GAS DETECTION SYSTEMS 113 SECTION 919 CENTRAL ALARMS STATIONS 114 SECTION 920 TRANSMISSION OF CITY MICROWAVE SIGNALS 116 SECTION 921 ELEVATORS AND CONVEYING SYSTEMS 116 CHAPTER 10 MEANS OF EGRESS Chapter 10 of the International Fire Code is amended in accordance with the amendments to Chapter 10 of the International Building Code. 120 CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS SECTION 1101 GENERAL 121 SECTION 1103 FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS 121 SECTION 1105 CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2 122 SECTION 1107 REQUIREMENTS FOR COMPRESSED GAS SYSTEMS 123 SECTION 1108 FIREFIGHTER FALL PROTECTION 123 CHAPTER 12 EMERGENCY AND TANDBY POWER SYSTEMS SECTION 1203 GENERAL 125 SECTION 1206 ELECTRICAL ENERGY STORAGE SYSTEMS 127 CHAPTER 20 AVIATION FACILITIES SECTION 2001 GENERAL 128 SECTION 2005 PORTABLE FIRE EXTINGUISHERS 128 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-4 SECTION 2006 AIRCRAFT FUELING 129 SECTION 2007 HELISTOPS AND HELIPORTS 129 CHAPTER 23 MOTOR FUEL-DISPENSING FACILITIES AND GARAGES SECTION 2303 LOCATION OF DISPENSING DEVICES 130 SECTION 2304 DISPENSING OPERATIONS 130 SECTION 2305 OPERATIONAL REQUIREMENTS 130 SECTION 2306 FLAMMABLE AND COMBUSTIBLE LIQUID MOTOR FUEL- DISPENSING FACILITIES 131 SECTION 2308 COMPRESSED NATURAL GAS MOTOR FUEL-DISPENSING FACILITIES 131 SECTION 2309 HYDROGEN MOTOR FUEL-DISPENSING AND GENERATION FACILITIES 131 SECTION 2311 REPAIR GARAGES 131 SECTION 2312 EXISTING MOTOR FUEL-DISPENSING FACILITIES 132 CHAPTER 24 FLAMMABLE FINISHES SECTION 2401 GENERAL 133 SECTION 2404 SPRAY FINISHING 133 SECTION 2405 DIPPING OPERATIONS 133 SECTION 2410 FLOOR SURFACING AND FINISHING OPERATIONS 133 CHAPTER 25 FRUIT AND CROP RIPENING SECTION 2503 ETHYLENE GAS 134 CHAPTER 26 FUMIGATION AND INSECTICIDAL FOGGING SECTION 2601 GENERAL 135 SECTION 2603 FIRE SAFETY REQUIREMENTS 135 CHAPTER 27 SEMICONDUCTOR FABRICATION FACILITIES SECTION 2703 GENERAL SAFETY PRECAUTIONS 136 CHAPTER 28 LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS AND WOODWORKING FACILITIES SECTION 2804 FIRE PROTECTION 137 SECTION 2809 EXTERIOR STORAGE OF FINISHED LUMBER AND SOLID BIOFUEL PRODUCTS 137 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-5 CHAPTER 30 INDUSTRIAL OVENS SECTION 3003 LOCATION 138 CHAPTER 31 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES 139 SECTION 3107 OPERATIONAL REQUIREMENTS 139 CHAPTER 32 HIGH-PILED COMBUSTIBLE STORAGE SECTION 3201 GENERAL 140 SECTION 3206 GENERAL FIRE PROTECTION AND LIFE SAFETY FEATURES 140 SECTION 3211 EXISTING BUILDING 142 CHAPTER 33 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 3301 GENERAL 144 SECTION 3311 MEANS OF EGRESS 144 SECTION 3313 STANDPIPES 144 CHAPTER 34 TIRE REBUILDING AND TIRE STORAGE SECTION 3405 OUTDOOR STORAGE 145 SECTION 3408 FIRE PROTECTION 145 CHAPTER 35 WELDING AND OTHER HOT WORK SECTION 3501 GENERAL 146 SECTION 3505 GAS WELDING AND CUTTING 146 SECTION 3508 ACETYLENE GENERATORS 146 CHAPTER 39 MARIJUANA OPERATIONS SECTION 3901 GENERAL 141 SECTION 3902 DEFINITIONS 147 SECTION 3903 EXTRACTION OPERATIONS 147 SECTION 3904 MARIJUANA GROWING OPERATIONS 147 CHAPTER 40 ALCOHOL BEVERAGE PRODUCTION FACILITIES 150 SECTION 4002 DEFINITIONS, ACRONYMS AND ABBREVIATIONS 150 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-6 SECTION 4003 GENERAL REQUIREMENTS 154 SECTION 4004 EQUIPMENT 163 CHAPTER 50 HAZARDOUS MATERIALS—GENERAL PROVISIONS SECTION 5001 GENERAL 172 SECTION 5002 DEFINITIONS 172 SECTION 5003 GENERAL REQUIREMENTS 173 SECTION 5004 STORAGE 173 SECTION 5005 USE, DISPENSING AND HANDLING 173 CHAPTER 53 COMPRESSED GASES SECTION 5307 COMPRESSED GASES NOT OTHERWISE REGULATED 174 CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5601 GENERAL 195 CHAPTER 57 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 5701 GENERAL 196 SECTION 5703 GENERAL REQUIREMENTS 196 SECTION 5704 STORAGE 197 SECTION 5706 SPECIAL OPERATIONS 197 CHAPTER 60 HIGHLY TOXIC AND TOXIC MATERIALS SECTION 6004 HIGHLY TOXIC AND TOXIC COMPRESSED GASES 198 SECTION 6005 OZONE GAS GENERATORS 198 CHAPTER 61 LIQUEFIED PETROLEUM GASES SECTION 6101 GENERAL 199 SECTION 6103 INSTALLATION OF EQUIPMENT 199 SECTION 6104 INSTALLATION OF EQUIPMENT 199 SECTION 6107 SAFETY PRECAUTIONS AND DEVICES 200 SECTION 6109 STORAGE OF PORTABLE LP-GAS CONTAINERS AWAITING USE OR RESALE 200 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE TOC-7 SECTION 6112 FIXED, MOBILE, OR TEMPORARY CONCESSIONS PROTECTIONS 200 CHAPTER 80 REFERENCED STANDARDS 201 APPENDICES APPENDIX ADOPTION STATUS 204 APPENDIX B FIRE-FLOW REQUIREMENTS FOR BUILDINGS SECTION B104 FIRE-FLOW CALCULATION AREA 205 SECTION B105 FIRE-FLOW REQUIREMENTS FOR BUILDINGS 207 APPENDIX C FIRE HYDRANT LOCATIONSAND DISTRIBUTION SECTION C106 WATER MAINS SERVING FIRE HYDRANTS 207 APPENDIX N SHOP DRAWING AND SYSTEM GRAPHIC REQUIREMENTS FOR FIRE PERMIT APPLICATION SECTION N101 GENERAL 208 SECTION N103 TECHNICAL REQUIREMENTS 208 APPENDIX O TALL WOOD BUILDINGS 226 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 1 CHAPTER 1 SCOPE AND ADMINISTRATION SECTION 101 SCOPE AND GENERAL REQUIREMENTS Sections 101.1 Title 101.2 Scope and 101.3 Intent are replaced as follows: 101.1 Title. The title of this code is and may be cited and referred to as the Fire Code, the Englewood Fire Code, or the Fire Code of the City of Englewood. It may be referred to herein as “this code” or “the code,” in both upper and lower case. The terms “Englewood” and “City” are understood to mean the City of Englewood. 101.2 Scope. This code establishes regulations affecting or relating to structures, processes, premises, and safeguards including, but not limited to: 1. Inspection of permanent and temporary buildings, processes, equipment, systems, and other fire- and safety-related situations, at intervals established by the fire code official but not to exceed once every 12 months. 2. Investigation of fires, explosions, hazardous materials incidents, and other related emergency events; the Denver fire department shall be responsible for fire/explosion cause determination and subsequent investigation; 3. Recovery of City costs related to emergency response incidents, including the mitigation of hazardous materials incidents; nuisance alarms; problematic systems; fire safety inspections; systems testing; re- inspections; re-testing; investigations; emergency fire watch assigned to private properties, etc. 4. Storage, use, processing, handling, production and transportation of hazardous materials; 5. Storage, use, processing, handling, production and transportation of flammable and combustible gases, liquids, and solids; 6. Interior finish, decorations, furnishings, and other combustibles that contribute to fire spread, fire load, and smoke production in all occupancies; 7. Hazards from interior fires in trash, excessive storage of combustibles, production of chemical material, and other materials that pose an exposure hazard to adjacent property in all occupancies including single family residences; 8. Hazards from outside fires in vegetation, trash, storage, vehicles, combustible and flammable materials, building debris, fencing, and other materials; 9. Regulation and control including assignment of fire watch personnel, of special events including, but not limited to, assemblage of people, exhibits, trade shows, amusement parks, haunted houses, outdoor events, livestock events, large sporting events, and other similar special temporary and permanent occupancies; 10. Existing occupancies and conditions, 11. Maintenance and testing of all fire- and life-safety systems; 12. Access and water supply requirements for Fire Department operations; 13. Review of design plans and construction documents including drawings, calculations and specifications for the design and construction of new buildings, and alterations, additions and repairs of existing buildings; Review of design plans and construction documents including drawings, calculations and specifications for the installation, alteration, addition and repair of life- and fire-safety systems, equipment, features, components, devices and apparatus including but not limited to fire protection systems, Fire Department access, water supply, flammable and combustible materials, storage, DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 2 production and use of hazardous materials, commercial processes. 14. Fire and life safety education of fire brigades, employees, responsible parties, and the general public including the review and approval of emergency procedures for all occupancies and evaluation of fire drills; 15. Control of emergency operations and scenes; 16. Conditions affecting firefighter safety. 17. Licensing certification of firms/designers/installers/inspectors/testers of life safety systems equipment referenced in this code and standards and property managers, etc., responsible for the safety of others. 18. Review of design plans, construction documents and shop/layout drawings for the installation, alteration, modification and repair of conveyances. 19. Inspection of conveyances. 20. Review of design plans, construction documents and process systems for the growing, retail and medical sales, extraction, enrichment and infusing of marijuana and by-products. 21. Inspection of facilities used for the growing, retail and medical sales, extraction, enrichment and infusing of marijuana. The provisions of this code shall supplement any and all laws relating to fire- and life-safety and shall apply equally to all of the following without restriction: persons, firms, corporations, the government of the United States of America, the government of the State of Colorado, the government of the City of Englewood, and all agencies, subdivisions, and departments thereof. The provisions of this Code shall apply to existing conditions as well as to conditions arising after the adoption of the Code. 101.2.1 Appendices. Provisions in the appendices shall apply as noted by the Appendix Adoption Status. 101.3 Intent. The purpose of this code is to establish the minimum requirements, consistent with nationally recognized good practice, for providing a reasonable level of occupant and pedestrian fire- and life-safety and property protection from the hazards of fire, explosion, production, use, and handling of dangerous and hazardous materials, substances, and devices, or dangerous conditions in new and existing buildings, structures, and premises, and to provide safety to firefighters and emergency responders during emergency operations. SECTION 102 APPLICABILITY Section 102.5 Application of residential code is amended by adding an exception as follows: Exception: Other than premise identification (address), section 102.5 shall not apply to the following: a. Interior or exterior renovations constructed under the provisions of the International Residential Code to existing detached one- or two-family dwellings; b. Additions constructed under the provisions of the International Residential Code to existing detached one- or two-family dwellings; or c. Demolition or removal of a one- or two-family dwelling and replacement with a single new one- or two-family dwelling constructed under the provisions of the International Residential Code; however, this Exception c does not apply to construction of a new structure permitted for use as an accessory dwelling unit. Sections 102.7 Referenced codes and standards and 102.8 Subjects not regulated by this code are replaced as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 3 102.1 Referenced codes and standards. Additional details regarding processes, methods, specifications, equipment testing and maintenance, or other pertinent criteria contained in these standards and codes listed in Chapter 80 of this Code shall be considered a part of this Code. Volumes 1 through 18 of the National Fire Codes are standards to this code. Additionally, all references to the “International Electrical Code,” and “ICC Electrical Code,” shall be changed to “NFPA 70, National Electrical Code (NEC).” Exception: National Fire Protection Association standards identified in Chapter 80 Referenced Standards as recommendations. 102.2 Subjects not regulated by this code. Where no applicable codes, standards, or requirements are set forth in this Code or contained within other laws, codes, regulations, ordinances, or bylaws adopted by the City of Englewood Fire Marshal’s Office, compliance with the applicable codes and standards of the National Fire Protection Association (NFPA) or other nationally recognized and approved standards shall be deemed as prima facie evidence of compliance with the intent of this code. Nothing herein shall derogate from the authority of the City of Englewood Fire Marshal’s Office to determine compliance with codes or standards for those activities or installations within the City of Englewood’s jurisdiction or responsibility. SECTION 103 DEPARTMENT OF FIRE PREVENTION Sections 103.1.1 Fire Prevention Division and 103.1.2 Rules and regulations are amended as follows: 103.1.1 Division of Fire Prevention. The Division of Fire Prevention, under the direction of the Fire Marshal, is a special operation within the Special Operations and Codes Division of the Police Department of the City of Englewood. The Special Operations and Codes Division operates under the authority of the Division Commander. The position of Fire Marshal is and may be referred to as the “Fire Code Official,” “Fire Official,” and “Fire Marshal,” in both upper and lower case. This code shall be administrated and enforced by the Fire Code Official. 103.1.2 Rules and regulations. The Fire Official shall have the full power to adopt, in reference to this Code, any rules, restrictions, or measures that may be advisable, following review and approval of such by the Chief of Police and City Manager. Section 103.3 Deputies is repealed. Section 103.4 Intergovernmental Agreement to Provide Fire Protection shall be added as follows: 103.4 IGA for Fire Protection. The 2015 Intergovernmental Agreement to Provide Fire Protection entered into by and between the City of Englewood, Colorado and the City of Denver, Colorado, setting forth the responsibilities of Englewood and Denver with respect to the provision of fire suppression services and other fire related services, including emergency medical services, E-911 communications, personnel, property, fire stations lease, and payment, is hereby incorporated into this Code to the extent such agreement defines the duties of both Cities in association with Fire Suppression and Emergency Response as those matters are set forth and understood within this Code. SECTION 104 GENERAL AUTHORITY AND RESPONSIBILITIES Section 104.1.1 Authority is added as follows: 104.1.1 Authority. The Fire Code Official is authorized to inspect land, buildings, structures, utilities, installations, equipment, devices, legal and illegal processes, and materials for fire, explosion, and other emergency hazards, releases of hazardous materials, false alarms, any unsafe conditions that relate to the protection of the public and/or property and other emergencies. The Fire Code Official is also authorized to issue permits, inspect, and enforce compliance regarding elevators and similar devices, escalators, moving walks, DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 4 automated people movers (APM, also known as AGTS) according to State of Colorado Conveyance Regulations (7 Code of Colorado Regulation 1101-8), the Englewood Fire Code and Section 1109 and Chapter 30 of the Englewood Building Code at a minimum. The Fire Code Official shall have the authority to investigate fire protection and other life safety systems that are disabled or not functioning. The Fire Code Official shall also have the authority to control the use, location, and transportation of flammable or combustible liquids or acids (in a chemical or physical state) or hazardous materials; the issuance of permits; the issuance of notices, orders, or City of Englewood Municipal Court summonses for the correction or immediate abatement of hazardous situations; the enforcement of this code and other laws, ordinances, rules, and regulations, which are within the perspective of this Code and standards set forth in Chapter 80. Section 104.3 Right of entry is replaced as follows: 104.3 Right of entry. Whenever it is necessary to make an inspection to enforce the provisions of this code, or whenever the fire code official has reasonable suspicion to believe there exists in a building or upon any premises, any vehicle, or any vessel, any conditions or violations of this code that make the premises, vehicle, or vessel unsafe, dangerous, or hazardous, the fire code official shall have the authority to enter the building, vehicle, or vessel to conduct an inspection and, if necessary, an investigation, taking photographs of unsafe, dangerous, or hazardous conditions or for investigative or fire investigation purposes or the pursuance of any other emergency, or to perform the duties upon the fire code official by this code. If such building, premises, or vehicle is occupied, the fire code official shall present credentials to the occupant and request entry. If such building, premises, or vehicle is unoccupied, the fire code official shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. If entry is refused, the fire code official has recourse to every remedy provided by law to secure entry. Sections 104.3.2 Interference with enforcement and 104.3.3 Power to protect property are added: 104.3.2 Interference with enforcement. It shall be unlawful for persons to interfere or cause conditions that would interfere with the fire code official in carrying out any duties or functions prescribed by this code. 104.3.3 Power to protect property. The fire code official shall have power to cause the removal of any real or personal property when necessary to preserve real property from fire, explosion, or other emergency; to prevent the spreading of fire; or to protect adjoining property. No person shall be entitled to remove any personal property in the possession of the fire code official saved from any fire until proof of ownership thereof is furnished. Section 104.4.1 Impersonation is added as follows: 104.4.1 Impersonation. Persons shall not use a badge, uniform, or other credentials to impersonate a fire code official - prevention, engineering or investigation. Section 104.6.3 Fire records is replaced: 104.6.3 Fire records. The Fire Department shall keep a record of all fires, explosions, and other emergencies occurring within its jurisdiction and of facts concerning the same, including reports (including investigation reports), photographs, videos, and statistics as to the extent of such fires and the damage or injury caused thereby, together with other information as required by the fire code official. All records related to a property shall be maintained for the life of the property. All other records shall be maintained for no less than seven (7) years. Section 104.6.3.1 Fire loss information is added as follows: 104.6.3.1 Fire loss information. It shall be the responsibility of any person suffering a fire, explosion, building collapse, or other emergency resulting in injury(s) to persons and/or property loss within the City of Englewood to report the incident and to provide the Division in writing with the dollar value of the resulting loss within ten (10) days of the loss. If insured, the person may DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 5 provide the name and address of the insurance company, in which case the insurance company shall supply the final loss figures to the Division. Section 104.7.2 Technical assistance is replaced in its entirety as follows: 104.7.2 Technical assistance. To determine the adequacy and permissibility of existing and proposed assemblies, facilities, materials, occupancies, processes, products, systems, and technologies attending the design, operation or use of a building, structure, premises, or appurtenances situated thereon, subject to review or inspection by the fire code official, the fire code official is authorized to require the owner or owner’s authorized agent to provide without charge to the jurisdiction, any or all of the following technical assistance and a meaningful report including recommendations: analyses, calculations, drawings, experiments, inspections, interpretations, observations, opinions, reviews, research, and tests. Technical assistance shall be provided, and the report prepared by a qualified expert preapproved by the fire code official. The fire code official is authorized to require the report to be prepared by, and bear the stamp of, a registered design professional. Section 104.7.2.1 Final determination is added as follows: 104.7.2.1 Final determination. The fire code official shall make the final determination as to whether the provisions of this code have been met. Sections 104.8.1 Application for modification and 104.8.2 Compliance with code are added: 104.8.1 Application for modification. The fire code official is authorized to modify any of the provisions of this code upon application in writing by the owner where there are practical difficulties in carrying out the provisions of the Code, provided the intent of the code shall be complied with, public safety secured, and substantial justice done. 104.8.2 Compliance with code. Buildings with equivalency, alternative, or modification approved by the building official and fire code official shall be considered conforming to the code. Sections 104.9.3 Fire protection features and 104.9.4 Building Code are added: 104.9.3 Fire protection features. Each application for an alternate fire protection feature shall be filed with the fire code official and shall be accomplished by such evidence, letters, statements, test results, or other supporting information as required to justify the request. The fire code official shall keep a record of actions on such applications, and a signed copy of the fire code official’s decision shall be provided for the applicant. 104.9.4 Building Code. Whenever the alternate material or method involves matters regulated by the Fire Code and Building Code, approvals are also subject to approval of the building code official. Sections 104.10 Fire investigations is replaced: 104.10 Fire investigations. The Denver Fire Department and Englewood Fire Marshal is authorized to investigate without delay the cause, origin, and circumstances of each and every fire or explosion or intent to commit such an act occurring within the City of Englewood involving the loss of life or injury to a person or destruction or damage to property and, if it appears to the fire investigators that such fire or explosion is of suspicious origin, the investigators are authorized to take immediate charge of all physical evidence relating to the intent or cause of the fire and are authorized to pursue the investigation to its conclusion. 104.10.1 Release of hazardous materials. The fire code official is authorized to investigate the cause, origin, and circumstances of unauthorized releases of hazardous materials. The fire code official is authorized to recover from the responsible party(s) all costs incurred by the City for mitigation, rendering the release harmless to people or property, including personnel and equipment, securing the incident scene, removal of materials released and cleanup. Section 104.10.1 Assistance from other agencies is deleted. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 6 Sections 104.10.2 Authorization of Englewood Police Department, 104.10.3 Limiting access, and 104.10.4 Interference with enforcement are added: 104.10.2 Authorization of Englewood Police Department. The Englewood Police Department is authorized to assist the Fire Department in any investigation when requested to do so by the Manager of Safety, the Fire Chief, or the fire code official. 104.10.3 Limiting access. The Fire Department shall have the authority to limit access to buildings, property, vehicles, vessels, or other similar conveyances by any vehicle, vessel, or person during an investigation. 104.10.4 Interference with enforcement. Persons shall not interfere, nor cause conditions that would interfere with, the fire investigator carrying out any duties or functions, including arrest of suspects, prescribed by this Code. Section 104.11.1.1 Scene barrier is added as follows: 104.11.1.1 Scene barrier. The incident commander in charge of an emergency scene shall have the authority to establish barriers to control access in the vicinity of such emergency and to place, or cause to be placed, ropes, guards, barricades, or other obstructions across any public or private street or alley, to delineate an emergency scene barrier(s). No person, except as authorized by the incident commander in charge of the emergency, shall be permitted to cross barriers established in accordance with Sections 104.11.1 and this section. Whenever the emergency incident involves private property, the owner of said property shall be responsible for all costs related to placement, rental and use of barricades; all costs incurred by the City for mitigation, rendering the scene harmless to people or property, and removal of equipment and materials and cleanup. Section 104.11.3.1 Resetting or silencing of alarms is added as follows: 104.11.3.1 Resetting or silencing of alarms. No person shall reset or silence a fire protection or life safety system unless by direction of the fire chief, fire code official or fire department official in charge of the incident. Section 104.11.4 Emergency power to demolish buildings and 104.11.5 Cost recovery are added: 104.11.4 Emergency power to demolish buildings. When a fire is in progress, the fire code official, or the officer in charge of the fire, may order any building that is in close proximity to such fire to be torn down, blown up, or otherwise disposed of for the purpose of checking the conflagration. The property owner shall be responsible for all costs related to all operations. 104.11.5 Cost recovery. The property owner shall be responsible for all costs related to placement, rental and use of barricades. Section 104.12 Unsafe buildings, structures or utilities is added as follows: 104.12.1 Notice and Abatement. If, after inspection by the Fire Code Official, the building, structure or utility is determined to be unsafe by the fire code official, it shall be abated by repair, replacement, removal or demolition upon notice by the fire code official. If the building or structure has common property line walls, then the fire code official shall notify the adjacent building owners that their building may be unsafe and may require repair or reinforcement. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 7 104.12.2 Buildings or Structures. In the case of an unsafe building or structure, the fire code official may order such building or structure, or any buildings or structures placed in jeopardy by the unsafe building or structure, vacated immediately. When necessary to protect life, property, health and public welfare, the fire code official may cause to have posted signs which shall prohibit entry into an unsafe building or structure. However, with permission of the fire code official, it shall be lawful to enter the unsafe building or structure for the purpose of effecting any required repairs, rehabilitation or demolition; or by members of the Fire Department. The signs shall be provided and attached to the building or structure by the Fire Code Official and shall read, in addition to other information, “UNSAFE – DO NOT ENTER.” 104.12.3 Utilities. In the case of an unsafe utility, the fire code official shall cause to be affixed an approved warning tag on the unit declared to be unsafe. The fire code official shall order the unsafe utility disconnected or its use discontinued until the unsafe condition is abated. In addition, the fire code official may order any building, structure or utility which is placed in jeopardy by the unsafe utility to be vacated and/or disconnected, and these shall not be reoccupied or reconnected until declared safe by the fire code official. It shall be unlawful for anyone to mark any unsafe utility, as herein defined, with any type markings or tags declaring them to be unsafe, except as authorized by the fire code official. 104.12.4 Demolition or Securing by the City. If the owner and/or occupant of an unsafe building, structure or utility fails to perform the repairs, rehabilitation, securing or removal required by an order within the time specified therein or any extension of time to comply with said order, the fire code official may, as set forth in this Section, cause the demolition or securing of the unsafe building or structure. 104.12.5 Emergency Demolition or Securing. In the event an emergency should occur wherein the continued use or existence of a building, structure or utility may constitute an immediate hazard to life, health, property or public welfare, the fire code official may order and/or cause the building, structure or utility to be demolished, removed, disconnected, secured or barricaded at once by any means available to the Agency. When feasible, the fire code official shall attempt to give notice, by any means, to the owner of the building, structure or utility prior to taking any action. Cost and expense of demolition, removal, securing or barricading, if borne by the City, shall be recovered as provided for in this Section. SECTION 105 PERMITS Section 105.1 General is replaced: 105.1 General. The fire code official shall be authorized to establish and issue permits, certificates, notices, approvals, or orders pertaining to fire and hazard control and fire and explosion hazards wherever indicated by this Code. A permit issued under the provisions of this Code shall continue until revoked or for such a period of time designated therein at the time of issuance. Such permit shall not be transferable, and any change in use, occupancy, operation, or ownership shall require a new permit. Permits for activities requiring evidence of financial responsibility by the jurisdiction shall not be issued unless proof of required financial responsibility is furnished. Any attempt to misrepresent or otherwise deliberately or knowingly design; install; service; maintain; operate; sell; represent for sale; falsify records, reports, or applications; or act in any related activity in violation of the requirements prescribed by this Code shall be a violation of this Code. Such violations shall be cause for immediate suspension or revocation of any related licenses, certificates, or permits issued by the fire code official. In addition, any such violation shall be subject to any other criminal or civil penalties as available by the laws of this jurisdiction. An inspection is required prior to the issuance of a permit. Any person who engages in any business, operation, or occupation, or uses any premises, after the permit issued therefore has been suspended or revoked pursuant to the provisions of this Code, and before such suspended permit has been reinstated or a new permit has been issued, shall be in violation of this Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 8 Section 105.1.7 Other required permits is added as follows: 105.1.7 Other required permits. The requirements for permits from other City agencies shall not waive the requirement for permits required by this Code. Where a permit is required by other City agencies, such permit shall be obtained prior to or simultaneous with the issuance of a permit required by this Code. Section 105.6 Required operational permits and all subsections are replaced as follows: 105.6 Required permits. The fire code official is authorized to issue operational permits for the operations set forth in Sections 105.6.1 through 105.6.160: 105.6.6 Ammunition. A permit is required to store and handle ammunition, large arms and small arms. 105.6.6.1 Large arms 105.6.6.2 Small arms 105.6.7 Burning in public places / Open burning. A permit is required for the kindling or maintaining of an open fire or a fire on any public street, alley, road, or other public or private ground. Instructions and stipulations of the permit shall be adhered to. Exception: Recreational fires when a fire ban has not been instituted. 105.6.8 Candles and open flames in assembly areas. A permit is required to use open flames or candles in connection with assembly areas, dining areas of restaurants or drinking establishments. 105.6.9 Canopies. A permit is required to erect a canopy having an area as follows: 105.6.9.1 Canopies having an area of 300 square feet or more but less than 500 square feet. 105.6.9.2 Canopies having an area of 500 square feet or more. 105.6.10 Carbon dioxide (CO2). 105.6.10.1 Carbon dioxide (CO2) systems used in beverage dispensing applications. A permit is required for the use of carbon dioxide (CO2) systems with more than 100 pounds (45.4 kg) of carbon dioxide or any system using any amount of carbon dioxide (CO2) below grade used in beverage dispensing applications. 105.6.10.2 Carbon dioxide (CO2) gas enrichment systems using on-site supply tanks and/or cylinders in plant growing (husbandry) applications. A permit is required for carbon dioxide enrichment systems with more than 100 pounds (45.4 kg) of carbon dioxide or any system using any amount of carbon dioxide (CO2) below grade used in plant growing (husbandry) applications. 105.6.10.3 Carbon dioxide (CO2) gas enrichment systems using a natural gas burner in plant growing (husbandry) applications. A permit is required for natural gas burners that are utilized to generate carbon dioxide (CO2) in plant growing (husbandry) applications. 105.6.11 Carbon monoxide alarms and carbon monoxide detectors. A permit is required for the installation, relocation or removal of carbon monoxide alarms and detectors required under provisions of Section 915. 105.6.12 Cellular/wireless signal repeater sites. A permit is required to install and maintain cellular/wireless signal repeater sites. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 9 105.6.13 Demolition by explosives. A permit is required for the use of any explosive device for demolition operations. 105.6.14 Exhibits and trade shows. A permit is required to operate exhibits and trade shows. 105.6.15 Explosives/blasting agents. A permit is required for the manufacture, storage, handling, sale or use of any quantity of explosives, explosive materials, fireworks or pyrotechnic special effects within the scope of Chapter 56. Exception: Storage in Group R-3 occupancies of smokeless propellant, black powder and small arms primers for personal use, not for resale and in accordance with Section 5606. 105.6.16 Failure to obtain a permit. A temporary permit is required when a required permit has not been obtained. The fee for this temporary permit shall be double the cost of the required permit. 105.6.17 File search. A fee is required for the following file searches: 105.6.18 Fire alarm signal delay equipment. A permit is required to install and maintain fire alarm signal delay equipment integrated with the FACP. 105.6.19 Fire department fire alarm radio transmitter (wireless communicator). A permit is required to install and maintain fire department fire alarm radio equipment for monitoring fire and burglar alarms. 105.6.58 Fire watch. A permit is required whenever a fire watch is mandated. 105.6.59 Fireworks/pyrotechnics. A permit is required for all professional pyrotechnic programs. 105.6.60 Flammable or combustible liquids. A permit is required: 1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the Department of Transportation (DOT) nor does it apply to piping systems. 3.1 To store, handle or use Class IIIB liquids of 1,000 gallons or more in a building or outside a building. 2. To remove Class I or Class II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes. 3. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. 4. To place temporarily out of service (for more than 90 days) an underground, protected above- ground or above-ground flammable or combustible liquid tank. 5. To change the type of contents stored in a flammable or combustible liquid tank to a material which poses a greater hazard than that for which the tank was designed and constructed. 6. To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments. 7. A site plan shall be submitted showing the following: distances from all buildings, property lines, utility poles, power lines, railroad tracks, etc. A Hazardous Materials Inventory Statement (HMIS) may be required upon request. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 10 105.6.118 Pyrotechnic event. A permit is required for all pyrotechnic events 105.6.118.3 Indoor/Outdoor pyrotechnic event 105.6.118.4 Use of propane effects 105.6.118.5 Pyrotechnic inspector during event. (Paid by promoter as after-hours inspection) 105.6.119 Pyrotechnician. A permit/certificate of fitness is required for all pyrotechnicians. 105.6.128 Special events. A permit is required for special events. 105.6.128.1 Places of assembly – any hazardous material or process at temporary events. 105.6.128.2 Places of assembly – refueling operations at temporary events in assembly occupancies. 105.6.128.3 Places of assembly – storage, use and handling of flammable/combustible liquids at temporary events. 105.6.128.4 Places of assembly – storage, use and handling of compressed gases at temporary events. 105.6.128.5 Event within existing facility 105.6.128.6 Plan submittal less than 14 days prior to event 105.6.128.7 Outdoor with six or more fuel-fired cooking/heating units 105.6.136 Storage of scrap tires and tire by-products. A permit is required to establish, conduct or maintain storage of scrap tires and tire byproducts of 2,500 cubic feet (566 m3) or more total volume of scrap tires and for indoor storage of tires and tire byproducts. 105.6.140 Tanks (Change of content). A permit is required to change the contents of a chemical or fuel storage tank. 105.6.141 Temporary fire standpipe. A permit is required to install and maintain a temporary fire standpipe. 105.6.142 Temporary generator. A permit is required to use a temporary generator. 105.6.143 Temporary heating appliance. A permit is required to install or use a temporary heating appliance. 105.6.143.1 Temporary space heating appliances (electric) in existing builings – all permits must be obtained from designated fire official via building ownership or management. 105.6.144 Tents or temporary membrane structures. See Section 3103.2. 105.6.144.1 Tent or temporary membrane structure - not open on all sides and having an area in excess of 200 sq. ft. 105.6.144.2 Tent or temporary membrane structure - open on all sides and having an area of 400 sq. ft. or more. 105.6.145 Tire rebuilding/recapping plants. A permit is required for the operation and maintenance of a tire rebuilding or recapping plant. 105.6.146 Tire shredding. A permit is required for operations involving shredding of tires. 105.6.147 Tire storage. A permit is required for tire storage of 2500 cubic ft. or more in any one control area. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 11 105.6.148 Trailer. A permit is required for trailers used for office functions. 105.6.148.1 Temporary – less than 180 days 105.6.148.2 Permanent – 180 days or longer Section 105.7 Required construction permits and all of its subsections are replaced in their entirety as follows: 105.7 Required construction permits. The fire code official is authorized to issue construction permits for work as set forth in Sections 105.7.1 through 105.7.32. 105.7.1 Appliances fueled by waste petroleum products. A construction permit is required to install appliances fueled by waste petroleum products. 105.7.2 Automatic fire extinguishing systems. A construction permit is required prior to the installation or modification of automatic fire extinguishing systems. Work performed to keep equipment operable or to make repairs is considered maintenance and requires a permit: Exceptions: 1. A required permit may be acquired after work is performed on an emergency basis to maintain an existing fire extinguishing system. The penalties stated herein shall not apply if the emergency permit application is submitted within two (2) normal business days after commencement of the emergency work. A full permit application is required within ten (10) normal business days after commencement of the emergency work. 2. With written approval from the fire code official prior to commencement of the work, maintenance performed in accordance with this code shall not require a permit. 3. Minor work not impacting the mechanics of the system including gauge replacement, leaking sprinkler replacement (less than 3), hydraulic placard replacements, single hose valve replacement (not including PRV’s), turn wheel replacements, escutcheon replacements, hangar replacements/repairs, etc. 105.7.3 Battery systems. A construction permit is required to install stationary storage battery systems in accordance with Section 1206.2.1. 105.7.4 Carbon dioxide (CO2) 105.7.4.1 Carbon dioxide (CO 2) systems used in beverage dispensing applications. A construction permit is required for the installation of carbon dioxide (CO2) systems with more than 100 pounds (45.4 kg) of carbon dioxide or any system using any amount of carbon dioxide (CO2) below grade used in beverage dispensing applications. 105.7.4.2 Carbon dioxide (CO2) gas enrichment systems using on-site supply tanks and/or cylinders in plant growing (husbandry) applications. A construction permit is required for the installation of carbon dioxide enrichment systems with more than 100 pounds (45.4 kg) of carbon dioxide or any system using any amount of carbon dioxide (CO2) below grade used in plant growing (husbandry) applications. 105.7.4.3 Carbon dioxide (CO2) gas enrichment systems using a natural gas burner in plant growing (husbandry) applications. A construction permit is required for the installation of natural gas burners that are utilized to generate carbon dioxide (CO2) in plant growing (husbandry) applications. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 12 105.7.5 Cellular / Wireless signal repeater site. A construction permit is required to install a cellular/wireless signal repeater site. 105.7.6 Compressed gases. When the compressed gases in use or storage exceed the amounts listed in Table 105.6.38, a construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a compressed gas system. Exceptions: 1. Routine maintenance. 2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work. 105.7.7 Compressed natural gas (CNG). A construction permit is required to install, modify or remove a compressed natural gas tank. 105.7.8 Conveyances. Construction permits are required for the installation, alteration, modification, removal, maintenance, and testing of all elevators and conveyances within the City of Englewood. Shop and/or layout drawings shall be submitted for review and approval prior to issuance of permits. Drawings shall comply with ASME A17.1 and FMO policy. Two sets of specifications and accurately-scaled and fully-dimensioned construction plans shall be provided in accordance with Appendix N. These plans shall include the applicable code edition which shall conform to the edition of the code currently adopted and shall include specifications of interior cab materials or indication on the plans that interior cab work is to be completed by others. Permits issued shall be displayed in the conveyance control room or control space associated with the permitted conveyance. See also Section 919 for additional requirements. 105.7.9 Cryogenic fluids. A construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, close or substantially modify an outdoor stationary cryogenic fluid storage system where the system capacity exceeds the amounts listed in Table 105.6.42. Maintenance performed in accordance with this code is not considered a modification and does not require a permit. 105.7.10 Fire alarm and detection systems and related equipment. A construction permit is required prior to the installation or modification of fire alarm and detection systems and related equipment. Work performed to keep equipment operable or to make repairs is considered maintenance and requires a construction permit. Construction permits are required for any work to the following systems: 1. Emergency alarm systems. 2. Emergency communication systems (ECS). 3. Mass notification systems. 4. Public safety radio communication systems (RES). 5. Two-way communication systems. 6. Gas detection systems. Exceptions: 1. A required permit may be acquired after work is performed on an emergency basis to maintain an existing fire alarm or detection system. The penalties stated herein shall not apply if the emergency permit application is submitted within two (2) normal business days after commencement of the emergency work. A full permit application is required within ten (10) normal business days after commencement of the emergency work. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 22 2. With written approval from the fire code official prior to the work, maintenance performed in accordance with this code may not require a permit. 105.7.11 Fire pumps and related equipment. A construction permit is required prior to the installation or modification of fire pumps and related fuel tanks, jockey pumps and controllers. Work performed to keep equipment operable or to make repairs is considered maintenance and requires a permit. Exceptions: 1. A required permit may be acquired after work is performed on an emergency basis to maintain an existing fire pump. The penalties stated herein shall not apply if the emergency permit application is submitted within two (2) normal business days after commencement of the emergency work. A full permit application is required within ten (10) normal business days after commencement of the emergency work. 2. With written approval from the fire code official prior to the work, maintenance performed in accordance with this code shall not require a permit. 3. Minor work not impacting the mechanics of the systems including gauge replacement, driver oil/lube job, hydraulic placard replacements, light bulb replacement, battery replacement, fuel treatment, packing adjustments, etc. 105.7.12 Flammable and combustible liquids. A construction permit is required: 1. To repair or modify a pipeline for the transportation of flammable or combustible liquids. 2. To install, construct or alter tank vehicles, equipment, tanks, plants, terminals, wells, fuel- dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. 3. To install, alter, remove, abandon or otherwise dispose of a flammable or combustible liquid tank. 105.7.13 Generator Set. A construction permit is required to install the following fueled generator set(s) with or without an integral tank. 105.7.13.1 Fuel Oil 105.7.13.2 Natural Gas 105.7.14 Hazardous materials. A construction permit is required to install, repair damage to, abandon, remove, place temporarily out of service, or close or substantially modify a storage facility or other area (including but not limited to tanks) regulated by Chapter 50 when the hazardous materials in use or storage exceed the amounts listed in Table 105.6.69. Exceptions: 1. Routine maintenance. 2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work. 105.7.15 High-piled combustible storage. A construction permit is required for the installation or reconfiguration of all high-piled storage systems. 105.7.16 Industrial ovens. A construction permit is required for installation of industrial ovens covered by Chapter 30. Exceptions: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 23 1. Routine maintenance. 2. For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work. 105.7.17 Inert gas systems used in commercial, manufacturing or industrial applications. A construction permit is required for the use of inert gas systems with more than 100 pounds (45.4 kg) of an inert gas or any system using any amount of an inert gas below grade used in a commercial, manufacturing or industrial application, such as water treatment with pH balancing, food processing or laboratories. 105.7.18 LP-gas. A construction permit is required for installation of or modification to an LP-gas system. 105.7.18.1 Cage – an installation permit is required to install a cage for storage of portable LP gas containers awaiting use or resale. 105.7.18.2 Tank – a construction permit is required to install, repair damage to, abandon, remove or place temporarily out of service an LP gas tank. 105.7.18.3 Automated cylinder exchange station. – a construction permit is required to install an automated cylinder exchange station. 105.7.19 Nitrous oxide-piped systems. A construction permit is required to install nitrous oxide-piped systems. 105.7.20 Ozone generator. A construction permit is required to install an ozone generator. 105.7.21 Powder coating. A construction permit is required to install a spray booth for powder coating. 105.7.22 Pressure vessel. A construction permit is required to install a pressure vessel. 105.7.23 Private fire hydrants. A construction permit is required for the installation or modification of private fire hydrants. 105.7.24 Process piping. A construction permit is required to install, repair or modify piping systems and their component parts (piping, tubing, valves and fittings) that convey hazardous materials including flammable and combustible liquids. 105.7.25 Refrigeration equipment. A construction permit is required for a mechanical refrigeration unit or system regulated by Chapter 6. 105.7.26 Repair /garages. A construction permit is required to install a repair garage operation. 105.7.27 Smoke control systems. A construction permit is required for the installation, modification, or removal from service of a smoke control system, including fans, controllers (VFD’s), ductwork, fire/smoke dampers, annunciators, and associated controls. Work performed to keep equipment operable or to make repairs is considered maintenance and requires a construction permit. Exceptions: 1. A required permit may be acquired after work is performed on an emergency basis to maintain an existing smoke control system. The penalties stated herein shall not apply if the emergency permit application is submitted within two (2) normal business days after commencement of the emergency work. A full permit application is required within ten (10) normal business days after commencement of the emergency work. 2. With written approval from the fire code official prior to the work, maintenance performed in accordance with this code shall not require a permit. 3. Minor repair work not impacting the safety function, infrastructure or software of the system such as like for like replacement of damper acutator (not more than 3), damper linkage and door DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 24 closures 105.7.28 Spraying or dipping. A construction permit is required to install or modify a spray room, dip tank or booth. 105.7.29 Standpipe systems. A construction permit is required for the installation, modification, or removal from service of a standpipe system. Work performed to keep equipment operable or to make repairs is considered maintenance and requires a permit. Exceptions: 1. A required permit may be acquired after work is performed on an emergency basis to maintain an existing standpipe system. The penalties stated herein shall not apply if the emergency permit application is submitted within two (2) normal business days after commencement of the emergency work. A full permit application is required within ten (10) normal business days after commencement of the emergency work. 2. With written approval from the fire code official prior to the work, maintenance performed in accordance with this code shall not require a permit. 3. Minor work not impacting the mechanics of the system such as gauge replacement, hydraulic placard replacements, single hose valve replacement (not including PRV’s), turn wheel & cap replacements, hangar replacements/repairs, etc. 105.7.30 Temporary membrane structures, tents and canopies. A construction permit is required to erect an air-supported temporary membrane structure or a tent having an area of 400 square feet (37 m2) or more. Exceptions: 1. Tents used exclusively for recreational camping purposes. 2. Funeral tents and curtains or extensions attached thereto, when used for funeral services. 3. Fabric canopies and awnings open on all sides which comply with all of the following: a. Individual canopies shall have a maximum size of 700 square feet (65 m2). b. The aggregate area of multiple canopies placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m2) total. c. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be maintained. 105.7.31 Underground hazardous materials storage tanks. A construction permit is required to install an underground hazardous materials storage tank. 105.7.32 Woodworking operations. A construction permit is required to install a woodworking operation. SECTION 106 FEES Section 106.2 Schedule of permit fees is amended by replacing it in its entirety as follows: 106.2 Schedule of permit fees. A fee necessary to cover administrative costs of inspection, licensing, record-keeping, and other requirements for all fire prevention programs under this Code shall be paid in accordance with fee schedules established by the Manager of Safety. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 25 SECTION 107 INSPECTIONS Sections 107.2.3 Dangerous or hazardous conditions or material through 106.2.13 Townhomes, condominiums and apartments are added: 107.2.3 Dangerous or hazardous conditions or material. The fire code official shall have the authority to order any person(s) to remove or remedy such dangerous or hazardous condition or material as set forth in this code. Any person(s) failing to comply with such order shall be in violation of this code. 107.2.4 Right of entry. The fire code official shall be authorized to inspect any building or premises for dangerous or hazardous conditions or materials as set forth in this code. Before entering, the fire code official shall obtain the consent of the occupant thereof or obtain a court warrant authorizing entry for the purpose of inspection except in those instances where an emergency exists. 107.2.5 Emergency. As used in Section 106.2.4, “emergency” means circumstances that the fire code official knows, or has reason to believe, exist and can constitute immediate danger to life and property. 107.2.6 Authorized personnel. Uniformed fire inspectors, fire investigators, and fire protection engineers shall be authorized to enter and inspect buildings, structures, vessels, vehicles, and premises as herein set forth. 107.2.6.1 Impersonation. Persons shall not use a badge, uniform, or other credentials to impersonate the fire code official. 107.2.7 Hazardous conditions. Where conditions exist and are deemed hazardous to life and property by the fire code official, the fire code official shall have the authority to summarily abate such hazardous conditions that are in violation of this code. 107.2.8 Plans and specification. The fire code official shall have the authority to require plans and specifications to ensure compliance with applicable codes and standards. The plans and specifications shall bear the stamp of a design professional 107.2.9 Inspection of construction and installation. The fire code official shall be notified by the person performing the work when the installation is ready for a required inspection or for fire protection or other life safety systems acceptance tests. All installations shall be complete prior to requesting an inspection or test. All components of a life safety system shall be installed prior to testing—no exceptions. 107.2.9.1 Work in violation. When any construction or installation work is being performed in violation of the plans and specifications approved by the fire code official, a written notice shall be issued to the responsible party to stop work on that portion of the work that is in violation. The notice shall state the nature of the violation, and no work shall be continued on that portion until the violation has been corrected. 107.2.10 Stop work or evacuation. The fire code official shall have the authority to order an operation or use stopped and the immediate evacuation of any occupied building, area of a building, or other property when such building, area of a building, or other property has hazardous conditions that present imminent danger. 107.2.10.1 Non-complying work. Whenever any work is being done contrary to provisions of this code, the fire code official is hereby authorized to order such work stopped. Such work should immediately stop until authorized by the fire code official to proceed. 107.2.11 Standby personnel. When, in the opinion of the Fire Code Official it is essential for public safety in a tent, canopy or membrane structure used as a place of assembly or any other use where people congregate, or any building, premises or property where people congregate, because of the number of DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 26 persons, or the nature of the performance, exhibition, display, contest or activity, or when potentially hazardous conditions exist, or an occupant load varies due to large crowd movement from one building to another building or one area of a building to another area of the building, or there is a reduction in a life safety feature, or there is an impairment to a fire protection feature, the owner, agency or lessee shall employ qualified Fire Watch personnel. 107.2.11.1 Owner’s responsibility. The owner, agent, or lessee shall employ standby fire personnel in an adequate number determined by the fire code official based on the potential hazard or reduction in a fire protection system or other life safety feature as described in Section 106.2.11, as required and approved, to be on duty. Such standby fire personnel or fire watch personnel shall be subject to the fire code official’s orders at all times and shall be identifiable and remain actively on duty during the times such places are open to the public, when such activity is being conducted, or in residential buildings, whenever occupied. 107.2.12 Records. The Fire Marshal’s Office shall retain, for the life of the building or structure, a record of each inspection made showing the findings and disposition of each inspection made. 107.2.13 Townhouses, condominiums and apartments. Portable fire extinguishers shall be mounted on the exterior at each level stairway(s) or one (2A:10BC) within each residential unit. When mounted on the exterior, the property management/homeowner’s association (HOA) shall be responsible for the care, maintenance and recharging, and use of the fire extinguisher, including inspection. Portable fire extinguishers shall be located, inspected and maintained in accordance with NFPA 10. The smoke detector(s) within the residential units shall be tested and maintained in accordance with NFPA 72. The carbon monoxide detectors shall be located, inspected, tested and maintained in accordance with NFPA 720. Section 107.5 Frequency of Inspections is added as follows: 107.1 Frequency of inspections. Fire safety inspections for the specific property/operation shall be required at intervals established by the fire code official but not to exceed once every 12 months. Section 107.6 Special inspections is added as follows: 107.2 Special inspections. The Fire Code Official is authorized to conduct special inspections, including fire safety inspections and systems acceptance testing, outside of normal business hours as deemed necessary to determine the extent of compliance with the provisions of this Code. Certified personnel shall perform the fire safety inspections and systems acceptance testing. The property owner, property manager, or contractor shall reimburse the City for special inspections outside of normal business hours shall be a minimum of three (3) hours Monday through Friday and a minimum of four (4) hours on weekends and holidays. SECTION 108 MAINTENANCE Section 108.7 Fire watch personnel, 108.7.1 Owner’s responsibility and 108.7.2 Permit required are added: 108.7 Fire watch personnel. When in the opinion of the fire code official it is essential for public or occupant safety, because of potentially hazardous conditions or a reduction in safety due to the occupant load, crowd movement, type of performance, display, exhibit, use, contest, activity; impairment to a fire protection or other life safety system; or any similar condition, the fire code official shall have the authority to require a fire watch in any building, premises or property. 108.7.1 Owner’s responsibility. The owner, agent, or lessee shall employ licensed and certified personnel for fire watch in adequate numbers as determined by the fire code official based on the potential hazard or reduction in safety described in Section 108.7. Fire watch personnel shall be subject to the fire code official’s orders at all times and shall be identifiable and remain actively on duty during the times specified by the fire code official. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 27 108.7.2 Permit required. Permits shall be required as set forth in Section 105.6.58. SECTION 109 BOARD OF APPEALS Section 109.1 Board of appeals is replaced in its entirety as follows: The entirety of section 109 BOARD OF APPEALS, including all subsections, shall be amended to read as follows: Refer to Section 8-1-7 of the Englewood Municipal Code for the requirements of this section. SECTION 110 VIOLATIONS Sections 110.3.2.1 Failure to comply through 110.3.2.4 Citation are added: 110.3.2.1 Failure to comply. It shall be unlawful to violate any provisions of this code, or to fail to carry out an order made pursuant to this code or violate any condition attached to a permit, approval, or certificate, or to erect, install, alter, repair or do work in violation of approved construction documents, or without the appropriate license, permit or directive of the fire official. Violations shall be punishable as prescribed in the City of Englewood Municipal Code. It shall be unlawful to fail to pay fees authorized pursuant to this code. 110.3.2.2 Time limits. Failure to comply with the time limits of an abatement notice or after a corrective order or notice of violation is issued by the fire code official shall result in each day that such violation continues being regarded as a new and separate violation and a new and separate offense. 110.3.2.3 Not owner-occupied. If the building or other premises is not owner occupied, under lease or otherwise, and the order or notice of violation requires additions or changes in the building or premises that would immediately become real estate and be the property of the owner of the building or premises, such orders or notices shall be complied with by the owner. 110.3.2.4 Citation. The fire code official is authorized to issue a citation to persons operating or maintaining an occupancy, premises, vessel, vehicle or other property subject to this code who allow a hazard to exist or fail to take immediate action to abate a hazard on such occupancy, premises, vessel, vehicle, or other property when ordered or notified to do so. A citation may be issued when work is performed without the appropriate license, permit or directive of the fire official, or in violation of approved construction documents. [remainder of page intentionally left blank] DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 28 Section 110.4 Violation penalties is replaced as follows: 110.4 Violation penalties. See Section 110.3.2.1 Failure to comply. SECTION 111 UNSAFE BUILDINGS Section 111.1 General is replaced in its entirety as follows: 111.1 General. If during the inspection of a premises, a building or structure or any building system, in whole or in part, constitutes a clear and inimical threat to human life, safety or health, the fire code official shall issue such notice or orders to remove or remedy the conditions as shall be deemed necessary in accordance with this section and shall refer the building to the Building Department for any repairs, alterations, remodeling, removing or demolition required. It shall be unlawful to maintain an unsafe condition in any building. Section 111.1.1 Unsafe conditions is replaced in its entirety as follows: 111.1.1 Unsafe conditions. Structures or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress, failure to comply with an approved occupant load, or which constitute a fire hazard such as storage of explosives, excessive amounts of combustible or flammable materials, vegetation deemed an exposure hazard, manufacture of controlled substances, unstable material, hazardous materials, fire safety system(s) inoperative, etc., or are otherwise dangerous to human life or to the public welfare, or which involve illegal or improper occupancy or inadequate maintenance, shall be deemed an unsafe condition. A vacant structure that is not secured against unauthorized entry shall be deemed unsafe. A structure, including residences, that constitutes a fire hazard and an exposure hazard in the event of fire or explosion shall be deemed unsafe. It shall be unlawful to maintain an unsafe condition or to fail to obey an order of the fire code official to correct an unsafe condition. The fire code official is authorized to take action to mitigate an unsafe condition, rendering the operation harmless to people or property. The property owner shall be responsible for all costs related to all actions. Section 111.1.2.1 Unsafe heating or electrical equipment and structural hazards is added as follows: 111.1.2.1 Unsafe heating or electrical equipment and structural hazards. When the fire code official deems any chimney, smokestack, stove, oven, incinerator, furnace, or other heating device, electrical fixture, or any appurtenance thereto, or anything regulated under a nationally recognized standard in or upon any building, structure, or premises not specifically mentioned in this code, to be unsafe or defective so as to create a hazard, the fire code official is authorized to serve upon the owner or the person having control of the property a written notice to remove or repair or alter as necessary. The fire code official is authorized to affix a condemnation tag prohibiting the use thereof, or until such repairs or alterations are made. It shall be unlawful to maintain unsafe heating or electrical equipment and structural hazards or to fail to obey an order of the fire code official to correct unsafe heating or electrical equipment and structural hazards. Section 111.1.2.2 Unsafe operations is added as follows: 111.1.2.2 Unsafe operations. When the fire code official deems any operation, interior or exterior, to be unsafe so as to create a hazard, the fire code official is authorized to serve upon the owner, contractor, or the person having control of the property, a written notice to remove or repair or alter as necessary. The fire code official is authorized to affix a condemnation tag prohibiting the use thereof, or until such repairs or alterations are made. In the event that the unsafe operation resulted in an emergency response, legal action and cost recovery will be directed to the responsible party. It shall be unlawful to maintain unsafe operations or to fail to obey an order of the fire code official to correct unsafe operations. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 29 SECTION 114 is added: LICENSES 114.1 General. A license is authority granted to the person to whom it is issued to perform the work authorized by the license. 114.2 Licenses required. City of Englewood licenses shall be required for the design, installation, modification, inspection, and testing of all life safety and conveyance systems and equipment. All life safety fitters/technicians shall be licensed to design, install, add to, modify, and perform all types of inspections, testing, maintenance, and repair of factory-engineered equipment. Conveyance inspectors and mechanics shall be licensed by the Fire Marshal’s Office per Section 114.3. All persons required to have a permit, license or certificates shall have a current—for calendar year—permit, license or certificate. 114.2.1 Ammonia safety / alarm systems. 114.2.2 Backflow prevention for fire sprinkler systems. 114.2.3 Carbon dioxide extinguishing systems. 114.2.4 Carbon monoxide detection systems. 114.2.5 Carbon monoxide safety / alarm warning systems. 114.2.6 Central station operator. 114.2.7 Central station runner. 114.2.8 Conveyances. 114.2.9 Clean agent fire extinguishing systems. 114.2.10 Department of safety radio enhancement systems. 114.2.11 Dry chemical extinguishing systems. 114.2.12 Electrical signaling and central wiring. 114.2.13 Emergency communication systems. 114.2.14 Fire alarm systems. 114.2.15 Fire detection systems. 114.2.16 Fire doors and other opening protectives. 114.2.17 Foam extinguishing systems. 114.2.18 Fire pumps. 114.2.20 Fire sprinkler systems – NFPA 13. 114.2.21 Fire sprinkler systems – NFPA 13D. 114.2.22 Fire sprinkler systems – NFPA 13R. 114.2.23 Fire standpipe systems – NFPA 14. 114.2.24 Firefighter’s emergency elevator recall systems. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 30 114.2.25 Foam extinguishing systems. 114.2.26 Kitchen hood extinguishing systems. 114.2.27 Oxygen coordinator. 114.2.28 Oxygen supply and delivery. 114.2.29 Portable fire extinguishers. 114.2.30 Refrigerant safety / alarm systems. 114.3 Conveyance licensing. Englewood Fire Marshal’s Office licenses shall be required for the installation, alteration, replacement, maintenance, removal, dismantling, or inspection activities of conveyances. A conveyance contractor license issued by the Fire Marshal’s Office is required for installation or alteration of equipment. SECTION 115 is added: PUBLIC FIRE EDUCATION 115.1 General. The fire code official shall have the authority to develop and implement a public fire safety education program as deemed necessary for the general welfare with respect to the fire hazards within the jurisdiction. 115.2 Educational programs and messages. The fire code official shall have the authority to ensure that duly authorized public fire safety educational programs or public fire safety messages are disseminated to the general public. SECTION 116 is added: EMERGENCY PLANS AND PROCEDURES 116.1 General. Where required, emergency plans, staff training, and emergency evacuation drills are required for all occupants. 116.2. Plan requirements. Emergency plans and emergency evacuation drills shall be developed in accordance with NFPA 1600, Standard on Disaster/Emergency Management and Business Community Programs, and Chapter 4, Emergency Planning and Preparedness, of this code. 116.3 Maintenance. Emergency plans shall be reviewed and updated annually. Revised plans shall be submitted for review and updates shall be provided whenever changes are made in the occupancy or physical arrangement of the building or fire protection systems or features. The owner or manager shall provide floor plans to the Fire Code Official. SECTION 117 is added: FIRE ALARM MONITORING - PERMITS AND LICENSES 117.1 General. The provisions of this section apply to the installation, operation of, and scope of monitoring. 114.2.31 Rubbish and linen handling systems. 114.2.32 Smoke control systems. 114.2.33 Special extinguishing systems. 114.2.34 Carbon dioxide beverage dispensing (including gas and detection/alarm). 114.2.35 Multi-family dwelling apprentice inspector. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 31 117.2 Central alarm station / Supervising station. These facilities, licensed by the Englewood Fire Marshal’s Office, monitor remote fire alarm signaling systems when personnel licensed by the Englewood Fire Marshal’s Office are in attendance at all times to take such action as required for the notification of the Englewood Fire Marshal’s Office. 117.3 Permits. Permits shall be obtained annually for central alarm station / supervising stations and the operators who take such action as required for notification of the Denver Fire Department. All central alarm station / supervising stations and operators shall have current—for current calendar year—permits and licenses. 117.4 Definitions. The following terms are defined in Chapter 2: CENTRAL ALARM STATION/SUPERVISING STATION CLASS I FIRE ALARM MONITORING CLASS II FIRE ALARM MONITORING OPERATOR RUNNER 117.5 License required. 117.5.1 Central alarm station/supervising station. No person or public agency shall monitor fire alarm systems in the City of Englewood without first obtaining a license to operate a Class I or Class II central alarm station/supervising station. 117.5.2 Operator. No person shall be employed as an operator in a central alarm station/supervising station that monitors fire alarm systems in the City of Englewood unless licensed as an apprentice operator or operator. 117.5.2.1 Class I operator. A Class I Operator license shall authorize the holder to act as an operator in any central alarm station/supervising station. 117.5.2.2 Class II operator. A Class II Operator license shall authorize the holder to act as an operator in any Class II central alarm station/supervising station. 117.5.2.3 Apprentice operator. An Apprentice Operator license shall authorize the holder to act as an operator only under the constant supervision of a licensed operator. 117.5.3 Runner. A central alarm station/supervising station Runner license shall authorize the holder to act as a runner for any Class I or Class II central alarm station/supervising station. 117.6 Runner service. The central alarm station/supervising station shall provide runner service to all Class I alarms. Maximum response time from receipt of alarm to arrival of runner service shall not exceed 45 minutes. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 32 CHAPTER 2 DEFINITIONS SECTION 202 GENERAL DEFINITIONS Section 202 General Definitions is amended by the addition of the following terms: ALARM CONTROL UNIT. A component of the [CO detection] system provided with a primary and secondary power source that receives signals from initiating devices or other control units and processes these signals to determine the required system output functions. ALCOHOL BEVERAGE (also, “ALCOHOL BEVERAGE”). A drinkable ethanol mixture intended for human consumption including wine, beer, and beverage spirits. ALCOHOL BEVERAGE PRODUCTION FACILITY (ABPF). Any building or portion thereof where ethanol mixtures are produced, stored, handled, blended, dispensed, or bottled in the production of alcohol beverages including areas for grain storage and handling. ALCOHOL BY VOLUME (ABV). Volume percentage of ethanol in an ethanol mixture. ALTITUDE. Altitude is the measure of elevation typically relative to sea level. The generally recognized altitude of Englewood, CO is 5,280 ft. Altitude has a direct impact on design considerations for life safety and property protection including but not limited to the physical properties of flammable and combustible liquids. See Section 3401.5.1. APPLIANCE. Visible notification component such as a bell, horn, speaker, light, or text that provides audible, visible, and/or tactile outputs to alert occupants of a hazardous condition. Single-station alarms contain both a [initiating] device and a [notification] appliance. BATTERY BACKUP. The listed device has a battery that powers it when the power provided through the building electrical system fails. BATTERY-POWERED. The listed device is powered solely by a primary battery for all power requirements and the battery is monitored for end-of-life by producing an audible trouble signal. BEVERAGE SPIRIT (TTB). A drinkable spirit intended for human consumption including neutral spirits or alcohol (i.e., vodka or grain spirits), whiskey, gin, brandy, blended applejack, rum, Tequila, cordials and liqueurs. BIOHAZARD. An infectious agent or hazardous biological material that presents a risk or potential risk to the health of humans, animals or the environment. The risk can be direct through infection or indirect through damage to the environment. Biohazardous materials include certain types of recombinant DNA; organisms and viruses infectious to humans, animals or plants (e.g., parasites, viruses, bacteria, fungi, prions, rickettsia); and biologically active agents (i.e., toxins, allergens, venoms) that may cause disease in other living organisms or cause significant impact or the environment or community. BREWERY. An ABPF or portion thereof, including accessory uses, in which beer or other malt liquors are produced. For spirit production, beer and wash are synonymous as precursors to distillation BULK STORAGE. The storage of ethanol mixtures in containers exceeding 1.3 gallons (5L) in volume. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 33 CARCINOGEN. A substance that causes the development of cancerous growths in living tissue. A chemical is considered to be a carcinogen if: 1. It has been evaluated by the International Agency for Research on Cancer (IARC) and found to be a carcinogen or potential carcinogen, or 2. It is listed as a carcinogen or potential carcinogen in the latest edition of the Annual Report on Carcinogens published by the National Toxicology Program, or 3. It is regulated by OSHA as a carcinogen. CASK. A closed vessel of 185 gallons (700 L) or less capacity, used primarily for storing Class I liquids, constructed of wooden staves and heads, held together by metal hoops, not equipped with provisions for emergency venting, and not intended for fixed installation. CENTRAL ALARM STATION/SUPERVISING STATION. A facility that receives fire alarm signals and at which personnel are in attendance at all times to respond to these signals. A supervising station that is licensed for central station service. CENTRAL FUEL-BURNING APPLIANCE ROOM. A room containing a fuel burning appliance serving multiple dwelling units, such as a boiler, fire place, stove, furnace, or similar equipment, with the potential to distribute CO to multiple dwelling units. CHEMICAL FUME HOOD. A ventilated enclosure designed to contain and exhaust fumes, gases vapors, mists, and particulate matter generated within the hood. CLASS I LIQUIDS. Used in Chapter 38 to identify ethanol mixtures that are Class IB or Class IC flammable liquids. CLASS I FIRE ALARM MONITORING. The monitoring of a fire alarm system by a licensed central station that is required by Englewood’s Building and Fire Codes. CLASS II FIRE ALARM MONITORING. The monitoring of a fire alarm system by a licensed central station that is not required by Englewood’s Building and Fire Codes. CO (CARBON MONOXIDE). A colorless odorless gas that is produced as a result of incomplete burning of carbon-containing fuels. CO ALARM. A single- or multiple-station device having a sensor that responds to CO and listed in accordance with UL 2034 that provides audible notification. Required CO alarms may be monitored by an alarm control unit, but shall be powered independently and shall function autonomously in the event the alarm control unit is nonfunctional. CO DETECTOR. A device listed per UL 2075 having a sensor that responds to CO, is monitored and powered by an alarm control unit, and does not necessarily have an integral notification appliance. CONTAINER. Any closed vessel of 119 gallons (450 L) or less capacity used for transporting or storing Class I liquids, not intended for fixed installation and not constructed of wood, but possible equipped with an overpressure-relieving mechanism in accordance with FM Global Approved Standard for Plastic Plugs for Steel Drums, Class Number 6083, or equivalent. ENGLEWOOD BUILDING CODE. The collection of International Code Council (ICC) publications as adopted and amended by the City of Englewood excluding the International Fire Code. ENGLEWOOD BUILDING AND FIRE CODE. The complete collection of International Code Council (ICC) publications as adopted and amended by the City of Englewood. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 34 ENGLEWOOD FIRE CODE. The International Fire Code (IFC) published by the ICC as adopted and amended by the City of Englewood. DEVICE. An alarm initiating component that originates transmission of a change-of-state condition, such as a CO detector, manual fire alarm box, etc. Single-station alarms are both a [initiating] device and a [notification] appliance. DISTILLATION. The separation and concentration of the constituents of an ethanol mixture by slowly raising the temperature of the mixture through the boiling points of its constituents then collecting and condensing the constituent vapors separately from the mixture. DISTILLERY (also DISTILLED SPIRITS PLANT – BEVERAGE). An ABPF licensed by the TTB to produce, bottle, rectify, process or store beverage spirits including areas for fermentation, distillation, storage, blending, packaging, and accessory uses. Other types of distilleries licensed by the TTB include: DISTILLED SPIRITS PLANT – EXPERIMENTAL. An experimental distilled spirits plant established for specific and limited periods of time solely for experimentation in, or development of, industrial spirits or sources of materials used to produce spirits, or processes for producing or refining spirits. DISTILLED SPIRITS PLANT – INDUSTRIAL. A distilled spirits plant established to manufacture articles, or produce, bottle or package, denature or warehouse spirits for industrial use. These spirits are not intended for beverage use. Distilled spirits – Vinegar Plants also fall into this category. DISTILLED SPIRITS PLANT – INDUSTRIAL / BEVERAGE. A distilled spirits plant that manufactures beverage and industrial spirits on the same premises. DUPLEX. A building consisting solely of a two-family dwelling as defined by the International Residential Code. ELECTROLYTE. A solid, liquid, or aqueous salt solution that permits ionic conduction between positive and negative electrodes of a cell. EMERGENCY shall mean one or more of the following: • Fire, regardless of size or type • Explosion • Building, structure, or utility failure • Rescue operations involving humans or animals, including people trapped in elevators due to power failure or mechanical malfunctions • Failure of or damage to fire protection or life safety systems • Exposure to a hazard(s) • Panic • Hazardous material leak or spill • Overcrowding of any building or premises • Rescue operations involving humans or animals injured or trapped in buildings, trenches, scaffolding, grandstands, etc. • Any other hazard or situation involving or endangering life or property. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 35 EMERGENCY RESPONDER RADIO ENHANCEMENT COMMUNICATION SYSTEM (RES/BDA). The RES/BDA is a network of amplifiers, fiber optic cable, coaxial cable, and radiating cable and/or discrete antennas with or without a distributed antenna system (DAS) controller, or an equivalent technology installed on or inside the property to enhance indoor public safety radio communications. ETHANOL (also ETHYL ALCOHOL or GRAIN ALCOHOL). A volatile, flammable, colorless, neurotoxic liquid fit for human consumption with structural formula CH-3CH-2OH (abbreviated as C2H5OH or C2H6O). ETHANOL MIXTURE. Liquid mixture comprised of ethanol and materials with hazards not regulated by the Englewood Building and Fire Code, namely water. EXTRACTION. The process of using solvents to remove essential oils or other botanic material from the marijuana plant. FALSE FIRE ALARM. The activation of any fire alarm system resulting in a response by the Fire Department, caused by the negligent or intentional misuse of the fire alarm system by an owner, employee, agent, tenant, guest, visitor, or any other activation of a fire alarm system not caused by a valid alarm signal, exclusive of a nuisance fire alarm. FERMENTATION. An enzymatically controlled, anaerobic breakdown of energy-rich compounds such as simple carbohydrates by microorganisms such as yeast, to yield carbon dioxide and ethanol. FUEL-BURNING APPLIANCE. An appliance that burns carbon-containing solid, liquid, and/or gaseous fuels. HARDWIRED. Device installed by wiring directly to the building electrical system, with battery backup, and not controlled by any disconnecting switch other than as required for over-current protection. HAZ MAT (HAZARDOUS MATERIALS). Materials with hazards regulated by the Englewood Building and Fire Code. HAZMAT INVENTORY STATEMENT (HMIS). A portion of an HMR containing a list of all the HazMat in a facility including information related to the materials such as product names, locations, quantities, regulated hazards, and Chemical Abstract Service (CAS) numbers. HAZMAT MANAGEMENT PLAN (HMMP). A portion of a HazMat Permit Application containing site maps and facility floor plans identifying HazMat locations and site and building features relevant to the management of HazMat inventories, systems and operations. HAZMAT REPORT (HMR). A consolidated description of a facility and the HazMat therein including a contact list, code-based description of the building and adjacent outdoor areas, and a HazMat Inventory Statement (HMIS). INSTALLED. Fit into position and made ready as set forth in the manufacturer’s guidelines, listing requirements and applicable standards, to perform the intended functions of detection, notification, and annunciation. INTERMEDIATE BULK CONTAINER. Any closed vessel defined in Title 49, Code of Federal Regulations, Parts 100 through 199 or in Part 6 of the United Nations’ Recommendations on the Transport of Dangerous Goods having a liquid capacity of 793 gallons (3000 L) or less, used for transporting or storing Class 1 Liquids, not equipped with provisions for emergency venting, not intended for fixed installation, and not constructed of wood. LOWER FLAMMABLE LIMIT (LFL) also [LOWER EXPLOSIVE LIMIT (LEL)]. The atmospheric volumetric concentration of a flammable vapor at which propagation of flame will occur in the presence of an ignition source. The LFL at sea level for ethanol vapor is 3.3 percent. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 36 LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. The lowest level of Fire Department vehicle access shall be measured from the lowest elevation of any required Fire Department access road located no more than 30 feet from any exterior wall of the building. Exceptions: 1. Where the access road is permitted to be farther than 30 feet from any exterior wall of the building, the lowest level of fire department vehicle access shall be measured from the lowest elevation of any required Fire Department access road located no more than 50 feet from any exterior wall of the building. 2. If any topography, waterway, non-negotiable grades or other similar conditions exist that preclude required Fire Department vehicular access, the fire code official is authorized to require additional fire protection systems as required by Chapter 9. MACHINERY ROOM. See Section 1104.2 of the International Mechanical Code. MASH. Typically, the mixture of ground or cracked grains, mashed fruit, or other crushed edible organic material steeped in hot water to release carbohydrates and reduce them to sugars. The term is used inconsistently (often overlapping with wort) for the various solutions in process up to the point where fermentation is complete. MASS NOTIFICATION SYSTEM. A mass notification system (MNS) is a system used to provide emergency information and instructions to people in a building, area, site or other space using intelligible voice communications and possibly including visible signals, text, graphics, tactile, or other communications methods. MINIMUM EXPLOSIVE CONCENTRATION (MEC). The lowest mass to volume concentration of combustible dust that will propagate a flame (sometimes referred to as LFL). The MEC for grain dust is 0.055 oz/ft3 (55 g/m3). MULTIPLE PURPOSE ALARM. A single device that incorporates the capability to detect more than one hazard, such as smoke, vapors, and/or gases. Multiple purpose devices shall emit audible alarms in a manner that clearly differentiates between the detected hazards. MULTIPLE STATION ALARM. [1] A single alarm device capable of being physically or wirelessly interconnected to one or more similarly capable devices so the actuation of any one device causes the appropriate notification signal to occur in all interconnected devices. [2] An interconnected group of single- alarm devices defined in [1]. NON-DEDICATED SMOKE CONTROL SYSTEM. Smoke control components and equipment that are shared with other systems, such as the building HVAC system. Upon activation of fire alarm, non-dedicated smoke control equipment changes mode of operation to achieve the smoke control performance objectives. “Non-dedicated systems” shall refer only to equipment and components controlled from the firefighters’ smoke control panel. NORMALLY CLOSED. A system or vessel in an ABPF used in the storage, production, dispensing, blending, bottling, or handling of Class 1 Liquids that, for up to 50 percent of the time it is in operation, its contents are not exposed to atmosphere and vulnerable to evaporation. Processes involving vessels such as casks opened only for filling, draining or sampling, distillation where all vapors are condensed below their flash point prior to collection, uncovered vessels of 5.3 gallon (20 L) capacity or less used to collect distillate below its flash point, and covered blending or maceration vessels are typically considered normally closed. NORMALLY OPEN. A system or vessel in an ABPF used in the storage, production, dispensing, blending, bottling, or handling of Class 1 Liquids that, for 50 percent or more of the time it is in operation, its contents DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 37 are continuously exposed to atmosphere and vulnerable to evaporation, or where a Class 1 Liquid at or above its flash point is exposed to atmosphere at any time during transfer, dispensing, or release. Continuous blending or maceration in uncovered vessels, open draining of Class 1 Liquids above their flash points, and the act of “bleeding” heads (the initial vapors generated during distillation) or tails (the last vapors generated during distillation) to atmosphere are typically considered normally open. NUISANCE FIRE ALARM. The activation of any fire alarm system resulting in a response by the Fire Department, caused by mechanical failure, malfunction, improper installation, lack of maintenance or other condition for which Fire Department personnel are unable to determine initiation of a valid alarm signal. (See Sections 401.5, “False Fire Alarm,” and 907.1.5). OPERATIONS PERMIT. A permit issued in conjunction with the operations listed in Section 105.6. OPERATOR. A competent person employed by a central alarm station and licensed by the Denver Fire Department to take such action as required for notification of the Denver Fire Department. OTHER HEALTH HAZARD MATERIAL. A hazardous material which affects target organs of the body, including but not limited to, those materials which produce liver damage, kidney damage, damage to the nervous system, act on the blood to decrease hemoglobin function, deprive the body tissue of oxygen, or affect reproductive capabilities, including mutations (chromosomal damage) or teratogens (effects on fetuses). OWNER. The owner of the dwelling, dwelling unit and/or rental unit, a mortgagee or vendee in possession, an assignee of rents, receiver, executor, trustee, or any other person, business, sole proprietorship, partnership, association, or corporation directly or indirectly in control of a building, structure or real property or their authorized agent. PERMITABLE QUANTITY. The minimum amount of hazardous or any other regulated material allowed to be stored or used at a property before an operations permit is required by Section 105.6. PILE. Independently stacked commodities possibly organized by separate spacers, dunnage, or pallets in which the demise of any storage container on a lower tier compromises the structural stability of the storage system. PLUG-IN. CO alarm with battery backup, installed by being plugged into an electrical outlet for primary power. PORTABLE TANK. A tank that is readily capable of being relocated within the facility, not permanently attached to immovable structure or ground, and not constructed of wood. POST OIL PROCESSING. The process of refining essential oils after the extraction, including but not limited to, dewaxing and winterization processes. PRESSURE VESSEL. Containers, intermediate bulk containers, processing vessels, and tanks that under normal conditions, are permitted to operate above 15 pounds per square inch gauge (psig; 103.4 kPa). PROCESS DESCRIPTION. An operational description such as a flow chart of the sequence of events required to convert raw materials from the state in which they enter the APBF through each development point until the finished products are derived. The process description identifies all input and output materials and includes quantities, concentrations, temperatures, pressures, types of equipment, systems, etc. at each development point using code-based terminology; e.g., “37 gallons of 55% ABV at standard temperature and pressure (STP)” vs. “all the high wines collected.” All systems and processes utilized to produce all intermediate and finished products are required to be included in the description. PROCESSING VESSEL. An open or closed vessel other than stills used in the manufacture of ethanol mixtures. Processing vessels include fermentation tanks, mash tuns, blending tanks, etc., but do not include long-term storage vessels such as vats or casks. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 38 PROPERTY. As used in this chapter, shall include private and public land in the undeveloped and developed state including the buildings, structures, paving and all other immobile improvements; natural features such as trees, shrubbery and similar botanical growth; and vehicles, vessels, equipment, materials and similar movable items located on them. RACK. Shelves or similar structural frame-supported system of tiers in which the demise of any storage container on a lower tier does not affect the structural stability of the storage system. RADIO FREQUENCY MAINTENANCE PLAN. The radio frequency maintenance plan is a document developed and distributed by the building owner for the purpose of maintaining the radio system from harmful interference generated on the property or otherwise under the control of the owner. RADIOACTIVE MATERIAL. Any material or combination of materials that spontaneously emits ionizing radiation. REGULATED MATERIAL. Any material materials regulated by the fire code for which an operations permit could be required including storage and/or use of hazardous materials, LPG, combustible dust operations. RELEASE/UNAUTHORIZED DISCHARGE. Any spilling, leaking, pumping, pouring, emitting, emptying, discharging, injecting, escaping, leaching, dumping, or disposing into the environment (including the abandonment or discharging of barrels, containers, and other receptacles containing any hazardous substances or pollutant or contaminant). REMOTE AREA. (c.f. NFPA 13). The specified floor area over which an assigned sprinkler density (in volume per minute per unit area) is required in the design of an automatic sprinkler system. RUNNER. A qualified person who responds to the location where a reported fire alarm system has been activated for the purpose of silencing, restoring, or confirming that the system is restored to a normal condition. SELF-SERVICE MOTOR FUEL-DISPENSING FACILITY. That portion of motor fuel-dispensing facility where flammable and combustible liquids, liquefied petroleum gas, compressed natural gas, or hydrogen motor fuels are dispensed from fixed approved dispensing equipment into the fuel tanks of motor vehicles by persons other than a motor fuel-dispensing facility attendant. SENSITIZER. A chemical that causes a substantial proportion of exposed people or animals to develop an allergic reaction in normal tissue after repeated exposure to the chemical. SINGLE-FAMILY DWELLING. Any improved real property used or intended to be used as a residence and that contains one dwelling unit. SINGLE STATION ALARM. A single device comprised of a sensor, alarm-initiating device, control components, and an alarm notification appliance. SINGLE STATION [CO] ALARM. A device comprised of a sensor, alarm-initiating device, control components, and an alarm notification appliance in one unit. SLEEPING ROOM. A room furnished with a bed and primarily used for sleeping purposes. SPIRIT. An ethanol mixture produced by the distillation of wine, wash, or a previously distilled spirit. STATIONARY TANK. A tank not intended to be relocated that is physically attached to immovable structure or ground. STILL. Any appliance is which distillation of an ethanol mixture is performed. For the purposes of Chapter 38, still includes pots, columns and condensing coils. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 39 STORAGE AREA. ABPF or portion thereof where ethanol mixtures or materials incorporated or utilized in the manufacture of ethanol mixtures are held for maturation, awaiting transport, or subsequent handling (c.f., use area). TANK. Any normally open or normally closed vessel having a capacity greater than 60 gallons (230 L) intended for storing or processing (but not transporting outside the facility) Class 1 Liquids, and equipped with provisions for emergency venting. TENANT. A person or legal entity who rents a dwelling unit from the owner for a fixed period of time usually under the terms of a lease or a similar legal entitlement or agreement. USE AREA. ABPF or portion thereof where ethanol mixtures or materials incorporated or utilized in the manufacture of ethanol mixtures are actively handled in processes such as fermentation, distillation, rectification, transportation, remixing, dispensing, bottling, blending, etc. (c.f., storage area). VAT (also FOUDRE). A stationary tank constructed primarily of wood. VESSEL. Used in Chapter 38 to reference reservoirs holding – unless otherwise noted – Class 1 Liquids including casks, containers, intermediate bulk containers, processing vessels, and tanks. WALL HYDRANT. Valved 2-1/2-inch (64 mm) exterior standpipe connection. WASH (also BEER, MALT LIQUOR). The ethanol mixture intended for distillation produced by the fermentation of mash or wort. For spirit production, wash and wine are analogous as precursors to distillation. WINE. An ethanol mixture produced by the fermentation of organic products, namely fruits, including agave. For spirit production, wine and wash are analogous as precursors to distillation. WINERY. An ABPF or portion thereof, including accessory uses, in which wine is produced. WORT. The sugar solution strained from mash for fermentation. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 40 CHAPTER 3 GENERAL REQUIREMENTS SECTION 301 GENERAL Section 301.2 Permits is replaced as follows: 301.2 Permits. Permits shall be required as set forth in Section 105.6 307-Open Burning, Recreational Fires and Portable Outdoor Fireplaces; Section 308-Open Flames; Mobile Food Preparation Vehicles. SECTION 302 DEFINITIONS Section 302.1 Definitions is amended to add the following term: 302.1 Definitions. The following term is defined in Chapter 2: ELECTROLYTE SECTION 304 COMBUSTIBLE WASTE MATERIAL Section 304.2.1 Required storage conditions is added as follows: 304.2.1 Required storage conditions. Combustible rubbish kept or accumulated within or adjacent to buildings, structures or residential dwelling units shall be in containers complying with this code, or in rooms or vaults constructed of non-combustible materials. Exception: Storage, accumulation, use and handling of combustible rubbish and waste, newspapers, magazines, etc. not in excess of 10 cubic feet aggregate. Section 304.3 Containers is replaced as follows: 304.3 Containers. Combustible rubbish, and waste material kept within or near a structure shall be stored in accordance with Sections 304.3.1 through 304.3.7. Section 304.3.5 Removal is added as follows: 304.3.5 Removal. Combustible rubbish stored in containers outside of noncombustible vaults or rooms shall be removed from buildings at least once each working day. Sections 304.3.6 Waste material handling operations and 304.6.1 Permits are added as follows: 304.3.6 Waste material handling operations. Occupancies exclusively performing commercial rubbish handling or recycling shall maintain rubbish or product to be processed or recycled as follows: 1. In approved vaults DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 41 2. In covered metal or metal-lined receptacles or bins, or 3. Completely baled and stacked in an orderly manner in an approved location. 304.3.6.1 Permits. A permit shall be required as set forth in Section 105.6 for a Waste Material Handling Plant. Section 304.3.7 Container location is added as follows: 304.3.7 Container location. A permit shall be required for the installation and maintenance of a waste receptacle with a capacity greater than 20 cubic feet. A site plan depicting the location of the waste receptacle must be submitted for approval prior to installation and anytime the waste receptacle is relocated. Toxic, explosive, flammable, chemical, infectious, radioactive materials and any other hazardous waste shall not be disposed of in the general waste dumpster(s). The waste receptacle(s) shall not be placed within fifteen (15) feet of combustible walls, openings, or combustible roof eave lines. The waste receptacle shall not obstruct emergency vehicular access or positioning for fire ground operations. SECTION 307 OPEN BURNING, RECREATIONAL FIRES AND PORTABLE OUTDOOR FIREPLACES Section 307.4 Location is replaced as follows, exceptions remain: 307.4 Location. When permitted by FMO Public Health & Environment (DPHE), the location for open burning shall be not less than 50 feet (15 240 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 50 feet (15 240 mm) of any structure. Section 307.4.3 Portable outdoor fireplaces is replaced as follows: 307.4.3 Portable outdoor fireplaces and chimeneas. Portable outdoor fireplaces and chimeneas are prohibited. SECTION 308 OPEN FLAMES Section 308.1.4 Open-flame cooking devices is replaced as follows: 308.1.4 Open-flame cooking devices. No gas-fired grills, charcoal grills, or other similar devices used for cooking, heating, or any other purpose, shall be used or kindled on any balcony or under any overhanging portion or within 10 feet (3 m) of any structure. Exceptions: 1. One- and two-family dwellings. 2. LP-gas burners having an LP-gas container with a water capacity not greater than 2.5 pounds [nominal 1 pound (0.454kg) LP-gas capacity]. Two extra 1 pound LP-gas containers may be stored on the balcony. 3. Listed natural gas appliances shall be permitted on balconies when installed in accordance with the International Fuel Gas Code and supplied by the building’s natural gas system. 4. Listed electric ranges, grills, or similar electrical apparatus shall be permitted. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 42 SECTION 309 POWERED INDUSTRIAL TRUCKS Section 309.3 Battery chargers is replaced as follows: 309.3 Battery-charging operations. Battery-charging operations shall be located in areas designated for such purpose. Where on-board chargers are used, charging shall be accomplished at locations designated for such purpose. 309.3.1 Battery chargers. Battery chargers shall be of an approved type. Combustible storage shall be kept a minimum of 3 feet (915 mm) from battery chargers. 309.3.2 Battery-charging areas. Battery-charging areas shall be kept free of extraneous combustible materials. Battery charging shall not be conducted in areas accessible to the public. 309.3.2.1 Battery-charging area fire protection. Where aggregate electrolyte capacity exceeds 100 gallons, battery-charging areas shall be protected with an automatic sprinkler system in accordance with NFPA 13. Exception: Automatic sprinklers shall not be required where the amount of electrolyte per battery-charging area is 100 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. 309.3.2.2 Battery-charging area construction. Where aggregate electrolyte capacity exceeds 100 gallons, battery charging areas shall be separated from the other portions of the building with a one- hour fire barrier constructed in accordance with Chapter 7 of the International Building Code. Exceptions: 1. One-hour fire barriers shall not be required where the amount of electrolyte per battery- charging area is 100 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. 2. In buildings that are protected throughout with an automatic sprinkler system in accordance with NFPA 13, one-hour fire barriers shall not be required where the amount of electrolyte per battery charging area is 200 gallons or less and the battery- charging areas are separated by a minimum of 75 feet. 309.3.2.3 Smoking prohibited. Smoking shall be prohibited in battery-charging areas. “No Smoking” signs shall be provided in the charging area in accordance with Section 310.3. 309.3.2.4 Neutralization. An approved method and materials capable of neutralizing a spill from the largest battery to a pH between 5.0 and 9.0 shall be provided. 309.3.2.5 Spill control. Each rack or tray of batteries shall be provided with a liquid-tight 4-inch minimum spill control barrier which extends at least one-inch beyond the battery rack in all directions. Alternative methods of spill control are subject to approval by the fire code official. Exceptions: 1. Spill control shall not be required where the amount of electrolyte per battery-charging area is 100 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. 2. In buildings that are protected throughout with an automatic sprinkler system in accordance with NFPA 13, spill control shall not be required where the amount of DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 43 electrolyte per battery charging area is 200 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. Section 309.4 Ventilation is replaced as follows: 309.4 Ventilation. Where aggregate electrolyte capacity exceeds 100 gallons, continuous ventilation shall be provided at a rate of not less than 1 cu-ft./min/sq. ft. of designated battery-charging area. Exceptions: 1. Ventilation systems shall not be required where the amount of electrolyte per area is 100 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. 2. In buildings that are protected throughout with an automatic sprinkler system in accordance with NFPA 13 ventilation systems shall not be required where the amount of electrolyte per battery charging area is 200 gallons or less and the battery-charging areas are separated by a minimum of 75 feet. Section 309.8 Signage is added as follows: 309.8 Signage. Doors into battery-charging areas shall be provided with approved signs. The signs shall state that: 1. The room contains energized battery systems. 2. The room contains energized electrical circuits. 3. The battery electrolyte solutions are corrosive liquids. SECTION 311 VACANT PREMISES Section 311.1.1 Abandoned premises is amended by removing the reference to the International Property Maintenance Code SECTION 315 GENERAL STORAGE Section 315.4.3 Pile size, aisles and driveways is added as follows: 315.4.3 Pile size, aisles and driveways. Combustible material shall be piled with due regard to stability of piles and in no case higher than twenty (20) feet. When the area used for outside storage exceeds fifty (50) feet but is less than one hundred fifty (150) feet, in any dimension, aisles of not less than eight (8) feet clear width shall be provided between piles. When the area used for outside storage exceeds one hundred fifty (150) feet in any dimension, a driveway between and around piles shall be at least fifteen (15) feet in width and maintained free of rubbish, equipment or other articles or materials. Driveways shall be so spaced that a maximum grid system unit of fifty (50) feet by one hundred fifty (150) feet is produced. SECTION 316 HAZARDS TO FIRE FIGHTERS Section 316.7 Fences, walls, retaining walls and similar barriers is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 44 316.7 Fences, walls, retaining walls, and similar barriers. The use of barbed wire or any other sharp- pointed material, devices or features that deliver a physical or health hazard on, as, or on top of, fences, walls, retaining walls, or similar barriers, regardless of height, is prohibited except as provided in accordance with Section 316.7.1. Exception: Barbed wire may be installed where approved by the fire code official and a permit is obtained in accordance with Section 105.6. Section 316.7.1 Electrified fences is added as follows: 316.7.1 Electrified fences. Electrified fences may be permitted by specific approval of the fire code official. All fences shall be designed in accordance with Sections 1609 and 1807 of the International Building Code. Only fences powered by a 12- volt direct current (DC) power source shall be considered. Section 316.8 Confined spaces is added as follows: 316.8 Confined spaces. Tanks that contain materials that would not contain enough oxygen to support life or contain a toxic atmosphere shall have at each entry point; a warning sign posted indicating the need for procedures for safe entry into confined spaces. SECTION 317 ROOFTOP GARDENS AND LANDSCAPED ROOFS Section 317.1 General is replaced as follows: 317.1 General. Rooftop gardens and landscaped roofs shall be installed and maintained in accordance with Sections 317.2 through 317.6 and Section 1505 and 1507.16 of the International Building Code and shall be installed in accordance with ANSI/SPRI-VF-1 and the administrative and design requirements for vegetated roofs in the Englewood Community Development and Building Department. Section 317.1.1 Vegetated roofing system materials is added as follows: 317.1.1 Vegetated roofing system materials. In buildings of Type V, IV, III, or II-B construction, the vegetated roofing system materials shall contain assemblies that include modular trays or containers that do not exceed 4 square feet per tray or container, weigh no more than 180 pounds per tray or container when fully saturated and vegetated, and do not present excessive burning characteristics as evaluated by the fire code official. Exception. The fire code official may allow vegetated roofing system materials that do not contain assemblies that include modular trays or containers when an owner can provide sufficient evidence that the rooftop garden or landscaped roof allows fire fighters or emergency responders to conduct ventilation during firefighting efforts and post-fire salvage and overhaul operations. Section 317.6 Fire access is added as follows: 317.6 Fire access. All roofs containing vegetated areas shall be afforded access via exit stairways and fixed permanent ladders to upper roofs. The exit stairways and fixed permanent ladders to upper roofs shall be located within 230 feet from any vegetated area. Access points shall be separated by a minimum of 10 feet from the vegetated areas. Exceptions: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 45 1. In buildings less than 4 stories in height, exit stairways and fixed permanent ladders need not be provided, but there shall be a minimum 8-foot-wide clear perimeter around the edges of the roof. 2. In existing buildings, the fire code official shall approve methods of access to all vegetated areas. SECTION 319 MOBILE FOOD PREPARATION VEHICLES Section 319.4.2 Fire extinguisher is replaced and new subsections are added as follows: 319.4.2 Fire extinguisher. Portable fire extinguishers shall be provided in accordance with Section 319.4.2.1 through 319.4.2.2 319.4.2.1 Fire extinguisher mounting location. A 2A:10BC fire extinguisher shall be mounted in each vehicle. 319.4.2.2 Fire extinguishers for cooking operations. If grease or grease-laden vapors are produced during cooking operations, a Class K extinguisher shall also be required. Section 319.8.1 Maximum aggregate volume is replaced as follows: 319.8.1 Maximum aggregate volume. The maximum aggregate capacity of LP-gas containers transported on the vehicle and used to fuel cooking appliances only shall not exceed 80 pounds (36 kg) propane capacity. Section 319.8.2 Protection of container subsections are added as follows: 319.8.2.1 Trailer tongue mounting. LP-gas containers may be mounted on the A frame structure of the tongue of the trailer with propane brackets that prevent any movement. 319.8.2.2 Rear of vehicle mounting. LP-gas containers mounted on the corners or rear of the vehicle shall be enclosed in an impact resistant cage to prevent damage from vehicular accident and have the bottom of the LP-gas containers no lower than 28 inches above bumper or A-frame structure. 319.8.2.3 Ventilation. LP-gas containers installed in a compartment on the rear of the vehicle or tongue of a trailer shall be ventilated at the top and bottom of the compartment. 319.8.2.4 Access door labeling. Access hatches and doors for concealed LP-gas container storage shall be labeled with DOT-style placards with an identification code of "1075" and a decal that states "flammable". 319.8.2.5 Roof mounting. LP-gas containers shall not be mounted directly on roofs. 319.8.2.6 Front of vehicle mounting. LP-gas containers shall not be mounted ahead of the front axle on a self-powered vehicle. Section 319.8.4.1 Gas pipe installation is added as follows: 319.8.4.1 Gas pipe installation. Installation of gas piping shall comply with all of the following: 1. LP-gas piping installed beneath the vehicle shall be painted black iron pipe with a minimum wall thickness of 0.049 inches (1.2 mm). Exception: Approved rubber coated flex connectors (UL-21 stainless steel) may be used to connect to fuel sources or to transition to a different support structure in order to isolate strain on the rigid system. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 46 2 Flexible connector. A LP-gas flexible connector, no longer than 5 feet, shall be installed between the regulator and the LP-gas container. 3 The LP-gas flexible connector and gas valve shall not extend past the body lines of the vehicle. Gas lines should preferably be installed down the center of the vehicle and away from the tire area. 4 All piping shall be installed outside the vehicle. Piping shall be under the vehicle and below any insulation or false bottom. When piping passes through sheet metal or a structural member, a rubber grommet or equivalent protection shall be installed to prevent chafing. 5 Gas piping shall be installed to enter the vehicle through the floor directly beneath or adjacent to the appliance served. 6 If a branch line is installed in gas piping, the tee connection shall be in the main gas line under the floor and outside the vehicle. Section 319.10.1 Exhaust system is replaced as follows: 319.10.1 Exhaust system. The exhaust system, including hood, grease-removal devices, fans, ducts and other appurtenances, shall be inspected and cleaned in accordance with Section 607.3 at the interval for high-volume cooking operations. Section 319.10.2 Fire protection systems and devices is replaced as follows: 319.10.2 Fire protection systems and devices. Fire protection systems and devices shall be maintained in accordance with Section 901.6. Hood extinguishment systems shall be maintained and inspected in accordance with Section 904.12.5. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 47 CHAPTER 4 EMERGENCY PLANNING AND PREPAREDNESS SECTION 401 GENERAL Section 401.1 Scope is amended by deleting the Exception. Section 401.3 Emergency responder notification (subsections 401.3.1 through 401.3.3 are deleted) is replaced as follows: 401.3 Emergency responder notification. In the event of an emergency, including but not limited to, unwanted fire, hazardous materials discharge, medical incident, or environmental calamity including utility malfunction, occurs on a property, the owner, occupant, or other person in responsible charge of the property or portion thereof, including tenants employees and property or equipment maintenance personnel, shall immediately report the emergency to 911 unless the Fire Department has approved an alternative emergency procedure for the event. Building employees, tenants and maintenance personnel shall implement the appropriate emergency plans and procedures. No person shall, by any means, require or otherwise purposely cause any delay in the reporting of an emergency. Section 401.3.1 Evidence of emergency is added as follows: 401.3.1 Evidence of emergency. Upon discovery of evidence of an unwanted fire, hazardous materials discharge, medical incident, or environmental calamity, even though it appears to have been extinguished or otherwise stabilized, the owner, occupant, or any other person in responsible charge of the property or portion thereof, including tenants, employees and property or equipment maintenance personnel shall immediately notify the Fire Department of the evidence including what is known of the location and circumstances. Such evidence shall not be disturbed, thus preserving data for the Fire Department to conduct an investigation. 401.3.2 Elevator entrapment communication procedures for new, altered, and existing conveyances. Upon an entrapped party’s activation of the elevator car 2-way communication system required by ASME A17.1, the authorized personnel receiving the call (call recipient), shall request the following information: 1. The number of occupants in the car; and 2. Whether any occupants are in medical distress; and 3. Whether smoke or fire is apparent; and 4. Whether any occupant has a physical or mental handicap If the response to 2, 3 and 4 above are all negative and the call recipient is located at a call center remote from the elevator location, the call recipient shall immediately notify the appropriate emergency contact for the property. Once known, the call recipient shall provide the trapped party with the estimated time of arrival of assistance. The call recipient shall immediately notify the Fire Department if any of the following occur: 1. The response to either 2, 3 or 4 above is affirmative. 2. Communication with a trapped party is lost prior to obtaining the information required above and cannot be re-established within 5 minutes. 3. Receive a second call from the same elevator within 5 minutes of the first call. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 48 4. The expected authorized building or elevator contractor or technician is unable to respond within 20 minutes of the first notification of entrapment. 5. There is contact from the same stalled elevator 20 minutes after the original call indicating that help has not arrived. 401.3.3 Procedures. for new, altered, and existing conveyances, written emergency evacuation procedures shall be made and kept on the premises. The procedures shall identify the hazards and safety precautions required in evacuating passengers from a stalled elevator. After responding to a trapped party incident, the fire department shall be notified immediately if any of the following occur; 1. Authorized building personnel responding to the incident determine that the elevator platform is not securely established within 7 inches of a landing. 2. Qualified elevator personnel responding to the incident determine that the elevator platform cannot be securely established within 18 inches of a landing. 3. It is found by any responding party that; any trapped occupants are in medical distress, smoke or fire is apparent and/or any occupant has a physical or mental handicap. Any personnel responding to an elevator trapped party incident may contact the fire department at any time during the event as they deem necessary. 401.3.4 Records. For new, altered, and existing conveyances, a record of authorized and sufficiently trained personnel responsible to respond to a trapped party elevator incident shall be maintained on the premises. Records of elevator entrapment incidents shall be maintained on site to include; date, time of responder arrival, car designation, number of trapped occupants, event resolution, cause, and remedial action taken. Section 401.5 Making false report is replaced as follows: 401.5 False alarm. No person shall deliberately or maliciously report a fire or unauthorized discharge of hazardous materials when that person knows that no fire or discharge exists. The person responsible for the false alarm shall reimburse the City for the total cost of responding to the false alarm. Section 401.9 Misleading information is added as follows: 401.9 Misleading information. It shall be unlawful for a person to willfully make any false, fraudulent, misleading, or unfounded report or statement or to willfully misrepresent any fact with the intention of misleading any Fire Department personnel or interfering with Fire Department operations. SECTION 402 DEFINITIONS Section 402.1 Definitions is amended by adding the following term: 402.1 Definitions. The following term is defined in Chapter 2: PROPERTY SECTION 403 EMERGENCY PREPAREDNESS REQUIREMENTS Section 403.8.1.6 Resident participation in drills is replaced as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 49 403.8.1.6 Resident participation in drills. Emergency evacuation drills shall involve the actual evacuation of residents to a selected assembly point. Section 403.12.2 Public safety plan for gatherings is amended by adding the following to the list of items required to be addressed in the public safety plan: ● Fire hydrant locations. ● Local fire protection (suppression and alarm). ● Public assembly areas. ● Emergency procedures and employee training. ● All other conditions possibly hazardous to life, property or public welfare in the occupancy. Section 403.13 Facility manager certification is added as follows: 403.13 Facility manager certification. All personnel responsible for facility maintenance, fire safety emergency procedures, evacuation plans, evacuation drills, employee training and response procedures, hazard communication, resident training, tenant identification, emergency response team formulation and training, hazardous materials management plans, hazardous materials inventory statement, etc. shall complete a training course and shall have a current certification SECTION 404 FIRE SAFETY EVACUATION AND LOCKDOWN PLANS Section 404.2 Contents is replaced as follows: 404.2 Contents. Fire safety and evacuation plan contents shall be in accordance with IFC Sections 404.2.1, 404.2.2 as amended and Denver Fire Department policy on Emergency Procedures and Emergency Evacuation. Section 404.2.2 Fire safety plans is amended by adding item 8 as follows: 8. Provide a description of the building’s life safety systems including fire alarm, fire sprinkler (including special suppression, standpipes, fire pumps, etc.), smoke control, elevator recall, areas of refuge, emergency power, etc. SECTION 405 EMERGENCY EVACUATION DRILLS Section 405.1 General is amended by adding the following after the last sentence: It shall be unlawful to refuse to participate or to interfere with Fire Marshal’ Office personnel conducting an emergency evacuation drill. Section 405.10 Extent of evacuation is added as follows: 405.10 Extent of evacuation. Fire and evacuation drills shall include the complete evacuation from the building of all persons required to participate. It shall be a violation of this code to refuse to participate or to interfere with the Fire Marshal’s Office personnel conducting a fire and evacuation drill. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 50 CHAPTER 5 FIRE SERVICE FEATURES SECTION 502 DEFINITIONS Section 502.1 Definitions is amended by adding the following term: 502.1 Definitions. The following term is defined in Chapter 2. LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS SECTION 503 FIRE APPARATUS ACCESS ROADS Section 503.1.1 Buildings and facilities is amended by adding the following to the end of the last sentence: …and the interior of all courts (also see Section 504.5). The approved route shall be not less than a 3-foot wide access walkway leading from fire apparatus access roads to all portions of the exterior walls of the first floor. Section 503.1.1 Buildings and facilities, Exception 1, Item 1.1 is replaced as follows: 1.1 Where a building is equipped throughout with an approved automatic sprinkler system installed in accordance with Sections 903.3.1.1 or 903.3.1.2, the 150-foot dimension may be increased to 250 feet. Section 503.2.1 Dimensions is replaced as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet, exclusive of shoulders. Existing fire apparatus access roads shall maintain their width but shall b not less than allowed in Table 503.2.1. Approved security gates shall comply with Section 503.6 and fire access roads shall have an unobstructed vertical clearance of not less than 13 feet 6 inches. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 51 TABLE 503.2.1 MINIMUM CLEAR STREET WIDTHS FOR EXISTING EMERGENCY FIRE APPARATUS ACCESS ROADS Type of Building/Structure to Be Served by Existing Fire Apparatus Access Road Minimum Unobstructed Width1,2 Single-family detached buildings, two-dwelling unit attached buildings, or townhouses with alleys 14 feet Single-family detached buildings, two-dwelling unit attached buildings, or townhouses without alleys but with driveways that extend to the road 16 feet Single-family detached buildings, two-dwelling unit attached buildings, or townhouses without alleys or driveways that extend to the road 16 feet Multi-family residential buildings, three (3) stories or less AND with 15 or less dwelling units per building3 16 feet Multi-family non-high-rise buildings, four (4) or more stories OR with 16 or more dwelling units per building3 Non-residential non-high-rise buildings/structures 20 feet with an additional 40-feet (length) of “no parking” fire lane at the main entrance of the building. Where 25 feet or greater unobstructed width is provided, a 40-foot “no parking” fire lane is not required. High-rise buildings/structures3 20 feet with an additional 40 feet (length) of “no parking” fire lane at the main entrance of the building. Where building/structure is located on a corner, 20 feet is required on 2 sides of the building. Where 25 feet or greater unobstructed width is provided, a 40-foot “no parking” fire lane is not required. 1 Based on 8 ft. parking and 18-inch curb-to-tire widths in accordance with City of Englewood standards, unless a 7 ft parking lane is allowed by Englewood Fire Marshal’s Office when existing streets are 32 ft. wide or less. 2 Where a fire apparatus access road serves two or more uses, the larger required minimum unobstructed width shall be maintained. 3A multi-family building with commercial on the first floor shall comply with the non-residential non-high-rise minimum clear width requirement, except that high-rise buildings/structures shall comply with high-rise minimum clear width requirement. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 52 Section 503.2.3 Surface is replaced to read as follows: 503.2.3 Surface. All–weather permanent fire access surfaces shall be asphalt, concrete, or other approved surface. Temporary fire access surfaces during construction are permitted to consist of a gravel road base or asphalt or other approved surface. See Section 1607 of the International Building Code for Fire Department apparatus loading. Section 503.2.4 Turning radius is replaced as follows: 503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be a minimum of 25 feet inside and 50 feet outside. Section 503.2.5 Dead ends is replaced as follows: 503.2.5 Dead ends. Dead-end fire apparatus access roads in excess of 150 feet (45 720 mm) in length shall be provided with an approved area for turning around fire apparatus in accordance with Figure 503.2.5. Figure 503.2.5 Dead-end fire apparatus access road turnaround is added as follows: FIGURE 503.2.5 DEAD-END FIRE APPARATUS ACCESS ROAD TURNAROUND Section 503.2.6.1 Grade-level structural deck is added as follows: 503.2.6.1 Grade-level structural deck. See Chapter 16 of the International Building Code for structural loading. All structural decks shall have permanent, all-weather load posting sign(s) indicating gross maximum vehicle loads, maximum tandem axle load and maximum single-axle load. Signs shall be posted in a conspicuous location at each deck entrance and shall be maintained by the owner at all times.” Section 503.2.7 Grade is replaced in its entirety as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 53 503.2.7 Grade. The grade of the fire apparatus access road shall not exceed 7% (4 degrees). All other criteria shall meet Transportation Engineering design criteria as specified by Englewood Public Works. Section 503.2.8 Angles of approach and departure is replaced in its entirety as follows: 503.2.8 Angle of approach and departure. The angles of approach and departure for fire apparatus access roads shall not exceed 6 degrees or as approved by the fire code official. Section 503.3 Marking is amended by adding the following sentence at the end of the section: Signs shall have a 12-inch by 18-inch dimension and shall comply with the Traffic Engineering Services (Public Works) Sign Manual as depicted in Figure 503.3 FIGURE 503.3. FIRE LANE SIGNS Sections 503.6.1 Width and 503.6.2 Approved means of emergency operation are added as follows: 503.6.1 Width. Security gates across a fire apparatus access road shall be a minimum 16 feet wide. 503.6.2 Approved means of emergency operation. Secured gates across a fire apparatus access road shall be provided with one or more of the following features: 1. Key box in accordance with Section 506. 2. An approved lock 3. Chains used to secure gates shall be ¼-inch maximum, non-case hardened steel. 4. Emergency operation approved by fire code official. SECTION 504 ACCESS TO BUILDING OPENINGS AND ROOFS Section 504.1 Required access is amended by adding the following at the end of the paragraph: A five-foot wide (1524 mm) access walkway leading from fire apparatus access roads to required exterior openings shall be provided. The location and configuration shall be approved by the fire code official. Exception: The fire code official is permitted to require a lesser width. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 54 Section 504.4 Roof hatches is added as follows: 504.4 Roof hatches. See Section 1011.12.3 of the International Building Code. Section 504.5 Courts is added as follows: 504.5 Courts. For buildings of Type III, IV, or V construction, access to grade level courts shall be provided from two remote locations. Access points shall be comprised of open-air breezeways not less than 6 feet (1829 mm) wide and not less than the height of the first story of the building. The breezeways shall lie perpendicular and shall have direct view of the court from the frontage location. Where access gates are afforded, a key box shall be placed at each entrance. Locations and configurations shall be approved by the fire code official (see also Sections 202, 1004.7, 1028.4 of the International Fire Code and Section 1205.3 of the International Building Code). SECTION 505 PREMISES IDENTIFICATION Section 505.1 Address identification is replaced and an exception added as follows: 505.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than six inches (153 mm) high with a minimum stroke width of 3/4 inch (19.1 mm). Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response Exception: Existing dwellings regulated by the International Residential Code. SECTION 507 FIRE PROTECTION WATER SUPPLIES Section 507.2 Type of water supply is replaced as follows: 507.2 Type of water supply. A water supply shall be connected to a reliable public water works system. Section 507.2.1 Private fire service mains is deleted in its entirety. Section 507.2.2 Water tanks is replaced as follows: 507.2.2 Water tanks. New water tanks for fire protection shall be prohibited. Exceptions: 1. Water tanks for fire protection, when approved by the fire code official, are permitted for NFPA 13D systems in accordance with Section 903.3.1.3 or Section P2904 of International Residential Code. 2. Existing water tanks for fire protection that were previously approved by the Fire Department. These tanks shall be inspected, tested and maintained in accordance with NFPA 25. Section 507.2.3 Water supply serving high-rise buildings is added as follows: 507.2.3 Water supply serving high-rise buildings. High-rise buildings shall be supplied by connections to a minimum of two public water mains located in different streets. Separate supply piping shall be DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 55 provided between each water main connection and the building. Backflow prevention devices and flow switches shall be provided in accordance with Section 912.6 at each water main entry to the structure. Each fire main shall be sized to meet the full demand of the fire protection system at each connection to achieve redundancy. Exception: Where approved by the fire code official, high-rise buildings without access to different water mains shall have two fire main connections to the same public main. The public main shall have valves such that an interruption of one water source can be isolated so that water supply will continue without interruption through the other connection. The two required fire mains shall have a minimum separation distance from each other of five (5) feet at all points from the public main to the building. Each fire main shall be sized to meet the full demand of the fire protection system at each connection to achieve redundancy. Section 507.3 Fire flow is replaced as follows: 507.3 Fire flow. Fire flow requirements shall be as determined in International Fire Code Appendix B,. Each new or existing fire hydrant as required in accordance with International Fire Code Appendix C, , shall be capable of providing not less than 1500 GPM at 20 PSI residual pressure. Section 507.5.1 Where required is replaced as follows: 507.5.1 Where required. See Section 507.3. Section 507.5.3 Private fire service mains and water tanks is replaced as follows: 507.5.3 Private fire service mains and water tanks. Private fire service mains and water tanks are not permitted except for existing systems previously approved by the Fire Department or as allowed in Section 507.2.2. Existing private service mains and water tanks shall be periodically inspected, tested and maintained in accordance with NFPA 25 at the following intervals: 1. Private fire hydrants (all types): Inspection annually and after each operation; flow test and maintenance annually. 2. Fire service main piping: Inspection of exposed, annually; flow test every five years. 3. Fire service main piping strainers: Inspection and maintenance after each use. Section 507.5.5 Clear space around hydrants is replaced as follows: 507.5.5 Clear space around hydrants. A five-foot (1524 mm) clear space shall be maintained around the circumference of fire hydrants, except as otherwise required or approved. SECTION 508 FIRE COMMAND CENTER Section 508.1 General is replaced as follows: 508.1 Fire command center (FCC). Where required by Section 907 or 909, buildings shall be provided with an FCC in accordance with this section. No piping, ducts or equipment foreign to required fire operations shall be permitted to enter, pass through or be installed within the FCC. Scale drawings of the FCC showing the location of all equipment and features, in plan and elevation views, shall be submitted for approval prior to installation. Section 508.1.1 Location and access is replaced as follows: 508.1.1 Location and access. The FCC shall: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 56 1. Be on the ground floor, and 2. Have a secured entrance directly accessible to and in immediate proximity of the main building entrance. 3. Have access within the building to all fire service access elevators. Exception: Unless otherwise approved by the fire code official. Section 508.1.2 Separation is replaced as follows: 508.1.2 Separation. To meet the system survivability requirements of NFPA 72, the FCC shall be separated from the remainder of the building by not less than a 2-hour fire barrier constructed in accordance with Section 707 of the International Building Code or a horizontal assembly in accordance with Section 711 of the International Building Code or both. Section 508.1.6 Required features is replaced as follows: 508.1.6 Required features. The FCC shall contain the following: 1. Emergency voice/alarm communication system unit in accordance with Section 907.5.2.2. 2. Fire Department communication system in accordance with Section 907.2.12.2. 3. Fire alarm control unit and annunciator in accordance with Sections 907.1.5 and 907.6.4.1. 4. Elevator status/control panel in accordance with Section 907.2.12.7. 5. Firefighter’s smoke control panel in accordance with Section 909.8. 6. Manual controls for simultaneously unlocking stairway and refuge area doors in accordance with Section 1010.1.9.12 of the International Building Code. 7. Emergency generator status panel in accordance with Section 907.2.12.8. 8. Telephone with controlled access to a public telephone network. 9. Fire pump remote status panel in accordance with Section 907.2.12.9. 10. Building as-built construction plans indicating typical floor and roof plans, detailing the building core, means of egress, fire protection system drawings, firefighting equipment, fire department access, interior generator and utility shut-off locations. These drawings shall be protected from damage and immediately accessible to the fire department. A storage rack to support these drawing shall be provided. 11. Building site plan with “North” orientation, local street intersection, fire hydrants, Fire Department connections, building entries, exterior generator and fuel locations and exterior utility shut-off locations. 12. Work table 3’ x 5’ and chair. 13. Public address system equipment, where specifically required by other sections of this code. 14. A key vault approved by the fire department to house keys to access mechanical and electrical equipment. 15. Two-way communication required by Sections 1009.6.5, 1009.8, 1010.1.9.13.7 Item 3(b), and 3008.6.6 of the International Building Code and two-way communication system required for elevator communication in accordance with ASME A17.1. 16. Multi-level lighting control. Separately switched lamps or dimming control is acceptable. Dimming DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 57 of fluorescent fixtures shall be by EMI/RFI shielded devices. 17. Mass Notification System (MNS) equipment. 18. Heating/cooling zone or system. 508.1.7 Heating/cooling zone or system for FCC. A separate heating/cooling zone or system operating continually shall be provided for the Fire Command Center. Section 508.2 Fire command room is added as follows: 508.2 Fire command room. Where required by Section 907.5.2.2.8, in a building with any emergency voice/alarm communication system or in a building where the owner requests that the fire alarm and life safety equipment not be installed in the lobby of the building, a fire command room shall be provided. The room shall be not less than 48 square feet (4.46 m2) with a minimum dimension of 8 feet (2.44 m), but not less than that required to accommodate the equipment on one wall. A minimum clear dimension of 6 feet (1.82 m) shall be provided in front of the equipment. The room shall be separated from the remainder of the building by not less than a 1-hour fire barrier constructed in accordance with Section 707 of the International Building Code, or horizontal assembly constructed in accordance with Section 711 of the International Building Code, or both. The fire command room shall be located in accordance with Section 508.1.1 and shall contain the following equipment, where provided: 1. Fire alarm control unit. 2. Emergency voice/alarm communication equipment. 3. Smoke control panel. 4. Emergency/Standby generator status panel. 5. Fire Pump remote status panel. 6. MNS equipment. 7. Two-way communication required by Sections 1009.6.5, 1009.8, 1010.1.9.13.7 Item 3(b), and 3008.6.6 of the International Building Code and two-way communication system required for elevator communication in accordance with ASME A17.1. The building annunciator shall be located as approved by the fire code official. Exception: Unless approved by the fire code official. SECTION 509 FIRE PROTECTION AND UTILITY EQUIPMENT IDENTIFICATION AND ACCESS Section 509.3 Access to fire pumps is added as follows: 509.3 Access to fire pumps. Access to fire pumps in new buildings shall be located at grade level with the level having direct access to outside or located one level below grade. Pump rooms that are located one level below grade shall be placed such that there are no intervening rooms between the stairway door serving that level and the pump room. Door serving the pump room shall be within 25 ft. of the stairway door. The stairway that serves the lower level shall exit directly to outside. Where a dedicated stairway is provided to access the pump room and mechanical rooms, stairway width shall not be less than 36 inches. Location of the fire pump room is subject to approval by the fire code official. Section 510 Emergency Responder Radio Coverage is replaced as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 58 SECTION 510 EMERGENCY RESPONDER RADIO ENHANCEMENT COVERAGE SYSTEM (RES) 510.1 Where required. Buildings shall have approved radio coverage in accordance with Section 510 for emergency responders as follows: 1. High-rise buildings 2. Underground buildings (constructed in accordance with Section 405 of the International Building Code) 3. Airport buildings and structures 4. In accordance with Section 510.1.1 510.1.1 Compliance testing. New buildings of 50,000 gsf or more and all new Group E and I occupancies over 10,000 gsf on any story shall be tested upon substantial construction completion and where lacking required coverage, shall be provided with an RES. Buildings having compliant initial radio coverage shall be tested every five years thereafter in accordance with Section 510.2.1.1 for continued adequacy of emergency responder radio communications coverage. Buildings failing to meet the minimum coverage requirements after testing shall be provided with a RES in accordance with Section 510. Where it is determined by the fire code official the radio coverage system is not needed, written documentation of the adequacy of existing radio coverage shall be maintained on site. 510.1.2 Emergency responder radio coverage in existing buildings. For existing high-rise, underground buildings, I-1, I-2 and I-3 occupancies and airport buildings, when undergoing an upgrade to install a Mass Notification System (MNS) or complete fire alarm head-end equipment replacement, the building shall be tested to Section 510 for public safety radio coverage and where deficient, RES coverage shall be provided. Buildings with currently acceptable signal strength shall be retested at five- year intervals in accordance with Section 510.2.1.1 to ensure continued compliant radio coverage. Where it is determined by the fire code official the radio coverage system is not needed, written documentation of the adequacy of existing radio coverage shall be maintained on site. 510.2 Emergency responder radio enhancement system coverage in buildings. Where required by Section 916, buildings shall have approved radio coverage for emergency responders within the building based upon the existing coverage levels of the communication system at the exterior of the building. Systems shall operate at the frequency of 806-816MHz and 851-861MHz. This section shall not require improvement of the existing communication system. Active components Bi-directional Amplifiers (BDA), Distributed Amplifier System (DAS) controller, UPS), of the RES system shall be installed in a room separated from the remainder of the building by a minimum 1- hour fire-resistance rated fire barrier constructed in accordance with Section 707 of the International Building Code or a one-hour fire resistance rated horizontal assembly constructed in accordance with Section 711 of the International Building Code or both. The Emergency Responder Radio Enhancement Coverage system shall be a standalone system totally dedicated to public safety and no components of this system may be shared with any other radio or cell phone systems. Modification, alteration, repair or removal of any RES system or component is specifically prohibited without the approval of the fire code official. Exception: Where it is determined by the fire code official that current radio coverage within the building is adequate, written documentation of the compliance of radio coverage shall be maintained on site. See Section 916 for testing requirements. 510.2.1 Coverage Requirement. The radio system control channel signal level shall exceed -100 dBm at 95% or more of the locations measured within each floor plate. Equivalently, the service area reliability shall be 95% or greater on each floor of the structure and parking areas. All designated areas of refuge, DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 59 Fire Command Centers, stairwells, main building lobbies and elevator lobbies shall have 100% signal coverage of -100dBm or stronger. 510.3 Radio systems. The RES system shall meet the coverage requirements defined in this section, and comprise one of following; bi-directional amplifiers with radiating (“leaky coax”) cable, a discrete distributed antenna system or other fire department approved equivalent technology. Radio communications systems shall only operate on the frequency range of 806-816MHz and 851-861MHz. All active electronic components in the RES system shall be powered by a dedicated uninterruptible power source (UPS) with a minimum backup time of 12 hours with all amplifiers at rated output. The UPS input circuit shall be a dedicated circuit and any cord and plug connection(s) shall be secured in an approved cabinet to prevent inadvertent disconnection. The circuit shall also be connected to the emergency generator where one is provided. The circuit shall be provided with a “lock-on” device. The RES system shall be maintained in an operative condition at all times. Exceptions: 1. In buildings provided with an emergency generator in accordance with Section 604, UPS minimum battery capacity shall be permitted to be 4 hours. 2. Where a legally required standby generator is installed in accordance with Section 604, and the UPS input circuit is automatically transferred to the generator source, UPS minimum battery capacity shall be permitted to be 4 hours. 510.3.1 Requirements. The system shall effectively operate throughout the structure in accordance with this section. Radio communication coverage is required throughout parking garages and all areas below grade. Acceptance of the installed communication system shall be based upon Fire Department approval of the acceptance test as described below. All RES equipment shall be FCC compliant. 510.3.1.1 Acceptance test. Test procedures shall comply with the Denver Fire Department and Englewood Police Department. Measurement locations shall be uniformly distributed to the extent practical. There shall be at least 10 sampling measurements per 4,000 sq. ft. (one per every 20 foot X 20 foot square) of gross building area. Adequate radio coverage shall be determined for the structure and parking areas separately. Elevators, stairways and enclosed areas within each grid must be included in the testing. Where grid points exhibit marginal RF signal levels, DFD personnel or an approved party will perform a radio test to determine if intelligible transmissions can be made through the enhanced radio system to and from the individual grid point without the need for retransmission. If this test fails, communications will be considered inadequate at that grid location and that grid will have failed to meet the required signal level. 510.3.1.2 Periodic testing. RES shall be tested annually and at five-year intervals. Additional testing may be required by the department where building modifications have the potential to degrade system performance. 510.3.1.3 Failure detection. RES equipment, including the RES amplifier and DAS controller if available, shall have failure detection circuitry which provides detection of mechanical, electrical and power failure of these components, as well as oscillation detection capability which will reduce the amplifier output to zero in the event of system oscillation. Detection of any failure output from an amplifier or main DAS controller, if provided, shall annunciate at the building fire alarm panel and result in a distinct local audible notification and transmission of a supervisory signal to the central monitoring station. RES system repairs shall be accomplished within 72 hours. 510.3.1.4 Permits. A construction permit is required prior to installation or replacement of any RES. Submittal and approval of shop drawings are required to obtain a permit. Permits shall only be issued to companies possessing a current contractor’s license. An annual fire permit for the RES shall be obtained and maintained current by the building owner. Alterations, modifications, repairs and required testing of RES shall require an operational permit issued by the Fire Marshal’s Office DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 60 to the licensed contractor performing the work. 510.3.1.5 Information signs. A legible sign stating “THIS BUILDING IS EQUIPPED WITH A PUBLIC SAFETY RADIO REPEATER SYSTEM” shall be conspicuously posted at the fire alarm panel. An additional sign stating, “THIS BUILDING IS EQUIPPED WITH A PUBLIC SAFETY RADIO REPEATER SYSTEM-- DO NOT TAMPER WITH OR DISCONNECT,” shall be located at each RES amplifier location. Signs shall be constructed of plastic or metal and shall be approved by the fire code official. 510.3.1.6 Shop drawings. Shop drawings, including RF grids, shall be submitted in accordance with Appendix N and approved prior to installation of any RES. Drawings shall be a deferred submittal in accordance with Section 133 of the International Building Code. Documents shall be of sufficient clarity and detail to fully describe the proposed installation and equipment. Handwritten notes or comments on drawings are not acceptable. 510.4 Wiring methods. Installation wiring for radio communications shall comply with the manufacturer’s recommendations, equipment listings. NFPA 72 and NFPA 70 (NEC). Radiating cables shall be FCC type approved and installed using manufacturer’s specifications to secure cables to the supporting structure. All terminations shall be made with manufacturer’s approved devices. Cable cuts shall be made with manufacturer approved tools and methods. Limited-use cable is not permitted. All membrane or through penetrations shall comply Section 714 of the International Building Code. 510.4.1 RES riser cable in high rise buildings. In high rise buildings, installation of riser cable and amplifiers for distributed antenna systems shall be located in stacked electrical rooms or telephone rooms or shaft enclosures separated from the remainder of the floor by not less than a one-hour fire resistance rated fire barrier shaft constructed in accordance with Section 707 or 713 of the International Building Code. Wiring runs from an RES unit amplifier to a riser shall be separated from the remainder of the building by a minimum 1-hour fire-resistance rated fire barrier constructed in accordance with Section 707 of the International Building Code or a one hour fire-resistance rated horizontal assembly constructed in accordance with Section 711 of the International Building Code, or both. 510.4.1.1 RES riser cable in non-high-rise buildings. In building construction type of V-A, Heavy Timber, III-A, II-A, I-A, and I-B installation of riser cable and amplifiers for distributed antenna systems shall be located in stacked electrical rooms, telephone rooms or shaft enclosure separated from the remainder of the floor by not less than a one-hour fire-resistance rated fire barrier constructed in accordance with Section 707 or 713 of the International Building Code. Wiring runs from an RES unit amplifier to a riser shall be separated from the remainder of the building by a minimum 1-hour fire-resistance rated fire barrier constructed in accordance with Section 707 of the International Building Code or a one hour fire-resistance rated horizontal assembly constructed in accordance with Section 711 of the International Building Code, or both. 510.5 Maintenance. Maintenance of the RES shall be the responsibility of the building owner and requires an operational permit issued by the Fire Marshal’s Office for any maintenance, repair or modification work. The building owner shall maintain a service contract for emergency repair with response to the site within two (2) hours of notification. 510.5.1. Radio frequency maintenance plan. A radio frequency maintenance plan shall be developed which prohibits use of electrical/electronic equipment which cause degradation to the RES. The radio frequency maintenance plan shall comply with the following at a minimum: 1. Prohibit the use of any electronic systems known to degrade the effectiveness of RES communications. 2. Permit Department site access during reasonable business hours when necessary to assess the source of interference to RES communications. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 61 3. Be incorporated into the lease of every tenant. 510.6 Installer certification. No contractor shall install, modify, repair, alter or replace an RES without a valid Englewood Fire Marshal’s license. All field installers shall be individually certified by the manufacturer for the equipment being installed. Each certified installer shall be permitted to supervise one apprentice/helper. 510.7 Records. Records of all system inspections, RES uplink and downlink gain settings, maintenance, annual tests and five-year test results shall be maintained on the premises in the “RES System Maintenanceand Test Results Log Book” which shall remain on the building premises and shall be available to the fire code official upon request. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 62 CHAPTER 6 BUILDING SERVICES AND SYSTEMS SECTION 603 FUEL-FIRED APPLIANCES Section 603.4 Portable unvented heaters is replaced as follows: 603.4 Portable unvented heaters. Portable unvented fuel-fired heating equipment is prohibited within the City of Englewood. Section 603.8.1 Residential incinerators is replaced as follows: 603.8.1 Residential incinerators. Residential incinerators are prohibited within the City and County of Englewood. SECTION 605 MECHANICAL REFRIGERATION Section 605.8 Refrigerant detection is replaced as follows: 605.8 Refrigerant detection. Machinery rooms shall contain refrigerant leak detection and initiate an emergency alarm in accordance with this section and Section 916. The detectors or sampling tubes that draw air to the detectors shall be located in areas where refrigerant from a leak will concentrate. A leak detection alarm shall be actuated at a value not greater than the corresponding occupational exposure limit (OEL) values identified in the International Mechanical Code for the refrigerant classification. The leak detection control unit shall provide a readout displaying the concentration of refrigerant gas detected. Accurate detector calibration shall be demonstrated during acceptance testing. Signage required by Section 908.8 shall state, outside the room “DO NOT ENTER WHEN LIGHT IS FLASHING – REFRIGERANT LEAK DETECTED” and inside the room “FLASHING LIGHT MEANS REFRIGERANT LEAK DETECTED – EVACUATE ROOM AND BUILDING.” SECTION 606 ELEVATOR OPERATION, MAINTENANCE, AND FIRE SERVICE KEYS Section 606.1 Emergency operation is replaced as follows: 606.1 Operation. New and altered elevators and conveying systems shall comply with Section 919 and Chapter 30 of the International Building Code. Elevators undergoing a controller replacement or alteration as defined in Colorado Code of Regulations 7CCR 1101-8 or ASME A17.1 shall be provided with Phase I emergency recall operation and Phase 2 emergency in-car operation. Existing elevators with a travel distance of 25 feet (7620mm) or more shall comply with the requirements of Chapter 11 of the International Fire Code,. All other alterations to existing elevators shall comply with State of Colorado requirements. Section 606.2 Standby power is amended to read as follows: 606.2 Emergency or standby power. In buildings and structures where emergency or standby power is required or furnished to operate an elevator, emergency or standby power shall be provided in accordance with Section 604. Operation of the system shall be in accordance with Sections 607.2.1 through 607.2.4. an DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 63 illuminated indicator shall be provided in the elevator lobby(ies) at the designated level in accordance with ASME A17.1. Section 606.2.1 Manual transfer is amended to read as follows: 606.2.1 Manual transfer. Emergency or standby power shall be manually transferable to all elevators in each bank. Section 606.2.2 One elevator is amended to read as follows: 606.2.2 One elevator. Where only one elevator is installed, the elevator shall automatically transfer to emergency or standby power within 10 seconds for an emergency power source and 60 seconds for a standby power source after failure of normal power. Section 606.2.3 Two or more elevators is amended as follows: 606.2.3 Two or more elevators. Where two or more elevators are controlled by a common operating system, all elevators shall automatically transfer to emergency or standby power within 10 seconds for an emergency power source and 60 seconds for a standby power source after failure of normal power where the emergency/standby power source is of sufficient capacity to operate all elevators at the same time. Where the emergency/standby power source is not of sufficient capacity to operate all elevators at the same time, all elevators shall transfer to emergency/standby power in sequence, return to the designated landing and disconnect form the emergency/standby power source. After all elevators have been returned to the designated level, not less than one elevator shall remain operable from the emergency/standby power source. Section 606.2.3.1 Two or more elevators in high-rise buildings without fire service access elevators is added as follows: 606.2.3.1 Two or more elevators in high-rise buildings without fire service access elevators. In high- rise buildings without fire service access elevators, not less than two elevators shall remain simultaneously operable from the emergency power source. One of these elevators shall be the elevator required to accommodate an ambulance stretcher. All elevators shall be manually transferable to the emergency power source in accordance with Section 607.2.1. Exception: Sufficient emergency power shall be provided for not less than one elevator that only serves open parking levels of the high-rise building. Section 606.2.3.2 Elevators in high-rise buildings with fire service access elevators, but without occupant evacuation elevators is added as follows: 606.2.3.2 Elevators in high-rise buildings with fire service access elevators, but without occupant evacuation elevators. In high-rise buildings with fire service access elevators, but without occupant evacuation elevators, no less than three elevators shall remain simultaneously operable from the emergency power source and elevators shall be capable of accessing all floors of the building. Where an elevator transfer floor is provided in order to provide access to all building floors, a minimum of five elevators shall be required for simultaneous operation on the emergency power source. Emergency power shall be provided to the required fire service access elevators in accordance with Section 3007.8 of the International Building Code,. The designated non-fire service access elevator(s) shall be capable of having the emergency power manually transferrable to any other non-fire service access elevator(s) in accordance with Section 607.2.1. Exception: Sufficient emergency power shall be provided for not less than two elevators that only serves open parking levels of the high-rise building. Section 606.2.4 Machine room ventilation is amended to read as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 64 606.2.4 Machine room ventilation. Where standby power is connected to elevators, the machine room ventilation or air conditioning shall be connected to the emergency or standby power source. Section 606.3.1 Signage for existing elevators without a flashing hat indicator is added as follows: 606.3.1 Signage for existing elevators without a flashing hat indicator. Existing elevators with shunt trip capability that do not provide a flashing hat indication in accordance with Section 907.3.3.5 shall have an approved sign mounted adjacent to the FACP stating; “CAUTION – Elevator is not equipped with “Flashing Fire Hat” capability. Elevator(s) could lose power if fire is detected in the elevator machine room or hoistway.” Sign shall be black lettering on a yellow background. Section 606.8 Exception is replaced in its entirety as follows: Exception: The owner shall place the building’s existing, approved non-standardized fire service elevator keys in a key box complying with Section 506.1.2. Section 606.8.1 is amended by adding items 5 and 6 as follows: 5. Keys shall be Group 3 security in accordance with ASME A17.1 and shall comply with DFD Policy 607-1. 6. All standardized fire service elevator keys located at the building shall be numbered sequentially by indelible marking and a key log shall be maintained on site that identifies the location and holder of each key. When a holder is no longer qualified to maintain possession of a key, the key shall be returned to the issuing authority for subsequent distribution in accordance with this code. Section 606.8.1.1 New elevator installations is added as follows: 606.8.1.1 New elevator installations. Where a new elevator is installed as part of an existing group of elevators with a common controller, all elevators in the group shall be upgraded to the same firefighters’ emergency operation as required by this Code. Section 606.8.1.2 Alterations to elevators is added as follows: 606.8.1.2 Alterations to elevators. Where an existing elevator is modified under any alteration encompassing a scope of work as described under Colorado Code of Regulations, 7 CCR 1101-8 or ASME A17.1 the altered elevator shall be provided with a standardized key. Where the altered elevator is part of an existing group of elevators with a common controller, all elevators in the group shall be retrofitted with a standardized key. Exception: Elevators without existing Phase 1 and Phase 2 operation. Section 606.8.1.3 Existing elevator installations is added as follows: 606.8.1.3 Existing elevator installations. Key switches required for Firefighters’ Emergency Operation and Emergency or Standby Power Systems selection on all elevators within a building shall be retrofitted with the approved standardized key. Section 606.8.3 is replaced as follows: 606.8.3 Duplication or distribution of keys. No person may possess a standardized fire service elevator key unless in accordance with this code. Duplication of keys is not permitted. Unauthorized distribution/duplication of keys is subject to the penalties of Section 109.2.2.1. Section 606.8.4 is replaced as follows: 606.8.4 Responsibility to provide keys. A key shall be provided for each switch installed. Standardized DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 65 fire service access keys shall be maintained in an approved lock box within a secured fire command center in accordance with Section 508 where provided, or an approved, listed key box in accordance with Section 506. Section 606.9 Elevator recall for high-rise buildings with pressurized hoistways is added as follows: 606.9 Elevator recall for high-rise buildings with pressurized hoistways. In addition to the requirements of ASME A17.1, Firefighters’ service elevator operation within high-rise buildings with pressurized hoistways shall be as follows: 1. The elevator doors shall automatically open when the car reaches the designated level. After a period of one minute, elevators shall automatically close their doors. The doors shall be responsive by pressing the designated return floor call button in the elevator lobby or by pressing the door open button in the interior of the elevator cab. Elevators shall remain at that level until manually overridden by the key- operated switch required by ASME A17.1. 2. Only the hall call buttons at the designated return level, the level the car(s) have returned to, shall function as door open buttons. All doors shall open simultaneously when operating under normal building power. When operating under emergency power, only the cars selected for emergency operation shall open their doors simultaneously. 3. During Phase 1 operation, the door recycle shall be 60 seconds. 4. Once the car is placed on Phase II, the fire department has control of the elevator; it shall operate in accordance with ASME A17.1, Section 2.27.3.3. Section 606.10 Fire service access elevators is added as follows: 606.10 Fire service access elevators. Installation of fire service access elevators shall comply with Section 919 and Section 3007 of the International Building Code. Section 606.11 Occupant evacuation elevators is added as follows: 606.11 Occupant evacuation elevators. Installation of occupant evacuation elevators shall comply with Section 919 and Section 3008 of the International Building Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 66 CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 806 DECORATIVE VEGETATION IN NEW AND EXISTING BUILDINGS Section 806.6 Combustible natural vegetation is added as follows: 806.6 Combustible natural vegetation. Limited quantities of combustible natural vegetation shall be permitted in A, E, I3, R1, R2/Dormitory, and R-4 occupancies where the fire code official determines adequate safeguards are provided based on the quantity and nature of the vegetation. Flame resistance shall be demonstrated in an approved manner for each item of vegetation. The use of unlisted electrical wiring and lighting on combustible natural vegetation is prohibited. SECTION 807 DECORATIVE MATERIALS OTHER THAN DECORATIVE VEGETATION IN NEW AND EXISTING BUILDINGS Section 807.5.2.2 Artwork in corridors is replaced as follows: 807.5.2.2 Artwork in corridors. Artwork and teaching materials shall be limited on walls of corridors to not more than thirty (30) percent of the area of each wall to which they are attached. The height from the floor to the ceiling multiplied by the length of the wall excluding door and window openings is considered the area of each wall. Artwork and teaching materials shall not be attached to any wall within eighteen (18) inches of the exit access door. Doors and windows, including view panels of interior exit access doors, shall not be covered. The use of crepe paper that is not listed as flame resistant is prohibited. Exceptions: 1. These area limitations do not apply to artwork and teaching materials listed as non-combustible. 2. Artwork and teaching materials contained within fully enclosed, non-combustible or limited combustible containers or coverings such as metal and glass display cases are not required to be included in the area limitations. 3. Corridor walls may be used to attach artwork and teaching materials not to exceed sixty (60) percent of the area of each wall when the building is protected throughout by an automatic fire sprinkler system in accordance with Section 903.3.1.1. Section 807.5.2.3 Artwork in classrooms is replaced as follows: 807.5.2.3 Artwork in classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than fifty (50) percent of the area of each wall to which they are attached. Artwork and teaching materials shall not be attached to any wall within eighteen (18) inches of the exit access door. Exceptions: 1. Classroom walls may be used to attach artwork and teaching materials not to exceed eighty (80) percent of the area of each wall when the building is protected throughout by an automatic fire sprinkler system in accordance with Section 903.3.1.1. The height from the floor to the ceiling multiplied by the length of the wall excluding door and window openings is considered the area of each wall. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 67 2. These area limitations do not apply to artwork and teaching materials listed as non-combustible. 3. Artwork and teaching materials contained within fully enclosed, non-combustible or limited combustible containers or coverings such as metal and glass display cases are not required to be included in the area limitations. Section 807.5.5.2 Artwork in corridors is replaced as follows: 807.5.5.2 Artwork in corridors. Artwork and teaching materials shall be limited on walls of corridors to not more than thirty (30) percent of the area of each wall to which they are attached. The height from the floor to the ceiling multiplied by the length of the wall excluding door and window openings is considered the area of each wall. Artwork and teaching materials shall not be attached to any wall within eighteen (18) inches of the exit access door. Doors and windows, including view panels of interior exit access doors, shall not be covered. The use of crepe paper that is not listed as flame resistant is prohibited. Exceptions: 1. Corridor walls may be used to attach artwork and teaching materials not to exceed sixty (60) percent of the area of each wall when the building is protected throughout by an automatic fire sprinkler system in accordance with Section 903.3.1.1. 2. These area limitations do not apply to artwork and teaching materials listed as non-combustible. 3. Artwork and teaching materials contained within fully enclosed, non-combustible or limited combustible containers or coverings such as metal and glass display cases are not required to be included in the area limitations. Section 807.5.5.3 Artwork in classrooms is replaced as follows: 807.5.5.3 Artwork in classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than fifty (50) percent of the area of each wall to which they are attached. Artwork and teaching materials shall not be attached to any wall within eighteen (18) inches of the exit access door. Exceptions: 1. Classroom walls may be used to attach artwork and teaching materials not to exceed eighty (80) percent of the area of each wall when the building is protected throughout by an automatic fire sprinkler system in accordance with Section 903.3.1.1. The height from the floor to the ceiling multiplied by the length of the wall excluding door and window openings is considered the area of each wall. 2. These area limitations do not apply to artwork and teaching materials listed as non-combustible. 3. Artwork and teaching materials contained within fully enclosed, non-combustible or limited combustible containers or coverings such as metal and glass display cases are not required to be included in the area limitations. Section 807.6 Ceiling artwork and teaching materials is added as follows: 807.6 Ceiling artwork and teaching materials. Artwork and teaching materials suspended from classroom and corridor ceilings shall be in accordance with the following: 1. Where permitted by Section 703.3, the ceiling structure must be capable of supporting the artwork and teaching materials. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 68 2. The total area of materials suspended from ceilings plus the covered area of each adjacent wall shall not exceed the wall areas permitted to be covered in accordance with Sections 807.5.2.2, 807.5.2.3, 807.5.5.2 and 807.5.5.3. 3. Display of artwork and teaching materials shall not impair visibility or distract attention from any egress signage or alarm notification appliance. 4. No material shall be attached to electrified fixtures, electrical wiring, egress signage, plumbing, fire alarm components, fire sprinkler components, etc. 5. The display of artwork or teaching materials shall not obstruct or compromise in any manner the fire sprinkler or fire detection system. 6. Display of artwork and teaching materials on wires or cords strung across corridors from wall to wall shall not form a continuous combustible curtain. There shall be a minimum clearance of seven (7) feet from the floor to the lowest portion of the display. 7. Wires or cords used to suspend artwork and teaching materials from the ceiling cannot be strung from corner to corner of a room or space and cannot be strung parallel to any wall further than six (6) inches from the wall. Exception: Where hanging or display of decorative materials is prohibited by Section 703.3. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 69 CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL Section 901.2 Construction documents is amended by adding the following after the last sentence: Shop drawings shall be provided in accordance with Appendix N. Section 901.6.3 Records is replaced in its entirety as follows (subordinate Section 901.6.3.1 remains): 901.6.3 Records. Records of all system installations, inspections, tests and maintenance required by Englewood’s Fire Code and referenced standards shall be maintained on the premises. Records shall be completed on National Fire Protection Association forms and/or forms provided by the Fire Marshal’s Office. The name and contractor license number(s) of the person(s) performing the work shall be legible on all forms. SECTION 902 DEFINITIONS Section 902.1 Definitions is amended as follows: 902.1 Definitions. The following terms are defined in Chapter 2: ALARM CONTROL UNIT APPLIANCE BATTERY BACKUP BATTERY-POWERED DEVICE DUPLEX FALSE FIRE ALARM HARDWIRED INSTALLED NON-DEDICATED SMOKE CONTROL SYSTEM SINGLE-FAMILY DWELLING SINGLE STATION [CO] ALARM SLEEPING ROOM DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 70 SECTION 903 AUTOMATIC SPRINKLER SYSTEMS Section 903.2.8.5 Balconies is added as follows: 903.2.8.5 Balconies. Sprinkler protection shall be provided for all balconies and ground floor patios of dwelling units of all construction types. Sidewall sprinklers that are used to protect such areas shall be located such that their deflectors are within 1 inch (25 mm) to 6 inches (152 mm) below the structural members, at a maximum distance of 14 inches (356 mm) below the deck, or as listed by the sprinkler manufacturer. Exception: Sprinklers are not required for noncombustible balconies where the balcony is not supplied by fuel gas and one of the following is met: 1. The roof or other overhead structure does not cover more than 50% of the entire balcony area. 2. The balcony has openings on two or more sides. The area of such openings must be at least 20 percent of the total perimeter wall area of the balcony. The aggregate length of the openings shall constitute a minimum of 40 percent of the perimeter of the balcony. Section 903.2.8.6 Townhouses is added as follows: 903.2.8.6 Townhouses. When two or more contiguous residential dwelling units constructed as townhouses, including those permitted under the International Residential Code, are protected by a single, monitored sprinkler system, that system shall be configured so it can be isolated (with valve and tamper switch) and water flow is annunciated separately at the fire alarm control panel for each dwelling unit and each protected common area. Section 903.2.9.1 Repair garages is amended by adding Items 5 and 6 as follows: 5. Repair garages with a spray booth and/or a mixing area greater than 16 square feet utilizing flammable finishes. Exception: It is not necessary to install sprinklers throughout the entire building when replacing a previously approved booth with an approved packaged booth or one constructed in accordance with Section 2404.3.2. 6. Repair garages using open flame or welding of any type where the garage floor area exceeds 3,000 square feet. Section 903.2.11.7 Shafts in high-rise buildings is added as follows: 903.2.11.7 Shafts in high-rise buildings. Where a reduction in shaft construction fire rating is permitted by Section 403 of the International Building Code, required sprinklers shall be located at the top of the shaft and at alternate floor levels. Sprinklers shall be provided with a dedicated riser with an isolation valve and flow and tamper switch. Activation of the flow switch shall communicate an alarm to the central station and activate vertical pressurization, but not occupant notification. Section 903.3 Installation requirements is replaced as follows: 903.3 Installation requirements. All fire sprinkler systems and special extinguishing system design drawings, shall be submitted in accordance with Appendix N. Section 903.3.1.1.1 Exempt locations is amended by replacing Items 3 and 4 as follows: 1. A room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. A room or space where sprinklers are considered undesirable because of the nature of the contents, DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 71 where approved by the fire code official. 3. Fire service access elevator machine rooms and machinery spaces. 4. Machine rooms, machinery spaces, control rooms and control spaces associated with occupant evacuation elevators designed in accordance with Section 3008 of the International Building Code. Section 903.3.1.2 NFPA 13R sprinkler systems is replaced as follows: 903.3.1.2 NFPA 13R sprinkler systems. Automatic sprinkler systems in group R occupancies in buildings up to and including four stories in height measured above grade plane shall be permitted to be installed throughout in accordance with NFPA 13R. Section 903.3.1.2.1 Balconies and decks is replaced as follows: 903.3.1.2.1 Balconies and decks. Sprinkler protection for balconies and decks shall comply with Section 903.2.8.5. Section 903.3.3.1 Insulation above sprinklers is added as follows: 903.3.3.1 Insulation above sprinklers. Insulation installed above sprinklers on the underside of floor or roof sheathing shall be secured in place with 20 gauge metal netting with a mesh size not greater than 2 inches x 2 inches. Section 903.3.5 Water supplies is replaced as follows: 903.3.5 Water supplies. The potable water supply shall be protected against backflow in accordance with IFC Section 912.6. Hydraulic calculations shall be based on water supply information provided by the City of Englewood Utilities Department. Water supply information provided shall be obtained within the last 12months.Hydraulic calculations shall be based on the water data provided with static and residual pressures reduced by 10% of the static value or 10 psi, whichever is smaller. Where water supply data is provided by City of Englewood Utilities Department, the high static pressure shall be used to verify that the fire pump churn pressure shall be maintained below the system design pressure. Shop drawings shall indicate the initial pressures and the reduced values as used in the hydraulic calculations. Exception: Sprinkler systems installed in accordance with IFC Section 903.3.1.3 Section 903.3.5.1 Domestic service is replaced as follows: 903.3.5.1 Domestic service. Use of domestic service for water supply to automatic fire sprinklers shall be prohibited. Exceptions: 1. Water supply for new NFPA 13D or IRC P2904 sprinkler systems. 2. UL-300 listed fire suppression systems in buildings that are not provided with automatic sprinklers. 3. Medical gas rooms in accordance with IFC Section 5306. Section 903.3.5.2 Residential combination services is deleted. Section 903.3.7 Fire department connections is replaced in its entirety as follows: 903.3.7 Fire department connections. Fire department connections shall be in accordance with Section 912. Section 903.3.8 Limited area sprinkler systems and all subsections through 903.3.8.5 are deleted in their entirety. Section 903.3.9 Elevator hoistways and machine rooms is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 72 903.3.9 Elevator hoistways and machine rooms. In buildings protected with an automatic sprinkler system in accordance with NFPA 13 or NFPA 13R, elevator hoistways and machine rooms shall only be provided with automatic sprinklers as described in NFPA 13, 8.15.5. Where sprinkler protection is provided, installation shall comply with NFPA 13 except as noted in this section. Hoistways and machine rooms/spaces shall be protected by 286-degree F sprinklers. Coverage shall be designed for Ordinary Hazard Group One. Sprinklers shall be supplied from a separate, independent branch line with a readily accessible indicating shut-off valve located outside the hoistway or machine room. Control valves shall carry identification signs. Where sprinkler protection is not provided, automatic fire detectors shall be provided in accordance with Section 907.3.3. 903.3.9.1 Elevators undergoing alteration. Where an existing elevator is undergoing an alteration in accordance with Colorado Code of Regulations, 7CCR1101-8, fire protection and emergency operation shall be provided in accordance with this Section and Section 607. In existing buildings with either a partial or complete fire sprinkler system and the elevator hoistway and/or the elevator machine room is not protected with sprinklers, the provisions of Section 903.3.9.1.1 or 903.3.9.1.2 shall apply. Installation of automatic sprinklers shall comply with Section 903.3.9. 903.3.9.1.1 Hydraulic Elevator. Protection of the elevator hoistway and machine room shall be provided as follows: 1. Smoke detectors shall be installed at all elevator lobbies and in the machine room(s) to provide recall. 2. Fire sprinklers (286F) and heat detectors (200 F) shall be installed within the elevator pit. Heat detector activation shall cause the hat indicator in the car to flash and initiate the required recall prior to operation of the sprinkler. Activation of a machine room smoke detector shall also cause the hat indicator within the car to flash. 3. In cars not equipped with a flashing hat indicator, signage shall be provided in accordance with Section 607.3.1. Activation of the heat detector within the elevator pit shall initiate recall. 4. Where an existing hoistway is equipped with a vent, the smoke detector at the top of the hoistway shall be maintained for vent operation. Activation of this smoke detector shall also initiate recall and cause the hat indicator in the car (where provided), to flash. 903.3.9.1.2 Traction Elevators. Protection of the elevator hoistway and machine room shall be provided as follows: 1. Smoke detectors shall be installed at all elevator lobbies and in the machine room(s) to provide recall. 2. A 135 degree Fahrenheit heat detector shall be installed at the top of the hoistway to provide recall and cause the hat indicator in the car to flash. 3. In cars not equipped with a flashing hat indicator, signage shall be provided in accordance with Section 607.3.1. Installation of the heat detector at the top of hoistway is not required. 4. Where an existing hoistway is equipped with a vent, the smoke detector at the top of the hoistway shall be maintained for vent operation. Activation of this smoke detector shall also initiate recall and cause the hat indicator in the car (where provided), to flash. Section 903.3.10 Sprinkler protection for electrical rooms is added as follows: 903.3.10 Sprinkler protection for electrical rooms. In buildings required to be fully sprinklered, electrical rooms containing electrical switchboards, panel boards, distribution boards, control equipment, generators and/or transformers shall be protected with automatic sprinklers. Sprinkler protection shall be designed with high-temperature sprinklers. Only sprinkler branch lines protecting the electrical room are permitted in the DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 73 room. Exceptions: 1. The room or space is under the control of a public utility. 2. The room is dedicated to electrical distribution equipment, has equipment operating at 600 volts or more and is provided with a smoke detection system connected to a monitored fire alarm system. Section 903.4.2 Alarms is replaced as follows: 903.4.2 Alarms. Approved audible/visible devices (24 VDC supervised) shall be connected to every automatic sprinkler system. These sprinkler water flow alarm devices shall be activated by main and/or zone water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building at least 10 feet above grade and within 25 feet of and visible from the fire department connections. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Exception: One- and two-family dwelling units and townhomes constructed in accordance with the International Residential Code. Section 903.4.2.1 Sprinkler monitoring panels is added as follows: 903.4.2.1 Sprinkler monitoring panels. Control panels installed for monitoring of sprinkler systems shall be located in accordance with Section 907.1.5. Section 903.4.3 Floor control valves is replaced as follows: 903.4.3 Floor control valves. An approved floor control valve, check valve, drain valve, and flow switch for isolation, control, and annunciation shall be provided at each sprinklered level, including the topmost, of buildings: 1. Exceeding two stories in height with a total combined area of all levels exceeding the NFPA 13 system protection area limitations or; 2. Required to have standpipes in accordance with Section 905. SECTION 904 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS Section 904.3.4.1 Visible notification is added as follows: 904.3.4.1 Visible notification. Visible notification shall be provided by yellow or amber strobes. Pending discharge and discharge warning strobes shall be in conspicuous locations as approved by the fire code official and activated by the agent releasing panel. Subject to the approval of the fire code official, pending discharge and discharge warning may be provided by combined audible/visible appliances. No more than two flash rates shall be possible in a single field of view in accordance with NFPA 72. Where pending- discharge and discharge warning strobes are provided in addition to visible fire alarm notification appliances, the warning strobes shall be synchronized, and fire alarm visible notification appliances shall be synchronized. A warning sign shall be provided that reads, “WARNING – Fire Extinguishing Agent Release in Progress.” Warning sign format, color and letter style shall be as approved by the fire code official. Warning signs shall be posted at each entrance door stating: “In the event of a system discharge, DO NOT enter without a self-contained breathing apparatus or until the area is thoroughly ventilated.” Section 904.3.5 Monitoring is amended by adding the following at the end of the last sentence: “and Section 907.” DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 74 Section 904.3.5.1 Releasing panel is added as follows: 904.3.5.1 Releasing panel. Pre-action and clean agent automatic fire-extinguishing systems shall be monitored and installed in accordance with this section and Section 907.6.7. Section 904.15 Fixed, Mobile, or Temporary Concessions Protections is added as follows: 904.15 Required Installations. Cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, and structures processes producing smoke or grease-laden vapors shall be equipped with an exhaust system that complies with all the equipment and performance requirements of section 609 and sections 904.15.1 through 904.15.6. Exception: Where fixed structures are governed by the International Mechanical Code, International Building Code and International Fuel Gas Code. 904.15.1. Cooking equipment shall be equipped with pre-engineered automatic extinguishing systems tested in accordance with UL 300 and listed and labeled for the intended application. The system shall be installed in accordance with this code, its listing and the manufacturer’s instructions. 904.15.2 Manual system operation and interconnection. Manual actuation and system interconnection for the hood suppression system shall be in accordance with Sections 904.12.1 and 904.12.2, respectively. 904.15.3 Portable fire extinguishers. A portable fire extinguisher complying with Section 906.4 shall be installed within a 10-foot distance of travel from cooking appliances. 904.15.4 Operations and maintenance. Automatic fire-extinguishing systems protecting commercial cooking systems shall be maintained in accordance with Sections 904.12.6.1 through 904.12.6.3. 904.15.5 Operational permits and Submittals. Pre-engineered, automatic extinguishing system shop drawings shall be submitted for permit application. Two complete sets of drawings shall be submitted to the Englewood Fire Marshal’s Office or electronic submittals shall be made through the online portal. Submittals shall including the following information: 1. System to be UL-300 listed 2. Product data sheets (panel, nozzles, etc.) 3. Nozzle location shown with type appliance. 4. Discharge density for the cooking equipment being protected. 5. Location of manual pull station from hood. SECTION 905 STANDPIPE SYSTEMS Section 905.1 General is replaced as follows: 905.1 General. Standpipe systems shall be provided in new buildings and structures in accordance with this section. Fire hose threads used for connection to standpipe systems shall be approved and shall be compatible with Denver Fire Department hose threads – 2.5-inch hose thread is national standard; 1.5-inch hose thread is a special 11.5 threads per inch. The location of Fire Department hose connections shall be approved by the fire code official. Where standpipe valve outlets are installed in stair enclosures, outlets and ancillary equipment (PRVs, drains, etc.) shall not reduce the required width of the stairway or landing. 905.1.1 Standpipe hose outlets. Each outlet shall have a cap and chain. Outlets shall be at least 36 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 75 inches and not more than 52 inches above finished floor. The valves shall have no less than 3 inches clearance around control valve and outlet cabinet shall not impede attachment of hose. Section 905.2 Installation standard is replaced as follows: 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. When water pressure at a standpipe outlet exceeds 175 psi static or residual at 250 gpm flow, a pressure-reducing valve shall be provided. The required pressure-reducing valves shall be located at the hose valve outlet only. Only field-adjustable valves shall be allowed. The valve shall have five (5) field- adjustable valve settings (A-E) on a color-coded indication label. Pin-in hex security screws shall be installed to secure the hand wheel and a high-impact plastic shield covering the pressure-reducing adjustment mechanism shall be provided. A pin-in hex bit shall be supplied with each valve. The pressure adjustment mechanism shall be actuated using an aluminum adjustment rod provided with each valve and actuated by rotating in either a clockwise or counter-clockwise direction. Pressure gauge taps shall be provided on inlet and discharge sides of each valve. A reflective decal shall be installed on the high-impact plastic shield valve with arrows and words indicating the direction to increase or decrease pressure. If special tools are required to make field adjustments, a minimum of four (4) such tools shall be provided at locations approved by the Fire Department. Section 905.3.1 Height is amended by replacing the Exceptions as follows: Exceptions: 1. Class I standpipes are allowed in buildings equipped throughout with an automatic sprinkler system in accordance with Sections 903.3.1.1 or 903.3.1.2 of the International Fire Code subject to the provisions of Section 913 of the International Fire Code. 2. Class I automatic dry standpipes are allowed in single use or mixed-use open parking garages constructed in accordance with Section 406.5 of the International Building Code, where the highest floor is located not more than seventy-five (75) feet above the lowest level of Fire Department vehicle access. In a mixed-use parking garage, the standpipe system serving the open parking garage shall be integrated with the fire protection system serving the other occupancies, and not be a stand-alone system. Hose connections shall be located as required for Class II standpipes in accordance with Section 905.5 of the International Fire Code. 3. Class I manual dry standpipes are allowed in single use open parking garages where the highest floor is less than 55 feet from the lowest level of Fire Department vehicle access. Hose connections shall be located as required for Class II standpipes in accordance with the Section 905.5 of the International Fire Code. This provision is applicable to open parking garages with one level of underground enclosed parking garage. 4. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system. 5. Intentionally deleted. Section 905.3.4.1 Hose and cabinet is deleted. Section 905.3.8. Rooftop gardens and landscaped roofs is replaced as follows: 905.3.8. Rooftop gardens and landscaped roofs. Buildings or structures that have rooftop gardens or landscaped roofs and that are equipped with a standpipe system shall have the standpipe system extended to the roof level on which the rooftop garden or landscaped roof is located. The standpipe hose outlet shall be located within 230 feet of all vegetated areas and located within the access point. Exception. In existing buildings, the fire code official may approve a standpipe hose outlet in an alternate location when the building provides an approved alternative method for fire fighters or emergency responders to accomplish suppression efforts. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 76 Section 905.4 Location of Class I standpipe hose connections is amended by replacing Items 1, 2 and 5 as follows: 1. In every required interior exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. Where exterior stairways are provided as part of the required exit stairway, hose connections shall be located at the floor landing or as otherwise approved by the fire code official. 2. On each side of the wall adjacent to the exit opening of a horizontal exit. Exception: Where all floor areas are reachable from an interior exit stairway hose connection on the same side of a horizontal exit within 200 feet for sprinklered buildings or 130 feet for nonsprinklered buildings, the hose connection on the other side of the horizontal exit shall not be required. 5. Where buildings have 4 or more stories above the grade plane and the roof slope is less than four units vertical to twelve units horizontal (33.3%) slope, there shall be at least two 2-1/2" roof manifold outlet connections above the roof line. Roof manifolds shall be located on the exterior perimeter of the stair enclosure within 20' of the roof access opening door. Section 905.4.1 Protection is amended by adding exception 2 as follows: Exceptions: 2. Where additional standpipes are needed to meet travel distance requirements in non-high-rise buildings, protection of piping is not required in buildings equipped with an approved automatic sprinkler system. Section 905.5.3 Class II system 1-inch hose is deleted in its entirety. Section 905.13 Combined systems is added as follows: 905.13 Combined systems. Working pressure and NFPA 13 Pressure Reducing Valve requirements for combined sprinkler and standpipe systems shall include and be based on the manual standpipe system demand pressure provided at the most remote fire department connection. SECTION 906 PORTABLE FIRE EXTINGUISHERS Section 906.1 Where required Item 1 and Exception are replaced as follows: 1. In new and existing Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. Exception: In Group R-2 occupancies, portable fire extinguishers shall be required only in locations specified in Items 2 through 6 where each dwelling unit is provided with a portable fire extinguisher having a minimum rating of 2-A:10-B:C. Section 906.2.2 Verification of service collars is added as follows: 906.2.2 Verification of service collars. Every portable fire extinguisher, regardless of type, shall have a verification of service collar, in accordance with NFPA 10. Only collars obtained from a licensed/certified fire extinguisher company are allowed. Collars shall not be cut. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 77 SECTION 907 FIRE ALARM AND DETECTION SYSTEMS Section 907.1.2 Fire alarm shop drawings is replaced as follows: Fire alarm shop drawings. Shop drawings for fire alarm systems shall be submitted for permit application as a deferred submittal in accordance with Section 133.5 of the International Building Code. Plan review and approval are required prior to issuance of a permit for system installation. Two sets of scaled, engineered installation shop drawings shall be submitted. Documents shall be of sufficient clarity and detail to fully describe the scope of work. Handwritten notes and comments on reproduced drawings are not acceptable. Submittals shall comply with Appendix N. Section 907.1.3 Equipment is replaced as follows: 907.1.2 Equipment. Systems and their components shall be listed and approved for the purpose for which they are installed. Installation locations of all control panels and annunciators are subject to field approval by the Fire Department. Keys for all equipment required to be accessible to the Fire Department shall be maintained in an approved location in accordance with Section 506 of the International Fire Code. All components shall be compatible with the system in which installed. Section 907.1.4 Connections to other systems is added as follows: 907.1.3 Connections to other systems. A fire alarm system shall not be used for any purpose other than fire warning or as specifically approved, e.g. pool alarm, access control release in accordance with Section 1010.1.9 of the International Building Code, elevator recall and shunt trip, emergency alarms in accordance with Section 908, CO alarms in accordance with Section 915, hazardous materials alarms in accordance with Chapter 50, compressed gas alarms in accordance with Chapter 53 or mass notification systems as approved by the fire code official. Section 907.1.5 Control units, annunciators and access keys is added as follows: 907.1.4 Control units, annunciators and access keys. All fire alarm control units and annunciators shall be UL 864 listed or equivalent. Locations shall be within 10’ (3.048m) of the main building entrance, unless an alternate location is specifically approved. Equipment locations are subject to field approval prior to installation. Installation shall comply with NFPA 72. Access keys to locked fire alarm equipment shall be maintained in an approved location. Fire alarm control units shall not be equipped with a key or special numeric code to access system reset and silence functions. Access to the reset and silence operator interface shall be secured behind a locked door. Field modification of control units or annunciators is not permitted. System zone and device disable functions shall not be accessible without a maintenance-level access code. Alarm signals shall be protected from unauthorized deactivation. This applies to disconnection of the panel alarm transmission to the monitoring station and the alarm output circuit(s) to notification appliances. Deactivation shall only be allowed by Fire Department personnel or authorized entities responsible for system testing and maintenance. Any system deactivation shall be reported to the monitoring station and the Fire Department. Facilities whose systems are estimated to be deactivated for 10 hours or more shall be provided with an approved fire watch. Exceptions: 1. In existing buildings undergoing a panel replacement, remote annunciators with silence and reset functions may be provided when approved by the fire code official. These units shall not be equipped with “enable/disable” switches and shall be contained behind a transparent, lockable cover. 2. Low-power radio (wireless) systems shall comply with NFPA 72 and are permitted only for installations where the total system coverage does not exceed 1500 sf. Multiple low-power systems in a building are not permitted. Installation of low-power and wired systems is not permitted in the same building. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 78 Section 907.1.6 Central alarm station connection is added as follows: 907.1.5 Central alarm station connection. All fire alarm and sprinkler protection systems required by this code or by special agreement shall be monitored by an approved Class I supervising station complying with Section 917. Multiple central alarm station connections from one building are not permitted. Campus arrangements or a complex of buildings requiring a graphic site map monument per Section 505.1 shall have each building’s address transmitted to the central station. Section 907.1.7 Multiple fire alarm systems in a single building added as follows: 907.1.6 Multiple fire alarm systems in a single building. Only one fire alarm system shall be installed per building. Multiple points of silence and reset are prohibited on a single system. Exceptions: 1. When permitted by the fire code official, portions of a building separated by fire walls without openings and identified with separate legitimate addresses are allowed to be considered separate buildings. When protected by an automatic sprinkler system, each portion of the building so considered shall be protected by a separate independent sprinkler system or a portion of a single sprinkler system dedicated to the separated portion of the building. 2. Multiple points of silence and reset as allowed by Section 907.1.9 Exception. 3. Multiple buildings constructed over a common structure where approved by the fire code official. Section 907.1.8 Problematic systems is added as follows: 907.1.7 Problematic systems. Fire alarm systems that generate two (2) or more false or nuisance fire alarms within twenty-four (24) hours, three (3) or more within thirty (30) days, or ten (10) or more within one year shall be immediately repaired, mitigated or replaced as necessary. A fine will be imposed for any false or nuisance fire alarms exceeding ten (10) within one year. A permit shall be obtained for all work. Fire protection, fire alarm and fire detection systems shall be properly maintained to provide at least the same level of reliability, performance and protection as designed and approved. The property owner shall be responsible for maintaining the system. If the system is found to be impaired two (2) or more times within a twelve (12) month period, legal action will be imposed until the system(s) is restored to a code complying condition. Section 907.1.9 Systems out of service is added as follows: 907.1.8 Systems out of service. Systems undergoing maintenance or modification shall not have any portion of the system out of service for more than ten (10) hours. During maintenance or modification, all manual pull stations and notification appliances shall remain operational. Fire watch must be provided in all areas of the building where maintenance or modification will place any portion of the system out of service. Exception: Where practical difficulties are associated with replacement of fire alarm detection systems in existing high-rise buildings, phased replacement of an existing fire alarm system shall be permitted as follows: 1. An Administrative Modification (AM) request for the phased replacement of the fire alarm and detection system shall be submitted to the fire code official for evaluation and approval prior to submission of shop drawings. 2. Two fire alarm control panels shall be allowed during the phased system upgrade. Existing and new fire alarm control panels shall be co-located at a location approved by the fire code official. During this period, it shall be acceptable to have two points of system reset via the two fire DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 79 alarm control panels. A wall map showing each floor with descriptions of which system is controlling devices in each area shall be posted adjacent to the fire alarm control panels during construction. Upon completion of the new front-end equipment installation and after all compatible devices have been transferred, tested and approved by the fire code official, the contractor will remove the old panel and related equipment. 3. Installation within each floor shall be completed prior to commencement of work on any other floor unless the contractor can complete multiple floors simultaneously. 4. Project duration shall not exceed 24 months from the date the fire alarm permit is issued, nor shall the total duration, including project planning, design and installation, exceed 36 months. Subject to the approval of the fire code official, a single extension of up to a maximum of one year may be requested in writing. Extensions shall be granted only in cases of unforeseen difficulties. Building owners and contractors shall make every effort to minimize any delay to project completion. 5. The applicant shall present a planned schedule with phased replacement of the system and components, including scope of work and sequence of operation with coordination of the two fire alarm panels, to the fire code official for review and approval prior to preparation of shop drawings. 6. Fire alarm and detection system protection shall be maintained at all times and in all areas, except where system/component replacement is taking place while installers are present. Existing and new devices and appliances not affected and outside of the installation area shall be maintained fully operational at all times. 7. Phasing of fire alarm system replacement shall be in an organized, coherent and logical sequence to reduce system disruption and allow work while maintaining the life safety systems of the building. 8. Audible and visual notification appliance coverage shall comply with NFPA 72 and this Code. 9. Either point graphic annunciation or LED directory-type annunciation shall be provided. Where LED directory-type annunciation is provided, each device type per level in conjunction with progressive remote indicating lights for detectored spaces shall be provided. Where multiple smoke control zones are provided within each level, each compartment shall be separately annunciated. For existing buildings with graphic annunciation, either the graphic annunciation shall be maintained or replaced with a new graphic annunciation panel. Annunciator panels shall include LED lights for automatic detection, manual pull, flow, tamper, special systems, supervisory and trouble. 10. Where the building has a smoke control system, detailed interface of the new fire alarm system with the existing or upgraded smoke control system shall be provided in the AM submission with details also shown on the shop drawings. 11. The building owner or owner's representative and the design professional shall sign the AM request. 12. The AM shall cite the practical difficulties of the proposed system replacement, the phased scope of replacement, the duration of each phase, as well as the total time from start to completion of the project. Failure to complete the project within the specified time frame shall subject the parties responsible to penalties specified in Section 109. Section 907.2.1.3 Illumination of means of egress is added as follows: 907.2.1.3 Illumination of means of egress. Illumination levels shall comply with Section 1008.2.1 of the International Fire Code and be interfaced to the fire alarm control unit as required. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 80 Section 907.2.1.4 Smoke control is added as follows: 907.2.1.4 Smoke control. Where required by Section 1029.6.2 of the International Building Code for assembly areas with smoke-protected seating. Smoke detection shall be provided as required for smoke control operation in accordance with Section 909.17. The smoke control system shall be activated automatically by an alarm initiated from a smoke detector, heat detector or dedicated sprinkler water flow alarm within the smoke zone. No detector zone shall exceed 22,500 s.f. (2090.31 m2) or serve more than one smoke control zone. Where ceiling heights are 30 ft (7.62m) or greater, air sampling-type smoke detection systems or approved beam detection shall be provided in lieu of ceiling spot smoke detection. Section 907.2.3 Group E is amended as follows: 907.2.3 Group E. Group E occupancies shall be provided with an approved manual fire alarm and automatic detection system throughout the occupancy. Emergency voice/alarm occupant notification shall be provided in accordance with Section 907.5.2.2 of the International Fire Code. Exceptions 1 and 2 to remain. Section 907.2.3 Group E Exception 3 is replaced as follows: 3. Manual fire alarm boxes and automatic detection are not required throughout Group E occupancies that are protected with automatic sprinklers throughout, where all the following conditions are met: 3.1 Interior corridors are protected by smoke detectors. 3.2 Manual fire alarm boxes are provided in the auditorium, cafeteria, gymnasium and staff locations. Section 907.2.3 Group E Exception 4 is replaced as follows: 4. Conversion of existing buildings to a small day care center complying with Section 305.2.4 of the International Building Code and E occupancies with less than 20 occupants excluding staff that is provided with smoke alarms complying with NFPA 72 located throughout. Smoke alarms shall be interconnected and provided with a power source complying with Section 907.2.11.6. Smoke alarms with an integral strobe shall be provided in staff offices and teachers’ lounge. Where battery operated smoke alarms are permitted by Section 305 of the International Building Code, existing buildings shall be provided with battery operated smoke alarms with 10-year tamper proof lithium batteries. Section 907.2.3.1 is added as follows: 907.2.3.1 Existing E occupancies. Where an existing Group E occupancy building undergoes an addition or alteration, an emergency voice/alarm communication system shall be provided throughout the new and existing Group E occupancy in accordance with Section 907.5.2.2 of the International Fire Code. Exceptions: 1. Where the Group E area increase is less than 20% and locations of smoke detectors comply with the existing building coverage. 2. Where the building alteration or addition does not increase the aggregate occupant load of the Group E occupancy to 100 or more. Section 907.2.6 Group I is amended by adding the following after the last sentence: An emergency voice/alarm communication system in accordance with Section 907.5.2.2 of the International Fire Code shall be installed where partial evacuation is provided. Exceptions 3 and 4 are added as follows: 3. A pre-signal system may be installed if approved by the fire code official. Twenty-four-hour personnel supervision is required at approved locations. Chimes may be installed in lieu of audible DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 81 notification appliances as approved by the fire code official. Englewood Fire Marshal approval is required for pre-signal application or alarm verification. 4. Automatic fire detectors are not required in sprinklered areas less than 24 sq. ft. (2.23sq m.). Sections 907.2.6.3.4 Zoning and annunciation and 907.2.6.3.5 Monitoring are added as follows: 907.2.6.3.4 Zoning and annunciation. Alarm, supervisory and trouble signals shall be displayed at the annunciation panel and be transmitted to the central alarm station. Alarm signals shall indicate the type of alarm and the zone of origin, in accordance with NFPA 72. Separate zones shall be provided for individual fire protection systems, buildings, building levels, cell complexes and sections of floors constructed as smoke compartments. 907.2.6.3.5 Monitoring. The fire alarm system shall be monitored by an approved central alarm station service or by transmission of a local alarm which will give audible and visible signals at an approved constantly attended location. Section 907.2.6.4 Group I-4 day care facilities: Day care occupancies shall be provided with an approved manual fire alarm and automatic detection system throughout the occupancy. Occupant notification shall be provided in accordance with IFC Section 907.5, as amended. Conversion of existing buildings to small day care centers shall comply with this section. Exceptions: 1. If less than 50 occupants, the system is not required to be monitored by a central alarm station. 2. Where the occupant load is 20 or fewer manual fire alarm systems and automatic smoke detection systems are not required where 120v AC smoke alarms with battery back-up, wired to an un- switched source are provided. 3. Manual fire alarm boxes are not required throughout the building where all the following apply: a. Interior corridors are protected by smoke detectors. b. System central alarm station monitoring is provided. c. Manual boxes are provided in locations supervised by staff in accordance with Item 4 below. 4. Where an approved automatic sprinkler system is installed throughout a Group I-4 day care occupancy, manual pull stations shall only be required in locations supervised by staff, (e.g. teachers' or nurses' lounge, custodial office, boiler room, administrative areas, auditorium and cafeteria). Notification appliances that activate on sprinkler waterflow and/or activation of a pull station shall be provided throughout. Section 907.2.10 Single- and multiple station-station smoke alarms is replaced as follows: 907.2.10 Single- and multiple station-station smoke alarms. Listed single- and multiple station-station smoke alarms complying with UL 217 shall be installed in accordance with Sections 907.2.10.1 through 907.2.10.6 of the International Fire Code, and NFPA 72, Chap 29. As approved by the fire code official, smoke alarms may be connected to a fire alarm system for supervision only. Smoke alarms within dwelling and sleeping units shall be inspected and tested in accordance with NFPA 72, Chapter 14 and the manufacturer’s instructions. A hard-copy log of all inspections, testing, maintenance and battery changes shall be kept at the property. This log shall include the dates of inspection, testing, maintenance and battery change and the person performing such. Upon request, a copy of the log shall be provided to the fire code official. If this information is not current or available, an inspection shall be made to inspect and test all devices or the property owner or agent of the property owner shall be directed to retain a contractor licensed to inspect and test all devices and submit a report of the inspection findings to the fire code official. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 82 Exception: Residential occupancies regulated by the International Residential Code shall comply with the applicable provisions of that code. Section 907.2.10.2 Item 4 is added as follows: 4. Placement of combination smoke and carbon monoxide alarms in buildings containing dwelling units shall comply with Section 915.7. Section 907.2.12 High-rise buildings is replaced as follows: 907.2.12 High-rise buildings. High-rise buildings provided with a fire command center in accordance with Section 508, manual fire alarm boxes located in accordance with Section 907.4.2 of the International Fire Code and an automatic fire alarm and detection system in accordance with Section 907.2.12.1 of the International Fire Code, a fire department communication system in accordance with Section 907.2.12.2 of the International Fire Code, and an emergency voice/alarm communication system in accordance with Section 907.5.2.2 that provides occupant notification of alarm on the fire floor, floor above, floor below and at the level of the FCC. Exceptions 1-6 to remain. Section 907.2.12.1. Automatic smoke detection is amended by adding items 3, 4, 5 and 6 as follows: 3. In all interior corridors serving as a means of egress for Group R-1, R-2 and R-4 occupancies, with an occupant load of 10 or more. 4. Not less than one foot but no more than three feet on the occupied side of each door that enters a refuge area, elevator lobby and exit stairway which does not directly exit from a refuge area, for occupancies other than R-1, R-2 and R-4. 5. At the top of stairwells and in elevator hoistways (heat detectors pin accordance with Section 907.3.3). These devices shall initiate an alarm condition and illuminate the respective indicator at the graphic annunciator. They shall not initiate occupant notification or the smoke control sequence. 6. Where unenclosed vertical openings are permitted by Section 712 of the International Building Code, smoke detectors shall be located around the perimeter of the opening, on each level, not less than four feet from the edge of the opening. Unenclosed stairway and escalator openings shall comply with this Section and 712.1.3 of the International Building Code. Two-story openings in other than I-2 and I-3 occupancies shall comply with Section 712.1.9 of the International Building Code. See Section 907.2.13 for atriums. Section 907.2.12.2 Fire department communication system is replaced as follows: 907.2.12.2 Fire department communication system. Two-way telephone communication services shall be connected to a UL 864 listed fire alarm system. Design of the fire department communications system shall consist of both of the following: 1. Hardwired components, in accordance with Section 907.2.12.2.1, consisting of permanent handsets, amplifiers and cable system for selective and “all-call” operation. Components shall be listed under UL product category code designation UOXX. 2. Radio communications using the emergency responder radio communications enhancement System (RES) in accordance with Section 510, designed and installed for full coverage in accordance with Section 510.1.1. Section 907.2.12.2.1 Hardwired systems is added as follows: 907.2.12.2.1 Hardwired systems. A two-way, Fire Department communication system shall be provided for Fire Department use, each phone on the two-way Fire Department communication system shall have a DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 83 separate control switch on the fire alarm control unit which distinctly identifies the location of the phone in use. The vertical riser and distribution wiring shall be installed in accordance with the National Electrical Code and shall comply with the pathway survivability requirements of NFPA 72, 24.5. Section 907.2.12.2.1.1 Handsets is added as follows: 907.2.12.2.1.1 Handsets. Permanently mounted telephone handsets shall be provided. Each permanently mounted handset shall initiate a signal from the handset to the FCC. Permanently mounted telephone handsets shall be provided in the locations listed below: 1. Each mechanical room with fans used for smoke control 2. Emergency and standby power rooms 3. Each fire pump room 4. Each elevator equipment room Section 907.2.12.4 Alarm notification is added as follows: 907.2.12.4 Alarm notification. Alarm notification in high-rise buildings shall comply with Section 907.5 of the International Fire Code, and notify occupants on the floor in alarm, the floor above, the floor below and at the level of the fire command center. Silence function shall be provided to independently silence notification appliances at the level of the FCC. This function shall be accomplished by an approved switch located in the FCC. Section 907.2.12.5 Smoke control system activation is added as follows: 907.2.12.5 Smoke control system activation. Smoke control systems shall be automatically activated by alarm-initiating devices including return riser duct detectors, water flow switches, manual pull stations, and manual operation from the fire command center (FCC), in accordance with Sections 907.2.12.5.1 and 907.2.12.5.2. After the initial alarm activation, any subsequent automatic alarm activation on another floor shall initiate the floor exhaust sequence in accordance with Section 907.2.12.5.2. Exception: Main sprinkler system water flow, heat or smoke detectors located in stair or hoistway enclosures, kitchen hood suppression activation and sprinkler system water flow in building service chutes or shafts. 907.2.12.5.1 Activation of pressurization. Activation of stair and elevator hoistway enclosure pressurization shall be initiated by activation of any alarm-initiating device in accordance with Section above Exception: On vegetated roofs, activation of rooftop manual pull stations shall not activate building vertical pressurization systems. 907.2.12.5.2 Smoke control exhaust. Exhaust in a smoke control zone shall be automatically activated by any automatic fire alarm or sprinkler initiating device within the respective smoke control zone. Unless otherwise approved by the fire code official, each floor of a high-rise building shall be considered a separate smoke control zone. Exceptions: Kitchen hood suppression system activation. Section 907.2.12.6 Annunciation is added as follows: 907.2.12.5 Annunciation. Graphic annunciation in accordance with Section 907.6.4.1.2 or computer graphic annunciation in accordance with Section 907.6.4.1.3 shall be provided. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 84 Section 907.2.12.7 Elevator status/control panel is added as follows: 907.2.12.6 Elevator status/control panel. An elevator status/control panel shall be provided. The elevator status/control panel shall: 1. Identify each elevator cab alphanumerically and the floors it serves. Identify corresponding cab number in elevator cab. 2. Indicate elevator(s) that are operating on emergency power. Visual indicators in accordance with ASME A17.1 are required. 3. Have a placard at elevator status/control panel stating how many elevators can operate under emergency power simultaneously. 4. Indicate elevator car position. 5. Indicate whether the elevators are operational. 6. Indicate direction of travel. 7. Have key switches as required for selective activation of cars if all are not capable of simultaneous operation on secondary power. 8. Phase I Fire Service Recall Key switches in accordance with ASME A17.1. 9. Two-way communication system from the elevator to the FCC shall be incorporated on the elevator status panel. Two-way communication systems shall meet ASME A17.1. No other elevator functions shall be installed on these panels without approval from the fire code official. Section 907.2.12.7.1 Fire service elevator status panels is added as follows: 907.2.12.7.1 Fire service elevator status panels. Status of designated fire service elevators shall be displayed on an approved standard emergency services interface in accordance with Section 919.9. These indications shall be combined with the requirements of Section 907.2.12.7. Section 907.2.12.8 Emergency generator status panel is added as follows: 907.2.12.8 Emergency generator status panel. An emergency generator status panel shall be provided. The emergency generator panel shall show: 1. Operating status (on-off) and malfunction indication as required by NFPA 110 2. Indication of transfer switch position (normal-emergency) 3. Indication that generator is in automatic mode 4. Main fuel oil storage tank low fuel level alarm. Section 907.2.12.9 Fire pump status panel is added as follows: 907.2.12.9 Fire pump status panel. A fire pump status panel shall be provided. The fire pump panel shall have: 1. Remote operating status indication as required by NFPA 20. 2. Motor/engine running/on or off. Pump running indication shall be transmitted to the fire alarm control panel as a supervisory signal and distinctly annunciated. 3. Low fuel level alarm for fire pump fuel tank. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 85 Section 907.2.13 Atriums connecting more than two stories is replaced as follows: 907.2.13 Atriums connecting more than two stories. A smoke detection and smoke exhaust system shall be provided in atriums that connect more than two stories. The smoke exhaust system shall be designed in accordance with Section 909.4 907.2.13.1 Activation. Activation of two smoke detectors in the atrium shall initiate the atrium exhaust sequence. In high-rise buildings, activation of a smoke detector located in areas separated from the atrium by a smoke barrier shall operate in accordance with Section 907.2.12.4. 907.2.13.2 Detection. Detection shall be as follows: 1. Area type smoke detectors, spaced in accordance with NFPA 72, shall be installed at the atrium ceiling where the ceiling is 30 feet (9.144 m) or less from the floor of the atrium. If the ceiling is greater than 30 feet (9.144 m) from the atrium floor, beam type detectors shall be installed. A detection system with alarm verification may be installed. The initial device in alarm shall initiate a supervisory condition at the fire alarm panel. 2. On the underside of projections into the atrium, spaced in accordance with NFPA 72. 3. Around the perimeter of the atrium opening on all floors open to the atrium. The detectors shall be spaced not more than 30 feet (9.144 m) on center and shall be located within 15 feet (4.572 m) of the atrium opening. 4. In high-rise buildings, where any part of the floor is open to an atrium, smoke detectors shall be located throughout the floor not included in the atrium area for every 2500 sq. ft. (232.258 sq m) of occupied floor space. No smoke detector shall serve more than one smoke zone. 5. All smoke detectors shall be accessible for maintenance and testing. Sections 907.2.19.1 Smoke detection in covered malls is added as follows: 907.2.19.1 Smoke detection in covered malls. Where covered malls require a smoke control system in accordance with Section 402.7.2 of the International Building Code, smoke detection shall be provided in accordance with Section 907.2.13.1.2. Section 907.2.22 Battery rooms is amended by adding an Exception as follows: Exception: A dedicated, detached on grade structure not to exceed 1,000 square feet. Section 907.3.1 Duct smoke detectors is amended by replacing Exception 1 as follows: 1. Spot-type smoke detectors may be used for return air system connection to vertical risers serving two or more stories in accordance with NFPA 72. Detectors shall be listed for the maximum anticipated airflow velocity. Detectors concealed above the ceiling shall be provided with a remote indicating light mounted on the ceiling directly below the device. Remote indicating lights shall be installed in an accessible, visible area directly below or adjacent to the detector in accordance with Section 907.4.3.1. Section 907.3.3 Elevator emergency operation is replaced as follows: 907.3.3 Elevator emergency operation. Automatic fire detectors installed for elevator emergency operation shall be installed in accordance with ASME A17.1 and NFPA 72. Where required, fixed temperature 190-degree F heat and smoke detectors shall be provided for shunt trip and recall operation. Where sprinklers are not provided in elevator hoistways in accordance with NFPA 13, 8.15.5, 135-degree F heat detectors shall be installed at the top of the hoistway for recall operation. Where elevator machinery is installed in a non-sprinklered hoistway, 135-degree F heat detectors shall be installed at the top of the hoistway for recall operation. Smoke detectors shall be installed in all machine rooms, control rooms and machine and control spaces. Where environmental or other conditions prohibit installation of smoke DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 86 detectors for recall, 135-degree F fixed temperature heat detectors shall be permitted to substitute for the required recall smoke detectors. In buildings with a fire alarm system, these detectors shall be connected to the building fire alarm system. Exceptions: 1. For existing buildings undergoing an elevator alteration, replacement or new installation, an administrative modification shall be submitted for approval where an existing complying fire alarm control unit cannot be expanded within its listing to accommodate required devices for recall and shunt trip. Upon approval by the fire code official, a temporary “elevator recall and supervisory panel” shall be installed in accordance with the provisions of the Administrative Modification. This panel shall report alarm and supervisory signals to the main FACP. The duration of a temporary elevator recall control and supervisory control unit installation shall not exceed 36 months from the date the temporary control unit permit is issued. Building plans shall be permanently mounted adjacent to the panel per 907.6.4.1.1.1. 2. For existing buildings undergoing an elevator alteration, replacement or new installation, and not equipped with a required fire alarm system, a dedicated “elevator recall control and supervisory control unit” shall be provided. This panel shall be located in accordance with Section 907.1.5. Building plans shall be permanently mounted adjacent to the panel per Section 907.6.4.1.1.1 Sections 907.3.3.1 In buildings without a fire alarm system is added as follows: 907.3.3.1 In buildings without a fire alarm system, system smoke detectors and a dedicated fire alarm system control unit shall be provided that is designated as an “elevator recall control and supervisory panel.” The system shall be designed and installed in accordance with NFPA 72 and ASME A17.1. Section 907.3.3.2 Where sprinklers are provided in elevator shafts and machine rooms, spaces or control rooms or spaces is added as follows: 907.3.3.2 Where sprinklers are provided in elevator shafts and machine rooms, spaces, or control rooms or spaces, elevator power shunt trip shall be activated prior to sprinkler operation in accordance with NFPA 72. Section 907.3.3.3 Shunt trip circuit breakers shall be located is added as follows: 907.3.3.3 Shunt trip circuit breakers shall be located in either the main power distribution room or installed in the elevator machinery room/space in a NEMA 3R enclosure. Section 907.3.3.4 System smoke detectors shall be located in elevator lobbies, sprinklered hoistways and machine/control rooms/spaces is added as follows: 907.3.3.4 System smoke detectors shall be located in elevator lobbies, sprinklered hoistways and machine/control rooms/spaces. Activation of these smoke detectors shall return to level of exit discharge, nonstop, all elevators serving that, lobby or with control equipment in the affected machine/control room/space except for the smoke detector in the elevator lobby at level of exit discharge which shall return the elevators to an alternate level. Elevators without a landing at level of exit discharge shall be returned to the landing that is closest to level of exit discharge or other approved level. The alternate level shall be approved by the fire code official. Elevators shall remain at the level where they returned, with doors open, until being manually overridden by the operator key switch required by ASME A17.1 or the elevator control panel in the FCC. Use of detector relay bases for recall activation is specifically prohibited. Exception: Upon recall, elevators in pressurized hoistways shall return to the designated or alternate level. Doors shall remain open for 60 seconds and then close. Section 907.3.3.5 Elevator firefighter indicator is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 87 907.3.3.5 Elevator firefighter indicator. Section 2.27.3.2.6 of ASME A17.1/CSA B44-2013 is deleted as a reference. Operation of the elevator firefighter indicator shall comply with Section 907.3.3.5.1 or 907.3.3.5.2. Section 907.3.3.5.1 New elevators is added as follows: 907.3.3.5.1 New elevators. When elevator recall is initiated by detection devices located in the elevator lobby, the firefighter indicator shall illuminate steady. Independent of the initiating device, when a detection device located in the elevator hoistway, machine room or other elevator control space activates, the firefighter indicator shall illuminate intermittently (flashing). Section 907.3.3.5.2 Alterations to existing elevators is added as follows: 907.3.3.5.2 Alterations to existing elevators. Where an existing elevator is modified under any alteration encompassing a scope of work described under 7CCR 1101-8, the elevator firefighter indicator shall function in accordance with Section 907.3.3.5.1. This requirement applies when any alterations are made to the firefighter’s emergency operation. Section 907.4.3.1 Automatic sprinkler system is renumbered to 907.4.3.2. Section 907.4.3.1 Remote indicating lights is added as follows: 907.4.3.1 Remote indicating lights. A remote indicating light shall be installed for detector(s) within each room with an entry door. The indicating light shall be located on the wall or ceiling above the door and within 12 inches (30.48 cm), on the exit corridor side. This shall include each door leading through adjoining or intervening rooms from an exit corridor to that room (progressive type). Remote indicating lights shall be installed on the ceiling directly below detectors located above ceilings. Remote indicating lights shall latch "on" and remain lit (steady or flashing at a minimum rate of one flash per second) until the fire alarm system is reset. Exception: Remote indicating lights may be deleted where a point-lit or computer graphic annunciator is provided. Section 907.5 Occupant notification systems is amended by adding Exceptions 2 and 3: 1. Smoke alarms in dwelling units and rooms used for sleeping purposes in R-1 occupancies. Duct detectors shall initiate a supervisory signal only. 2. Occupant notification shall not activate upon operation of detectors at the top of stairwells or in elevator hoistways or main or service chute water flow devices. Section 907.5.2 Alarm notification appliances is replaced as follows: 907.5.2 Alarm notification appliances. Audible and visible alarm notification shall be provided to alert occupants of the area having a fire alarm system as well as in the means of egress serving the occupancy. The fire alarm control panel shall incorporate an alarm silencing switch that shall only de-activate the audible notification appliances until the system is manually reset. Alarms shall be provided in accordance with Sections 907.5.2.1, 907.5.2.2 and 907.5.2.3, and as required by other sections of this code. Notification appliances shall be listed for the purpose. Section 907.5.2.1 Audible alarms is amended by adding the following after the last sentence: In theaters, nightclubs, dance halls, ballrooms and similar areas, means shall be provided to reduce or eliminate background noise upon activation of the fire alarm system. Fire alarm audible notification shall comply with Sections 907.5.2.1.1 and 907.5.2.1.2. Section 907.5.2.1 Audible alarms Exception 1 is replaced as follows: 1. Alternate alarm notification shall be permitted in critical care areas of Group I-2 occupancies as DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 88 approved by the fire code official. Section 907.5.2.1.3 Low frequency alarms is added as follows: 907.5.2.1.3 Low frequency alarms. Low frequency alarm signal appliances shall be provided for general alarm notification to all sleeping units in accordance with NFPA 72, 18.4.5.3. Section 907.5.2.2.3 Alternate uses is replaced as follows: 907.5.2.2.3 Alternate uses. The emergency voice/alarm communication system may be used for other emergency communication announcements with the approval of the fire code official. Section 907.5.2.2.6 Low frequency alarm signal is added as follows: 907.5.2.2.6 Low frequency alarm signal. A minimum of two cycles of an alert tone complying with NFPA 72, 18.4.5.3 shall precede and follow required voice evacuation messages. Section 907.5.2.2.7 Background noise reduction is added as follows: 907.5.2.2.7 Background noise reduction. In very high noise areas, such as theaters, nightclubs, ballrooms and dance halls, the system shall be designed to reduce or eliminate the background noise upon alarm activation. Section 907.5.2.2.8 Communication system location is added as follows: 907.5.2.2.8 Communication system location. All buildings provided with and emergency voice/alarm communications system shall have the communication systems and other life safety equipment located in a fire command center (FCC) or fire command room constructed in accordance with Section 508. Section 907.5.2.3.2 Visible notification appliances in Groups I-1 and R-1 occupancies is replaced as follows: 907.5.2.3.2 Visible notification appliances in Groups R-1and I-1 occupancies. Group R-1and I-1 sleeping and dwelling units shall be provided with visible notification activated by an integral in-room smoke alarm required by Section 907.2.11. Visible notification appliances shall also be provided which are activated by the building fire alarm and/or automatic sprinkler system. The minimum number of sleeping units per building to be provided with visible notification appliances shall be in accordance with Table 907.5.2.3.2. All accessible units required by Table 1107.6.1.1 of the International Building Code. shall be provided with visible notification appliances as part of this requirement. Section 907.5.2.3.3 Group R-2 is replaced as follows: 907.5.3.3 Visible notification appliances in Group R-2 occupancies. Group R-2 sleeping and dwelling units shall be provided with visible notification activated by an integral in- room smoke alarm required by Section 907.2.11. Visible notification appliances shall also be provided which are activated by the building fire alarm and/or automatic sprinkler system. The minimum number of sleeping units per building to be provided with visible notification appliances shall be in accordance with Table 907.5.2.3.2. All accessible units required by Table 1107.6.1.1 of the International Building Code shall be provided with visible notification appliances as part of this requirement. Section 907.5.2.3.4 Visible notification appliances in R-3 and R-4 occupancies is added as follows: 907.5.2.3.4 Visible notification appliances in R-3 and R-4 occupancies. Sleeping rooms shall be provided with visible notification activated by an integral in-room smoke alarm. Visible notification appliances shall also be provided which shall be activated by the building fire alarm and/or sprinkler system, where provided. Exception: Buildings that do not contain more than two dwelling units. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 89 Section 907.6 Installation and monitoring is replaced as follows: 907.6 Installation and monitoring. A fire alarm system shall be installed and monitored in accordance with this section and NFPA 72. Section 907.6.1 Wiring is replaced as follows: 907.6.1 Wiring. Fire alarm system and communications wiring shall comply with provisions of NFPA 72 and NFPA 70 (NEC) Article 760. Wiring color code shall be consistent throughout the entire system and permanently posted inside the fire alarm control panel. Separate colors shall be used for each type of initiating circuit, indicating circuit and control circuit. Color coding shall be by continuous colored insulation or by application of six-inch (15.24 cm) long colored heat-shrink tubing at the end of each conductor at all splices, taps and terminations. Wiring shall not be painted. Wireless protection systems utilizing radio-frequency transmitting devices shall comply with the special requirements for supervision of low-power wireless systems in NFPA 72. Section 907.6.1.1 Survivability is added as follows: 907.6.1.1 Survivability. Where occupant relocation or partial evacuation is part of the building life-safety plan, fire alarm system communication and other required emergency communication systems survivability shall be provided in accordance with NFPA 72 and this Section. Audible and visible notification appliance circuits, and firefighter two-way communications, shall be designed and installed such that attack by fire within an evacuation zone shall not impair control and operation of the system outside the evacuation signaling zone. Exceptions: 1. Two-way communication systems at elevator landings or elevator lobby areas of rescue assistance as required by Section 1009.8 of the International Building Code. 2. Notification appliance circuits shall not be routed through stairway enclosures except for the required appliances located in the stairway enclosure. Section 907.6.1.1.1 System Design is added as follows: 907.6.1.1.1 System design. Where survivability is required, the systems wiring shall be designed to meet Pathway Survivability Level 3 in accordance with NFPA 72. Exception: Stacked electrical closets that are separated from the remainder of the building by two- hour fire-resistance rated fire barriers are permitted as a “protected area” for application of NFPA 72, 12.4.4(3). Where communication “risers” are routed horizontally because the rated rooms do not stack, the wiring shall be installed utilizing circuit integrity cable installed in conduit per UL FHIT.28 or routed in 2-HR fire resistance rated horizontal assemblies. Section 907.6.1.2 Communication systems in existing buildings is added as follows: 907.6.1.2 Communication systems in existing buildings. Where occupant partial evacuation/relocation notification is provided and the existing communication systems comply with one of the performance design alternatives below, those systems shall be permitted to remain. The systems shall be maintained in accordance with the original design. Retrofit of existing systems are permitted to comply with the provisions of this section. 1. Separate "A" and "B" risers with alternating floor speakers, designed such that no more than ½ the speakers on a floor shall be affected by loss of any one amplifier, pre-amplifier or cable within the floor or communication zone. 2. Class A wiring configuration for risers and floor distribution provided system survivability is maintained in the event of a failure of any distributed or banked amplifier to limit the failure to no DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 90 more than ½ the notification appliances on the floor plate in the notification zone. Internally backed- up amplifier modules are acceptable. 3. Class A wiring configuration for risers and class B floor distribution wiring with alternating speakers such that system survivability is maintained in the event of a failure of any distributed or banked amplifier to limit the failure to no more than ½ the notification appliances on the floor plate in the notification zone. Internally backed-up amplifier modules are acceptable. Section 907.6.1.3 Monitoring integrity is added as follows: 907.6.1.3 Monitoring Integrity. Conductors and connections that interconnect equipment, devices and appliances shall be monitored for integrity, in accordance with NFPA 72, Chapter 12. Power supplies and in-building fire emergency voice/alarm communication systems shall be monitored for integrity in accordance with NFPA 72, Chapter 10. Section 907.6.4 Zones is replaced as follows: 907.6.4 Zones. All fire alarm systems shall be divided into alarm zones. When two or more alarm zones are provided, visible zone indication shall be provided at an approved location. Zones shall comply with this section unless otherwise approved by the fire code official. Trouble and supervisory signals shall be indicated in accordance with this section and NFPA 72. Annunciator panels shall comply with Section 907.6.4.1. Annunciation zones shall comply with the following: Each building level shall be annunciated separately as follows: 1. All manual devices. 2. All automatic devices. 3. Where standpipes are required in accordance with Section 905, at each fire sprinkler water flow detection device. Sprinkler zones shall comply with NFPA 13. Separate visible indication shall be provided for: 1. Main fire sprinkler flow. Individual risers in accordance with Section 903 of the International Fire Code. 2. Each special extinguishing system 3. Each non-required system 4. Each special detection system 5. Each stairway (where detection is provided) 6. Each emergency alarm system in accordance with Sections 908 and 915 and Chapters 50 and 53. 7. Each elevator hoistway and machine room (separate zone indication for smoke and heat detectors as provided) 8. System trouble 9. Sprinkler control valves (supervisory only). Maximum 20 devices per zone 10. Duct detectors (supervisory only). Maximum 20 devices per zone 11. Fire pump running supervisory indication 12. Elevator shunt trip power supervisory indication 13. Radio enhancement system power supervisory indication DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 91 14. Area of rescue assistance two-way communication supervisory indication 15. Radio enhancement system malfunction supervisory indication 16. Radio communicator trouble Section 907.6.4.1 Annunciator panels is replaced as follows: 907.6.4.1 Annunciator panels. Annunciator panels shall be point-lit graphic or computer graphic or a directory LED point display type as approved by the fire code official. Upon initiation of an alarm, supervisory or trouble condition the panel shall record the status. Alarms shall “lock-in” until the fire alarm system is reset with a dedicated reset switch located at the main fire alarm control panel. Annunciation lights shall be red for “Alarm” and yellow for “Trouble” and “Supervisory” signals. Each signal type shall be distinctly identified. Exception: Where a monitored building fire alarm control unit is not provided, annunciator panels are not required for a dedicated function elevator recall control and supervisory control unit or sprinkler waterflow and supervisory control unit. 907.6.4.1.1 Directory annunciator. A directory annunciator shall be provided as required. Location shall be field approved. The annunciator shall be provided with individual alarm indications in accordance with Section 907.6.4 for each zone. Indicators shall be of sufficient size and intensity to be visible in normal lighting. 907.6.4.1.1.1 Building plans. Scaled floor plans shall be permanently mounted adjacent to directory type annunciator panels. Plans shall be of durable construction, easily readable in normal lighting, protected by a smooth, transparent, plastic surface and shall include every building level including mezzanines and roofs. Plan content shall comply with Appendix N. 907.6.4.1.2 Point-lit graphic annunciator. A graphic annunciator shall be provided as required in Sections 907.6.4.1.2.1 through 907.6.4.1.2.3. 907.6.4.1.2.1 When required. A point-lit graphic annunciator is required for the following: underground buildings, high-rise buildings, buildings with a smoke control system in accordance with Section 909 and where required for a pre-action fire sprinkler or clean agent extinguishing system in accordance with Section 907.6.7. 907.6.4.1.2.2 Location in building. Location of annunciators shall be field approved. Locations depicted on reviewed drawings are not permitted until field verification is secured. 907.6.4.1.2.3 Graphics. The annunciator shall consist of building plans in accordance with Appendix N, with the addition of discrete LED indications for each alarm and supervisory initiating device. The annunciator shall be provided with a momentary push-button “Lamp Test.” Separate indications for “Trouble” and “Supervisory” conditions shall be provided. Section 907.6.4.1.3 Computer graphic display is added as follows: 907.6.4.1.3 Computer graphic display. Computer graphic displays shall be permitted for individual system designs. Systems shall be fully compliant with UL 864. Systems shall contain a full color primary and secondary display. Demonstration of the specific equipment to be installed with the actual operating software for the proposed system shall be presented to the fire code official. Operator interface to the graphic shall be based on: 1. Ease of use. Primary operator interface shall be standard 2-button mouse driven. Optional secondary interfaces may be provided. 2. Adequacy of display for operational purposes. Displays shall be capable of presenting the entire floor plate with all devices and device status shown on an initial alarm screen. On any alarm DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 92 indication, the floor plate in alarm shall come up on the screen with all devices shown and the device in alarm highlighted. Display segmentation from this initial view shall be possible for expanding the view of the area of alarm incidence. Displays shall be contrasting black lines and lettering on a white background. 3. Flexibility of system for upgrade. 4. Minimal proprietary components. Accepts standard picture file types. 5. Plain English report generation of events, histories, maintenance schedules, device status and settings and user access. 6. UL-864 listed event-driven primary display. Secondary display(s) as approved by the fire code official. All displays shall be specified for 24-hour, 7-day continuous operation. A 3-year warranty is recommended. 7. Secure access. 8. Fire alarm device icons shall be in accordance with NFPA 170 or graphic icons as approved by the fire code official. Building plans in accordance with Section 907.6.4.1.1.1 shall be provided and shall be located as approved by the fire code official. Section 907.6.7 Pre-action and clean agent extinguishing systems is added as follows: 907.6.7 Pre-action and clean agent extinguishing systems. Pre-action and clean agent extinguishing systems shall have a dedicated releasing panel and annunciator connected to the building fire alarm system where provided. Pre-action systems shall be installed in accordance with NFPA 13. Clean agent systems shall comply with Section 904.10. Control panels shall be listed for releasing service. Control panel and annunciator shall be located outside the protected area in a location approved by the fire code official. Areas protected by a single releasing panel shall be contiguous. Shop drawings for system installations shall be submitted in accordance with Appendix N, NFPA 13 and NFPA 2001. Cross-zoned detection systems shall transmit a building alarm on activation of the first initiating device. Fire protection piping and initiating device, control and annunciation drawings shall be submitted together. Clean agent systems are supplemental and not permitted to substitute for required automatic sprinkler systems unless specifically approved by the fire code official. Section 907.6.7.1 Annunciation is added as follows: 907.6.7.1 Annunciation. Pre-action and clean agent systems shall be provided with a local directory annunciator zoned for manual, smoke detector, flow alarm and tamper supervisory indications in accordance with Section 907.6.4.1.1. Systems with under floor and/or above ceiling detection devices shall be provided with a point-lit graphic annunciator in accordance with Section 907.6.4.1.2. Systems shall annunciate alarm and supervisory conditions at the main building fire alarm panel. Section 907.6.7.2 Application of pre-action systems is added as follows: 907.6.7.2 Application of pre-action systems. The types of pre-action systems that are approved for use in accordance with NFPA 13 are: single interlock, non-interlock and double-interlock systems. Installation of double-interlock pre-action systems shall be subject to approval by the fire code official. Section 907.11 Non-required full or partial systems is added as follows 907.10 Non-required full or partial systems. Fire alarm systems and fire detection systems not required in this Code or by special agreement are not required to be connected to a central station. Where non- required fire alarm and/or fire detection systems are connected to a central station, the central station shall be an approved Class I central station. Multiple central station connections from one building are not DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 93 permitted unless approved by the fire code official. Installation of non-required full or partial fire alarm or fire detection systems shall comply with NFPA 72, Chapter 23. Zone annunciation shall be provided in accordance with Section 907.6.4. Annunciator and control panels for non-required or partial systems shall be of an approved type and have permanent signage indicating “Non-required System” or “Partial System.” Partial and non-required systems shall be maintained operational. System removal shall be permitted only with the approval of the fire code official. Exception: New and existing dwellings regulated by the International Residential Code. Section 907.11.1 General system design and installation requirements is added as follows: 907.11.1 General system design and installation requirements. Shop drawings must be submitted for approval. Documents shall be stamped and signed by a professional engineer licensed by the State of Colorado and shall comply with Section 907.1.2. Non-required systems installed in a building with a required fire alarm system shall have the non-required system connected to the required fire alarm control panel. Each non-required system shall annunciate as a separate zone at the required fire alarm control panel. Multiple fire alarm control panels are not allowed where a required system is installed. Section 907.11.2 Design criteria is added as follows: 907.11.2 Design criteria. Design of non-required fire alarm systems shall comply with the following: 1. A minimum of one audible/visible alarm appliances per floor in an approved location. 2. One initiating device zone per floor. 3. Existing duct detectors are not required to be connected to a non-required system. 4. Secondary power is required for the FACP in accordance with NFPA 72. 5. Multiple non-required, non-monitored systems in a building are not required to be interconnected. SECTION 908 EMERGENCY ALARM SYSTEMS Section 908.3 Emergency Fuel Shut Off (EFSO) for Aircraft Fueling is added as follows: 908.3 Emergency Fuel Shut Off (EFSO) for Aircraft Fueling. Emergency alarms for notification of an emergency condition involving aircraft fueling shall be provided as required in Section 2006.6. Section 908.4 Emergency alarm systems is added as follows: 908.4 Emergency alarm systems. Manual emergency alarm systems shall be designed in accordance with this section and the manual fire alarm requirements of NFPA 72. Manual emergency alarm-initiating devices shall be yellow or amber, comply with the mounting requirements of Section 907.4.2 and be installed outside of each interior exit and exit access door, and inside of each exterior exit and exit discharge directly serving the potentially contaminated area(s) identified in Sections 908.1 through 908.3 unless otherwise approved by the fire code official. Emergency alarm systems shall be monitored by the building fire or sprinkler alarm control panel unless otherwise approved by the fire code official. An emergency alarm system shall be annunciated as a separate zone on the building annunciator and transmitted to the central station as a separate/distinct signal and be relayed to DFD Dispatch as such. Where the fire or sprinkler alarm control panel is not monitored by a supervising station, annunciation shall be provided in an approved location. Floor plans of the area protected by an emergency alarm system shall be provided as part of the building graphic maps. Audible and visible emergency alarm notification appliances shall be installed on the interior and exterior DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 94 of the areas identified in International Fire Code Sections 908.1 through 908.3 per the notification requirements of NFPA 72. Audible and visible notification appliances along with clearly legible signage shall be installed inside and outside of these occupancies in approved locations to alert all occupants possibly inside or entering the potentially contaminated area. Audible emergency alarm notification shall have tone and pattern distinctly different from fire alarm notification. Visible notification appliances shall be amber strobes or beacons. Subject to the approval of the fire code official, complete notification in accordance with NFPA 72 throughout a building or facility beyond the potentially contaminated area is not required provided the potential for migration of the hazard to other occupied areas is small. Signage shall be placed adjacent to the amber strobes/horns. The sign shall have a minimum 2 -inch block lettering with a minimum ½-inch stroke unless otherwise approved by the fire code official. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. Language shall be as approved by the fire code official. Section 908.4.1 Emergency alarm systems shop drawings is added as follows: 908.4.1 Emergency alarm systems shop drawings. Shop drawings for emergency alarm systems shall be submitted for permit application as a deferred submittal in International Building Code. Plan review and approval are required prior to issuance of a permit for system installation. Two sets of scaled, engineered installation shop drawings shall be submitted. Documents shall be of sufficient clarity and detail to fully describe the scope of work. Handwritten notes and comments on reproduced drawings are not acceptable. Submittals shall comply with Appendix N. Section 909 Smoke Control Systems is replaced as follows: SECTION 909 SMOKE CONTROL SYSTEMS 909.1 Scope and purpose. This section applies to mechanical smoke control systems when they are required by other provisions of this code. The purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. Smoke control systems regulated by this section serve a different purpose than the smoke- and heat-venting provisions found in Section 910. Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the International Mechanical Code. Exceptions: 1. This provision does not preclude application of the performance based design calculations. 2. Stairway and hoistway pressurization system designs in high rise buildings where the uppermost occupiable floor is more than 250 feet above the lowest level of fire department vehicle access, and all healthcare occupancy groups, shall be performed by an engineering analysis. 909.2 General design requirements. Buildings, structures or parts thereof required by this code to have a smoke control system or systems shall have such systems designed in accordance with the applicable requirements of Section 909 and the generally accepted and well-established principles of engineering relevant to the design. The construction documents shall include sufficient information and detail to adequately describe the elements of the design necessary for the proper implementation of the smoke control systems. These documents shall be accompanied by sufficient information and analysis to demonstrate compliance with these provisions. 909.3 Smoke control systems. As required by other sections of this code, smoke control system(s) shall be provided for high-rise buildings, atriums, covered malls, underground buildings, assembly occupancies with smoke-protected seating, stages and areas in accordance with Section 410 of the International Building Code, DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 95 airport buildings in accordance with Appendix S of the International Building Code, and assembly occupancies with an aggregate of 1,000 or more occupants in high-rise buildings. This requirement shall be applicable to the Occupancy Groups as follows: A; B; E; M; R-1; R-2, and I-1 and I-3. 909.3.1 Unenclosed vertical openings. Where unenclosed vertical openings are provided as permitted by Section 712 of the International Building Code, buildings with a smoke control system shall have the floor openings between smoke zones protected by draft curtains and closely spaced sprinklers installed in accordance with NFPA 13 smoke detectors located at the floor side of the opening. 1.4 Construction document submittals. Construction documents for smoke control systems shall be submitted for permit application with the construction drawings for the project in accordance with Section 154 including the seal and signature of the design professional responsible for the coordination of the smoke control design package 1.5 Shop drawing submittals (deferred submittal). The deferred submittal shall be consistent with the approved construction document submittal and reviewed by the engineer of record prior to submission to the Englewood Fire Marshal in accordance with Appendix N. 1.6 Smoke barrier construction. Smoke barriers shall comply with Section 709 of the International Building Code. 1.7 Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power system. Secondary power shall be from an approved emergency or standby source complying with NFPA 70 (NEC). The secondary power source and its transfer switches shall be in a separate room from the normal power transformers and switchgear and shall be enclosed in a room constructed of not less than 1-hour fire barriers ventilated directly to and from the exterior. Power distribution to the automatic transfer switch from the two sources shall be by independent routes. Transfer to secondary power shall be automatic and in compliance with NFPA 70 (NEC). 909.7.1 Power sources and power surges. Elements of the smoke control system relying on volatile memories or the like shall be supplied with uninterruptible power sources of sufficient duration to span a 15-minute primary power interruption. Elements of the smoke control system susceptible to power surges shall be suitably protected by conditioners, suppressors or other approved means. 909.7.2 Wiring. In addition to meeting requirements of NFPA 70 (NEC), all wiring, regardless of voltage, shall be fully enclosed within continuous raceways in mechanical rooms, electrical rooms, elevator equipment rooms and vertical risers. Wiring shall not be painted. The detection and control system wiring shall be clearly marked at all junctions, accesses and terminations. 909.8 Firefighter’s smoke control panel. A firefighter’s smoke control panel meeting the requirements of UL 864 and listed for smoke control under UL product category guide designation UUKL shall be provided and shall include manual control or override of automatic control for mechanical smoke control systems. Upon an alarm, the fire alarm system shall take direct control of all smoke control system components such as fans, dampers, activation of dedicated pressure control systems and status indication. The fire alarm system shall provide a signal to any temperature control or building automation systems for HVAC system enable/disable control and status. Where HVAC systems are utilized for smoke control the fire alarm system shall take direct control of those HVAC system components utilized for smoke control. Hard-wired interlock is acceptable. The fire alarm system shall provide automatic and manual override control and status. Terminal air distribution units may remain under their own normal building automation control. The panel shall be located in a fire command center complying with Section 509 in high rise buildings or buildings with smoke-protected assembly seating. In all other buildings, the firefighter’s smoke control panel shall be installed in an approved location adjacent to the fire alarm control panel. The firefighter’s smoke control panel shall comply with Appendix N. 909.8.1 Smoke control systems. The firefighter’s control panel shall be provided for manual or override of automatic control of mechanical smoke control systems. This panel shall graphically depict the individual DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 96 smoke control system fan and damper controls, their relative location within the building, stairwells, hoistways, building pressurization and exhaust airflow, refuge area pressurization and all other smoke control zones that apply. This panel shall clearly show the building arrangement and smoke control zones served by the systems. The graphic panel shall be oriented to the building and include a North reference compass point. A combination of vertical (section) and/or horizontal (plan) graphic arrangement may be necessary. The operating control and status indicators on the FSCP shall have a maximum height from the floor of 6 feet, 6 inches and a minimum of 2 feet, 0 inches, and may require more than one section to accommodate height limitations. Layout, labeling and location of the fire fighters control panel shall be reviewed and approved by the Fire Department prior to fabrication. 909.8.2. Verification. Control systems for mechanical smoke control systems shall include provisions for verification. Verification shall include positive confirmation of actuation, testing, manual override and the presence of power downstream of all disconnects. A preprogrammed weekly test sequence shall report abnormal conditions audibly, visually and by printed report. The preprogrammed weekly test shall operate all devices, equipment, and components used for smoke control. 909.9 System response time. Smoke control system activation shall be initiated immediately after receipt of an appropriate automatic or manual activation command. Smoke control systems shall activate individual components (such as dampers and fans) in the sequence necessary to prevent physical damage to the fans, dampers, ducts and other equipment. The total response time for individual smoke control systems to achieve their desired operating mode shall not exceed the following time periods: Fan operating at desired state – 75 seconds Damper position travel – 60 seconds 909.10 Testing of smoke control systems. Before the Fire Department accepts the smoke control systems and prior to initial occupancy, the smoke control systems shall be tested in their presence to confirm that the systems operate in compliance with this Section. In addition, all smoke control systems shall be tested annually and shall be maintained to perform its intended purpose under the code version with which it was built. 909.10.1 Acceptance testing. The requirements of acceptance testing defined hereinafter shall be the minimum requirements. All acceptance tests shall be witnessed by a Fire Department representative. 1. Furnish a testing procedure, reviewed by the smoke control system design professional engineer, to the Fire Department 72 hours in advance of the acceptance tests being performed. The procedure shall define how compliance with the code will be demonstrated. The procedure shall also identify what instrumentation including artificial smoke generating equipment, will be used during the testing. 2. Smoke control systems testing shall include the following subsystems to the extent that they affect the operation of the smoke-control system: a. Fire alarm system (See NFPA 72) b. Building automation and temperature control system c. HVAC equipment d. Electrical equipment e. Power sources including emergency or standby power f. Automatic suppression systems g. Automatic operating doors and closers h. Dedicated and non-dedicated smoke-control systems i. Emergency elevator operation DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 97 3. Prior to witnessed acceptance testing of the smoke control systems, the design professional engineer shall confirm and advise the Fire Department in writing that the entire smoke control system has been installed, air balanced and tested in accordance with its design, plans, specifications and this code. 4. The following shall be notified so that they may witness the acceptance testing: a. Design professional Engineer-of-Record b. Building contractor c. Owner’s representative d. Englewood Fire Marshal e. Englewood Building Department 5. Unless otherwise approved by the Fire Department, sufficient smoke shall be generated to produce at least the volume of the smoke zone being tested within approximately five (5) minutes. All smoke- generating devices shall be supplied by the owner or his representative and shall meet with the approval of the fire code official. 6. Acceptance testing shall demonstrate that the correct outputs are produced for a given input for each control sequence specified. The following control sequences shall demonstrate complete smoke -control sequence. a. Normal mode b. Automatic smoke-control mode for first alarm c. Manual override of normal and automatic smoke-control modes d. Return to normal 7. After the smoke control system is activated, smoke shall not continue to migrate to other smoke zones of the building. 8. Smoke control systems shall demonstrate the ability to inhibit smoke from migrating across smoke zone boundaries to other areas and containment within the active smoke zone. Smoke control systems shall also demonstrate the continual reduction of smoke concentration from within the active smoke zone by demonstrating exhaust rates of at least 40% during incident (sealed floor except one stairway door in open position) and at least 80% of the design rate in post fire conditions for salvage and overhaul operations. These system capabilities shall be measured and verified with anemometers or similar measurement tools during acceptance testing at the exhaust intake locations. 909.10.1.1 Testing requirements. Tests shall be performed in full automatic mode with the building operating under both normal power and emergency power. Test equipment shall include manometer (calibrated within last 12 months), spring scale and other equipment as necessary to adequately measure and record system performance. Communications shall be provided between the test locations and the fire command center. 1. For a building that is not a high rise, multiple tests on more than one floor or smoke zone shall be required to demonstrate proper operation. 2. For high rise buildings, tests shall be conducted at a minimum of three locations. a. A floor in the lower third, a floor in the middle third and a floor in the upper third of the building. b. With a floor in alarm, an additional automatic alarm shall be initiated on a floor immediately above or below the initial floor in alarm. All floors in alarm shall go to exhaust mode DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 98 c. With a floor in alarm, a manual pull station on another floor shall be activated. Smoke control operation shall not be affected. d. For atriums, more than one test may be required depending upon the atrium configuration, its relationship to adjacent spaces and if the atrium is located in a high-rise. e. Activation of one smoke detector in each smoke control zone on each floor being tested. f. Activation of at least one sprinkler flow switch. g. Activation of at least one manual pull station. 3. For high rise buildings, pressure differentials shall be measured across stairway doors, across elevator/lobby/refuge corridor area doors and adjoining spaces, between atriums and areas immediately adjacent to atriums where atriums are part of a high-rise building. Door opening force into stair enclosures or refuge areas shall not exceed 30 lbs. under any conditions. 4. Upon activation of the fire alarm system for each test, confirm that the smoke control system fans and dampers have assumed the correct operating condition for the type of alarm initiating device and the location of the initiating device. This shall be confirmed also at the smoke control panel in the fire command center. 5. Manually override the operation of a sampling of fans and dampers during each test, taking care not to damage system components. Return all override switches to their “auto” position after each test. 6. Make-up air provisions may include: a. Stairway doors on the fire floor may be opened and used as a source of make-up air during smoke exhaust system testing. b. Variable frequency drives for smoke exhaust system fans may be controlled in response to duct static pressure settings. c. Dedicated make-up air systems. d. Other methods as documented in the design submittals and approved by the fire code official. 909.10.3 Annual tests. Annual tests shall be performed in accordance with Sections 909.10.3.1 and 909.10.3.2, on all smoke control systems including those installed prior to adoption of this code. It is recognized that smoke control systems installed prior to adoption of this Code could have parameters that are different than those described in this section. In those cases, smoke control tests shall be adjusted accordingly to meet the intent of this section. Englewood Fire Marshal representatives shall have the authority to witness any regularly scheduled annual testing of smoke control systems. 909.10.3.1 Equipment operating tests. The following equipment operating tests shall be conducted annually on the smoke control system components: 1. Verify the proper control and status indication of smoke control dampers (i.e., "OPEN/CLOSED") and fans (i.e., "ON/OFF") by visual observation at each damper and fan location and at the smoke control status/control panel in the fire command center. 2. Verify that all smoke control dampers and fans assume the correct operating position under both normal and fire modes and when the manual override switches at the smoke control status/control panel are placed in the "auto" position. 3. Verify that the manual override switches function properly for smoke control dampers and fans. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 99 4. Items l, 2 and 3 above may be performed by qualified service technicians who are familiar with the proper operation of the smoke control systems and equipment. The engineer responsible for conducting the smoke control system performance tests shall develop the test procedures to be used and review the results obtained by the service technicians, including an actual sampling to confirm the accuracy of the test. A statement summarizing this review shall be included in the performance test report described in Section 909.10.4 that is required to be submitted by the engineer to the Fire Department. 5. A copy of the written test procedure and an accurate log of tests shall be maintained in the fire command center and at either the building management office or the maintenance office. A copy of the previous test report shall be submitted to the engineer responsible for the smoke control performance tests for the engineer's review and approval prior to the smoke control test. Any defects, system modifications and repairs shall be recorded in the log. Necessary corrections shall be made prior to the smoke control performance test. 909.10.3.2 Performance tests. Within 30 days after completion of annual equipment operating tests defined above, conduct the following smoke control system performance tests. The annual smoke control systems tests shall be conducted under the direct supervision of a professional engineer qualified in the testing of such smoke control systems. 1. Activate the smoke control systems automatically through the fire alarm system for tests used to confirm proper sequencing of the system components. Measure actual relative pressure differentials between areas in alarm and adjacent areas and actual door opening forces. 2. For high rise buildings, conduct smoke control tests, observations and measurements of all aspects of the smoke control system at a minimum of 15% of the smoke-controlled floors with a minimum of 3 floors, evenly spaced throughout the vertical sections of the building. Smoke control tests in subsequent years shall be conducted on previously untested floors, as may be practical so that all floors ultimately are tested. 3. For all other buildings, conduct smoke control tests, observations and measurements of all aspects of the smoke control system at a minimum number of locations to demonstrate proper performance as approved by the Fire Department. Each test shall attempt to involve as many different fan systems as practical. Smoke control tests in subsequent years shall be conducted on previously untested locations, as may be practical so that all locations ultimately are tested over a three-year period. 4. Tests of the smoke control system shall be conducted by activation of at least one smoke detector in each smoke control zone on each floor being tested. One test of at least one of the smoke control zones shall include activation of one sprinkler flow switch. In addition, the smoke control tests shall include activation of at least one manual fire alarm box. For high rise buildings, pressure differentials shall be measured across stairway doors, between floors in alarm and floors immediately above and below floors in alarm, across elevator/lobby/refuge corridor area doors and adjoining spaces in Group R-1, R-2 or I-1 occupancies, and between atriums and areas immediately adjacent to atriums where atriums are part of high-rise buildings. 5. Upon activation of the fire alarm system for each test, confirm that the smoke control system fans and dampers have assumed the correct operating condition for the type of alarm initiating device and the location of the initiating device. This shall be confirmed also at the smoke control panel in the fire command center. 6. Manually override the operation of a sampling of fans and dampers during each test, taking care not to damage system components. Return all override switches to their “auto” position after each test. 909.10.4 Test reports. Within 30 days of completing any smoke control test, submit a test report to the DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 100 Fire Department. A copy of the previous and current test reports shall be kept in the fire command center. The test report shall be written by the professional engineer who conducted the testing. The test report shall bear the seal and signature of the professional engineer. Any defects, modifications and repairs shall be recorded in a log kept in the fire command center and at either the building management office or the maintenance office. The test report shall include, but is not limited to the following: 1. Provide a brief description of the smoke control system installed in the building being tested and state the year the building received its construction permit for the smoke control system. Provide a sequence of operation for the smoke control system. 2. Describe in general terms the equipment operating test procedures. Include a list of the equipment operating and smoke control test deficiencies along with a schedule of the proposed corrective action. 3. Describe detailed procedures followed during the equipment operating tests. Describe detailed procedures followed during the smoke control tests. 4. List test equipment used and outside air temperature and wind conditions at the time the smoke control tests were conducted. 5. State sequences and timing of the system operations during all smoke control tests (e.g., smoke detector activation time, fan start times, time for dampers to assume the correct position, etc.). 6. List the location of test measurements and the measured values for pressure differentials and door- opening forces for each test location. 7. Record any operational defects and performance deficiencies with respect to the requirements of this section, and state recommendations for corrective action. Include a schedule to re-test each deficiency. Submit results of any subsequent tests performed after completion of the corrective action. 8. Engineer’s assessment indicating that the smoke control system, as installed and tested, conforms to the requirements of Section 909. 909.10.5 Functional test requirements for smoke control system equipment. Testing of smoke control equipment shall be performed in accordance with this section to determine that the installed systems continue to operate in accordance with the approved design. Operational testing of the smoke control system shall include all equipment such as fans, dampers, controls, and doors. Testing shall include positive confirmation of actuation. System equipment and components shall be exercised for sufficient time to provide positive confirmation of proper operation or fault condition. 909.10.5.1 Written record. Results of the tests shall be documented in the building’s life safety systems testing and maintenance log and printed reports generated during the automated testing. Testing documents must be maintained on-site in the fire command center or in a location approved by the fire code official. 909.10.5.2 Dedicated systems. 909.10.5.2.1 Dedicated systems shall be tested semiannually. 909.10.5.2.2 The smoke-control system shall be operationally tested as prescribed in Section 909.10.5. Dedicated smoke control systems shall be operated for each control sequence. 909.10.5.2.3 Operation of the correct outputs for each given input shall be verified and recorded. 909.10.5.3 Non-dedicated systems. 909.10.5.3.1 Non-dedicated systems shall be tested annually. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 101 909.10.5.3.2 The smoke-control system shall be operationally tested as prescribed in Section 909.10.5. Nondedicated smoke control systems shall be operated on a representative sample of each type of equipment sufficient to verify proper operation for each control sequence. For high rise buildings, tests shall be conducted at a minimum of 15% of the smoke-controlled floors with a minimum of 3 floors, evenly spaced throughout the vertical sections of the building. Tests in subsequent years shall be conducted on previously untested floors, as may be practical so that all floors ultimately are tested. For all other buildings, tests shall be conducted at a minimum number of locations to demonstrate proper performance as approved by the Fire Department. Tests in subsequent years shall be conducted on previously untested locations, as may be practical, so that all locations ultimately are tested over a three-year period. Operation of the correct outputs for each given input shall be verified and recorded. 1.1.6 System repairs and maintenance. All deficiencies noted in the annual report will be corrected within 30 days and, if required by the engineer, the smoke control system shall be re-tested. All smoke control systems will be maintained to perform its intended purpose under the code version with which it was built. As stated in Section 107, correction and abatement of violations of this code shall be the shall responsibility of the owner. With approval of the Englewood Building Department and the Englewood Fire Marshal Office smoke control systems may be remodeled to comply with current code. 909.11 System acceptance. Buildings, or portions thereof, required by this code to comply with this section shall not be issued a certificate of occupancy until such time that the fire code official determines that the provisions of this section have been fully complied with and that the fire department has received satisfactory instruction on the operation, both automatic and manual, of the system. Exception: In buildings of phased construction, a temporary certificate of occupancy, as approved by the fire code official, shall be allowed provided that those portions of the building to be occupied meet the requirements of this section and that the remainder does not pose a significant hazard to the safety of the proposed occupants or adjacent buildings. 909.12 Smokeproof enclosures. For buildings required to comply with Sections 403 or 405 of the International Building Code, a smokeproof enclosure shall consist of an enclosed, pressurized stairway or ramp conforming to Section 909.15.1 and 1023.11 of the International Building Code and this Section. 909.12.1 Ventilation systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment and ductwork shall comply with one of the following: 1. Equipment and ductwork shall be located exterior to the building and directly connected to the smoke proof enclosure or connected to the smoke proof enclosure by ductwork enclosed by two- hour fire barriers. 2. Equipment and ductwork shall be located within the smoke proof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by two-hour fire barriers. 3. Equipment and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by two-hour fire barriers. 909.13 Design criteria. All smoke control systems shall comply with the requirements of Sections 909.13.1 through 909.13.10. All equipment shall have local operating controls disabled when in smoke control mode. Equipment internal faults shall not cause shutdown of the smoke control equipment unless approved in writing by the fire code official. Equipment including, but not limited to, fans, current transducers (CT’s), differential pressure transmitters, sail switches, ducts, duct protecting materials, automatic dampers, balance dampers, actuators, linkage, limit switches and motor controllers shall be suitable for their intended use. Equipment functions and operating characteristics shall not detract from the smoke control systems’ stable and reliable DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 102 performance. Upon smoke control activation, VFD’s shall operate in override or life safety mode where faceplate commands and non-smoke control commands are ignored. In addition, non-critical faults (safeties) shall be ignored to ensure the continued and stable performance of the smoke control fan. 909.13.1 Minimum pressure differential. The minimum pressure differential across stairway and hoistway smokeproof enclosures on fire floors, shall be +0.05-inch water gauge (0.0124 kPa) with pressurization fans turned on and fire floor in exhaust mode. Where elevator lobbies are provided, the pressure differential shall be measured between the pressurized lobby and fire floor with pressurization fans turned on and fire floor in exhaust mode. Minimum operating performance of pressurization fans shall not be less than 12 Hz for VFD’s or the motor control’s minimum manufacturer published rating. 909.13.2 Maximum door opening force. The maximum pressure difference across a smoke barrier or smoke zone and an opening into a stair enclosure shall be determined by the required door-opening forces. Door opening force shall not exceed 30 pounds applied horizontally at the latch side of the door on the door-opening device under any operating condition. Maximum door opening force shall not exceed 15 pounds at stairway entry doors during a non-fire mode of operation. Opening force at elevator lobby doors shall comply with International Building Code and be measured on the fire floor with the hoistway pressurization fans turned on and fire floor in exhaust mode. 909.13.3 Resistance to smoke recirculation. Locate outdoor air intakes for pressurization systems remote from points of discharge for smoke exhaust systems in order to minimize the potential for recirculation of smoke to the outdoor air intakes. The minimum separation distance shall be 10 ft. in any direction. 909.13.4 Determination of the volume of a space. The volume of a given building element shall be defined as the space that is contained between the finished floor slab(s) of one level and the underside of the floor or roof element above, and the walls or partitions that form the boundaries of the space. 909.13.5 Fire/Smoke damper temperature rating. The temperature rating for the thermal element in fire and combination fire/smoke dampers, where they are applied in smoke exhaust systems, shall be no less than 250° F. For systems where the probable temperature rise to which the damper will be exposed may be higher than 250° F the temperature shall be computed by an approved method. 909.13.6 Fans. In addition to other requirements, belt-driven fans shall have 1.5 times the number of belts required for the design duty, with the minimum number of belts being two. Fans shall be selected for stable performance based on normal temperature and, where applicable, elevated temperature. Calculations and manufacturer’s fan curves shall be part of the documentation procedures. Fans shall be supported in accordance with Chapter 16 of the International Building Code. Motors driving fans shall not be operated beyond their nameplate horsepower (kilowatts), as determined from measurement of actual current draw, and shall have a minimum service factor of 1.15. 909.13.7 Motor controllers and variable frequency drives (VFDs). Motor controllers and variable frequency drives (VFDs) provided to operate fans of smoke exhaust and pressurization systems shall be installed in secure, conditioned and protected locations. These devices shall be located in a room or space separated from the remainder of the building by a 1-hour fire-resistance rated fire barrier. Power wiring and control wiring between switchgear and /or panels, motor controllers, VFDs and smoke control system motors and control dampers shall be in non-flexible metallic raceway up to the component connection. VFDs for smoke control system fans shall not be equipped with a manual or automatic bypass switch except where fans are designed and set for 60 hertz, nominal. Exception: The final connection to the component shall be made with the appropriate flexible conduit in accordance with NFPA 70 (NEC). 909.13.8 Ducts. Duct materials and joints shall be capable of withstanding the probable temperatures and pressures to which they are exposed during smoke control operating conditions. Ducts shall be constructed and supported in accordance with the International Mechanical Code. Ducts shall be leak tested to 1.5 times the maximum design pressure in accordance with nationally accepted practices. Measured leakage shall not DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 103 exceed 5 percent of design flow. Results of such testing shall be a part of the documentation procedure. Ducts shall be supported directly from fire-resistance-rated structural elements of the building by substantial, noncombustible supports. Exception: Flexible connections (for the purpose of vibration isolation) complying with the International Mechanical Code, that are constructed of approved fire-resistance-rated materials. 909.13.9 Equipment, inlets and outlets. Equipment shall be located so as to not expose uninvolved portions of the building to an additional fire hazard. Outside air inlets shall be located so as to minimize the potential for introducing smoke or flame into the building. Exhaust outlets shall be so located as to minimize reintroduction of smoke into the building and to limit exposure of the building or adjacent buildings to an additional fire hazard. 909.13.9.1 Vegetated roofs. Stairway and hoistway pressurization system intakes shall be separated by a minimum of 15 feet from vegetated areas. 909.13.10 Automatic dampers. Automatic dampers, regardless of the purpose for which they are installed within the smoke control system, shall be listed and conform to the requirements of approved, recognized standards. 909.14. Smoke control systems for atriums (where required by Section 404 of the International Building Code). 909.14.1 Requirements. The operation of the smoke control systems shall be controlled through the fire alarm system and shall comply with the requirements of this Section. The atrium volume shall include all spaces not separated from the atrium by the provisions of Section 404.6 of the International Building Code. 909.14.2 Operation. Where required by Section 907.2.14, activation of initiating devices shall cause the following sequence to occur: 1. Open atrium exhaust dampers. 2. Open supply dampers to atrium. 3. Close exhaust dampers on all adjacent smoke zones. 4. Start exhaust fans. 909.14.3 Atrium exhaust. The system shall exhaust a minimum of six air changes per hour. A minimum of 50 percent of the volume of supply air shall be sized and introduced via gravity supply or fan powered inlets within 10 feet of the lowest level of the atrium. The total volume of supply air shall be 75 percent of the required volume of exhaust air. A maximum velocity of 200 feet per minute shall be maintained across the net free area of the supply air openings. 909.14.4 Exhaust openings. Atrium exhaust openings shall be located in the ceiling or in a smoke trap area immediately adjacent to the ceiling at the top of the atrium. The lowest level of the exhaust openings shall be above the top of the highest elevation of door openings into the atrium. 909.15 Smoke control systems for high-rise buildings. 909.15.1 Stairway pressurization systems. 909.15.1.1 Requirements. Where the uppermost landing of an exit enclosure serves an occupiable floor located more than 75 feet above the lowest level of fire department vehicle access road, the stairway enclosure and associated exit passageway shall be mechanically pressurized with outdoor air, via one or more separate, dedicated pressurization systems. The operation of each stairway pressurization system shall be controlled through the fire alarm system. Fire, smoke, or fire/smoke dampers are prohibited in stairway pressurization systems. Isolation dampers are permitted in the DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 104 outdoor air intake ductwork, where such dampers are provided with a hard-wired interlock with the drive or starter, that proves “damper open” position, and that the damper is configured to “fail” open from a control standpoint. Each stairway pressurization system shall be enclosed in an approved two- hour fire-resistive rated fire barrier and/or horizontal assembly from the outdoor air intake to the stairway enclosure penetration. Ductwork shall not be required within the stairway enclosure. Exception: Where ductwork is not provided for stairway pressurization, stairway shaft leakage shall not exceed 10% of actual supply, exclusive of the door leakage. 909.15.1.2 Operation. Each fan discharge shall be provided with a duct smoke detector that shall annunciate a supervisory signal at the fire command center (graphic annunciator) and shall illuminate a lamp adjacent to the fan status indicator at the firefighter’s smoke control panel. The capability to manually override the operation of each fan shall be provided to the Fire Department personnel in the fire command center. Fans shall not shut off until manually overridden by Fire Department personnel or until the fire alarm system is reset. Each stairway pressurization system shall indicate that the system is moving air at the firefighters smoke control panel in accordance with Appendix N. Monitoring of air flow is permitted to be accomplished with torque indication on a variable frequency drive, differential pressure across the fan or current switches on the power feed to the fan. Variable frequency drives used for smoke control systems shall not be required to be UUKL listed. The drive shall not fail to a greater capacity than that associated with the control setpoint for the fan. 909.15.1.3 Design. The air volume introduced into the stairway shall be as follows: 15 floors or less, at least 800 cfm per floor; 16 floors or more, at least 10,000 cfm, plus 200 cfm per floor in excess of 15 floors with 0.5-inch water column static pressure minimum at the duct penetration into the stairway. In order to comply with the requirements of Section 909.13, dynamic static pressure control shall be provided for stairway pressurization fans. Either dynamic static pressure or fixed speed controls shall be provided. Dynamic static pressure controls are permitted to be tuned and set to a fixed value. Air for the stairways serving buildings where the uppermost occupied floor is more than 120 feet above the lowest level of fire department vehicle access shall be introduced into the stairway at a minimum of two injection points. One injection point shall be located not more than 50 feet above the grade plane. In buildings where the uppermost landing of an exit enclosure serves an occupiable floor located more than 250 feet above the lowest level of fire department vehicle access, an engineered design shall be required. 909.15.2 Hoistway pressurization systems. 909.15.2.1 Requirements. Each elevator hoistway with a total rise of 75 feet or more or any elevator hoistway serving any occupiable floor located more than 75 feet above the lowest level of fire department vehicle access shall be mechanically pressurized with outdoor air, via one or more a separate, dedicated pressurization systems in accordance with Section 909.15.1.1. Where hoistway pressurization is provided in lieu of required enclosed elevator lobbies in any building as permitted by Section 3006.3 Item 4 of the International Building Code, design shall comply with provisions of Section 909.15.2.3 909.15.2.2 Operation. System operation shall comply with Section 909.15.1.2. 909.15.2.3 Design. The air volume introduced into the elevator hoistway shall be as follows: 15 floors or less, at least 900 cfm per floor, plus 270 CFM per door opening, with 0.5-inch water column static pressure minimum at the duct penetration into the hoistway; 16 floors or more, at least 13,500 cfm, plus 270 cfm per door opening, with 0.5 inch w.c. static pressure minimum at duct penetration into the hoistway. In order to comply with the requirements of Section 909.13, dynamic static pressure control shall be provided for hoistway pressurization fans. Dynamic static pressure or fixed speed controls shall be provided. Dynamic static pressure controls are permitted to be tuned and set for a fixed value. In buildings where the uppermost elevator landing serves an occupiable floor located more than 250 feet above the lowest level of fire department vehicle access, an engineered design shall be required. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 105 Hoistway pressurization system performance shall not interfere with the opening and closing of elevator doors. Refer to Chapter 30 of the International Building Code for door operation. 909.15.2.4 Smoke venting to exterior. Smoke venting of pressurized elevator hoistways to the exterior of the building shall not be required. 909.15.2.5 Elevator machine rooms. Elevator machine rooms may be pressurized indirectly via the elevator hoistway pressurization system through the cable slots in the machine room floor. 909.15.2.6 Lobby/ Areas of rescue assistance. Elevator lobbies designated as areas of rescue assistance are permitted to have the elevator lobby/area of rescue assistance pressurized using the elevator hoistway pressurization system by transferring air to the elevator lobby area of rescue assistance from the hoistway. The lobby/area of rescue assistance shall be pressurized by the transfer of air from the pressurized hoistway through the leakage at the elevator doors. Where approved by the fire code official, use of transfer openings protected with fire/smoke dampers between the hoistway and the lobby/area of rescue assistance is also acceptable. 909.15.3 Smoke exhaust systems. 909.15.3.1 Requirements. Smoke exhaust system(s) shall be provided in high-rise buildings system shall be controlled via the fire alarm system, to operate in conjunction with the other applicable smoke control systems for the building, in order to achieve the objectives as follows: 1. To maintain a zone of negative pressure in the fire floor (or smoke zone) relative to the other floors or adjacent smoke zones, means of egress stair enclosures and elevator lobby/refuge areas; and... 2. To maintain a maximum stair enclosure or smoke barrier door opening force on the fire floor or smoke zone in alarm. The prescriptive approach described herein is not intended to preclude the use of a performance-based smoke control approach, such as that defined by NFPA 92. 3. Maintenance of tenable environment is not required in the smoke-control zone of fire origin 909.15.3.2 Configuration. Smoke exhaust systems shall include motorized combination fire/smoke dampers or a motorized smoke and a fire damper on each floor of a multi-level building served by the system(s). The exhaust damper(s) in the fire floor smoke zone in alarm shall be commanded open, in order to exhaust that zone, and the smoke exhaust fan commanded to “ON”. The exhaust dampers in other smoke zones shall be driven to, or shall remain in, the closed position. The use of smoke dampers shall not preclude the provision of fire dampers, where required by other sections of this code. Exhaust damper(s) shall be located within the upper third of the finish floor height. 909.15.3.3 Design criteria. The general building smoke exhaust system(s) for each floor/smoke zone shall be sized in accordance with the following: 1. The smoke exhaust system shall be sized to remove a minimum of 5 air changes per hour on the fire floor in Occupancy Groups A, B, E and M. 2. The smoke exhaust system shall be sized to remove a minimum of 15 air changes per hour in the typical floor corridors, the typical floor corridors/elevator lobbies, or the typical floor elevator lobbies in Occupancy Groups R-1, R-2, I-1 and I-3. Amenity spaces less than 3,000 sf in Groups R-1 and R-2 occupancies are not required to be provided with a separate smoke exhaust system. 3. That appropriate consideration shall be made for damper leakage on non-fire floors connected to a central riser system, when selecting the smoke exhaust fan(s). 4. Smoke exhaust systems shall be in ducts constructed in accordance with Section 909.13.8. 5. The engineer shall design make-up air to be available to the smoke zone in alarm so exhaust rates satisfy 909.10.1(8). Submittal documentation shall include analysis presenting DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 106 methodology for achieving such. 909.15.3.4 Operation. Upon activation of an automatic alarm initiating device as described in Section 907, the following smoke control sequence shall occur: 1. Turn off all supply and make-up air fans, unless used to afford make-up air to the smoke exhaust zone. 2. Open exhaust dampers on the zone in alarm. 3. Close smoke exhaust dampers to all other smoke zones. 4. Close all supply air dampers, unless used to afford make-up air to the smoke exhaust zone. 5. Initiate stairway and elevator hoistway pressurization sequences in accordance with Sections 909.15.1 and 909.15.2. 6. Start exhaust fans. 909.15.4 Street level tenant exception. Smoke exhaust systems shall not be required to serve individual tenant areas or lobbies located on the level of building egress. 909.15.5 Small assembly areas or similar uses exception. Smoke exhaust for assembly areas or similar uses 3,000sf (278m2) or less shall not be required when these areas are separated by smoke partitions constructed in accordance with Section 710 of the International Building Code. 909.16 Smoke control systems for parking garages within high rise structures. 909.16.1 Requirements. Elevator lobbies designated as refuge areas on all floors within an enclosed parking structure shall have the elevator lobby/refuge area pressurized using the elevator hoistway pressurization system by transferring air to the elevator lobby/refuge area. Use of transfer openings protected with fire/smoke dampers between the hoistway and the lobby/refuge area is acceptable. 909.16.2 Open parking garages. A general building smoke control system shall not be required for elevator lobbies that are enclosed and that serve an open parking garage, if direct access without stairs or obstructions is available for people with special needs to exit from the elevator lobby to the open parking garage level or directly to a public way. 909.16.3 Enclosed garages. Exhaust fans associated with an enclosed parking structure shall be capable of manual operation from the smoke control panel. Such exhaust fans will not require a redundant source of electrical power, and this shall be indicated at the smoke control panel with the words, “Not on Emergency Power.” 909.17 Smoke exhaust for assembly occupancies with 1,000 occupants or more in high-rise buildings, stages and areas in accordance with Section 410 of the International Building Code, and underground buildings. 909.17.1 Requirements. Each area shall be separated into smoke zones not to exceed 52,000 square feet on a single floor. Smoke zones shall be separated from each other by walls that extend from the floor to the underside of the floor or roof above except for the following: 1. Openings into atriums. 2. Pedestrian bridges between two buildings. 3. Non-required stair enclosures between floors. 4. Open escalators between multiple floors. 5. Where draft stops as prescribed in Section 909.17.2.1 are provided. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 107 909.17.2 Design criteria. Building construction shall be configured in order to support the performance of the smoke exhaust system, in accordance with the following: 1. Where wall separation is not provided between smoke zones, draft stops shall be provided. The configuration of the draft stops shall be as approved by the Building and Fire Departments. 2. A smoke zone in alarm shall actuate the respective smoke exhaust system, while smoke exhaust systems in adjacent smoke zones remains inactive. 3. Where smoke zones have wall separations, a positive static pressure differential shall be maintained between adjacent non-alarm zones, relative to the smoke zone in alarm. 4. Sprinkler and smoke detection zones shall coincide with smoke zones. 5. Products of combustion must be demonstrated to be contained within the zone of origin, for smoke zones without wall separations. Failure to restrict products of combustion to the floor or area of origin shall be considered non-compliant with the performance requirements for the smoke exhaust system. 909.17.2. Assembly area smoke zones shall be separated from adjacent zones by draft stops located immediately adjacent to each smoke zone. The draft stops shall be at least 18 inches deep. The draft stops shall be of non-combustible or limited combustible material that will stay in place before and during sprinkler operation. Exception: Assembly areas smoke zone separation from adjacent smoke zones is not required for ceiling heights 18 feet and greater. 909.17.3 Design criteria. The smoke exhaust system shall exhaust a minimum of six air changes per hour. 909.17.3.1 Operation. Upon activation of a fire alarm initiating device in accordance with Section 907, smoke control operation shall comply with the following: 1. Open exhaust dampers for smoke zone in alarm 2. Start smoke zone exhaust fans 3. Close supply dampers to smoke zone in alarm 4. Adjacent zones go to 100% outside air 5. All other systems maintain normal operation 909.18 Reserved. 909.19 Smoke control systems for covered mall buildings. Where required by Section 402 of the International Building Code smoke control systems shall comply with Section 909.14. 909.20 Alteration of smoke control systems in existing high-rise buildings. Smoke control systems shall be maintained in operational condition as required by the code under which the system was installed. The system alteration may be considered for application under this code with approval by the fire code official, provided that; the building is fully protected by automatic sprinklers complying with current NFPA 13 provisions for high rise buildings, the building has complying standpipes, and smoke detection is provided in accordance with Section 907.2.12.1.1. Upon approval, the altered configuration shall be considered the new requirement and documented as approved by the Englewood Building Department and the Englewood Fire Marshal. Future work shall not be allowed to adversely affect the performance of the system. Construction drawings and system sequence of operation shall be submitted for approval in accordance with Appendix N. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 108 SECTION 910 SMOKE AND HEAT REMOVAL Section 910.3.1 Listing and labeling is replaced in its entirety as follows: 910.3.1 Listing and labeling. Smoke and heat vents shall be listed and labeled to indicate compliance with UL 793 or FM 4430. Exception: Gravity-operated drop out vents are not permitted. Section 910.3.4 Smoke and heat vent fall protection is added as follows: 910.3.4 Smoke and heat vent fall protection. In Group F, M, and S occupancies fall protection shall be provided meeting minimum requirements of Sections 910.3.4.1 and 1108 Items 1, 2 and 3. Section 910.3.4.1 Fall protection construction is added as follows: 910.3.4.1 Fall protection construction. Fall protection shall be of such construction and mounting that they are capable of withstanding a load of at least 400 pounds per square foot applied perpendicularly at any one area on the screen. Covers shall be secured in place to prevent accidental removal or displacement. Openings limitation shall be not more than 6 inches in diameter or of slatwork with openings not more than 2 inches wide with length unrestricted. SECTION 912 FIRE DEPARTMENT CONNECTIONS Section 912.2 Location is amended by replacing the last sentence as follows: 912.2 Location. With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of fire department connections shall be field approved by the fire code official prior to installation. Fire department connections shall be a minimum of one 2½ x 2½ x 4-inch Siamese or single 2½-inch, as approved by the fire code official. In buildings with standpipes, an FDC shall be located within 100 ft. of a fire hydrant. Section 912.2.3 Orientation is added as follows: 912.2.3 Orientation. Fire department connections shall be oriented so inlets are in a horizontal line. Exception: Two inlets may be stacked with written approval from the fire code official. Section 912.4.1 Locking fire department connection caps is replaced as follows: 912.4.1 Locking fire department connection caps. To prevent vandalism & theft, locking connection caps protecting the inlet and swivel shall be provided and compatible with Englewood key box keys or as approved by the fire code official. Section 912.6 Backflow protection is replaced in its entirety as follows: 912.6 Backflow protection and main flow switch. A backflow preventer and flow switch shall be installed on all potable water supply mains serving all automatic sprinkler systems. Exception: Subject to the fire code official, backflow prevention and a main flow switch may be omitted on automatic sprinkler systems installed a part of a domestic water supply system. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 109 The backflow preventer shall be installed within 5 feet (610 mm) of the point where the main first penetrates the envelope of the building or structure. The main flow switch shall be installed within 2 feet (610 mm) on the system side of the backflow preventer and in addition to all other flow switches required by this code. The automatic sprinkler system shall be configured so that only one flow switch activates an alarm condition by the actuation of a single sprinkler. When the main and other downstream flow switches can be triggered sequentially by the activation of a single sprinkler, only the flow switch closest to that sprinkler shall be monitored as alarm and actuate exterior notification in accordance with Section 903.4.2; the other sequential flow switches shall be monitored as supervisory. SECTION 913 FIRE PUMPS Section 913.1 General is amended by adding the following after the last sentence: 913.1 General. Where provided, fire pumps shall be installed in accordance with this section and NFPA 20. Limited service controllers are not permitted. Access to fire pumps shall comply with Section 509.3. Section 913.2 Protection against interruption of service is amended by adding the following after the last sentence. 913.2 Protection against interruption of service. The fire pump, driver and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions. Except as permitted by NFPA 20, rooms containing fire pumps shall be free of storage, equipment, and penetrations not essential to the operation of the pump and related components. Section 913.2.2 Circuits supplying fire pumps is replaced as follows: 913.2.2 Circuits supplying fire pumps. Installation of cables used for survivability of fire pump circuits shall comply with NFPA 70 (NEC) Article 695. Section 913.4 Valve supervision is replaced as follows: 913.4 Valve supervision. Fire pump suction, discharge and bypass valves and isolation valves on the backflow prevention device or assembly shall be supervised by an approved central station complying with Section 917. Section 913.4.1 Test outlet valve supervision is replaced as follows: 913.4.1 Test outlet valve. The hose control valves for the fire pump test outlet(s) shall be located on the exterior of the building. The main supply valve controlling the fire pump test outlet(s) shall be supervised in the closed position. Section 913.6 is added as follows: 913.6 Fire pump requirement for non-high-rise buildings. Where Class 1 manual wet standpipes are required by other provisions of this code, augmentation of the standpipe system by the Fire Department shall comply with Section 913.6.1. Section 913.6.1 System supply is added as follows: 913.6.1 System supply. Minimum flow rate for the hydraulically most remote standpipe shall be 500 gpm, and the calculation procedure shall be in accordance with NFPA 14. The minimum flow rate for additional standpipes shall be 250 gpm per standpipe, with the total not to exceed 1,000 gpm for buildings that are sprinklered throughout in accordance with NFPA 13 or NFPA 13R. Minimum pressure for system design shall be as required by NFPA 14 with Fire Department pumpers supplying the system with a maximum DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 110 flow rate of 1,000 gpm and a maximum pressure of 175 psi at the fire department connection (FDC). All system components shall be listed and rated for system working pressure. Section 913.7 Remote status panel is added as follows: 913.7 Remote status panel. Where the fire pump room is not constantly attended, a fire pump remote operating status panel shall be provided in accordance with NFPA 20. The fire pump remote operating status panel shall be located adjacent to the fire alarm control panel or as determined by the fire code official. Section 913.8 Diesel engine pump drivers is added as follows: 913.8 Diesel engine pump drivers. Diesel drivers for fire pumps shall comply with NFPA 20. A dedicated fuel supply shall be provided sufficient for eight (8) hours of operation. Fill openings shall be located on the exterior of the building with an approved fill port. If fuel pumping is required from a main fuel tank to a diesel engine pump driver, a duplex pumping system shall be provided. SECTION 915 CARBON MONOXIDE DETECTION Section 915.1.1 Where required is amended as follows: 915.1.1 Where required. Carbon monoxide detection shall be provided in Group I-1, I-2, I-4 and R occupancies and in classrooms in Group E occupancies in the locations specified in Section 915.2 where any of the conditions in Sections 915.1.2 through 915.1.6 exist. Installation of carbon monoxide alarm, detection and combination smoke alarm and carbon monoxide alarms in buildings containing residential dwelling units shall comply with Section 915.7. Provisions of Section 915.7 pertaining to dwelling units supersede other regulations referencing dwellings in Section 915. Section 915.1.5 Private garages is amended by adding the following after the last sentence: 915.1.5 Private garages. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms in buildings with attached private garages. Exceptions below do not apply to R-2 occupancies. Exceptions 1-4 to remain Section 915.3 Carbon Monoxide detection is replaced as follows: 915.3 Detection equipment. Carbon monoxide detection required in dwelling units and sleeping units by International Fire Code Sections 915.1 through 915.2.3 shall be provided by carbon monoxide alarms complying with International Fire Code Section 915.4. Section 915.3.1 Location is added as follows: Exception: One and two Family dwellings and town-homes 915.3.1 Location. In locations outside of sleeping units and dwelling units in buildings that are not equipped with either a fire alarm system or a sprinkler monitoring system, carbon monoxide detection required by Sections 915.1 through 915.2.3, shall be provided by carbon monoxide alarms complying with Section 915.4 or carbon monoxide detection systems complying with Section 915.5. In locations outside of sleeping units and dwelling units in buildings that are equipped with a fire alarm system or a sprinkler monitoring system, carbon monoxide detection required by Sections 915.1 through 915.2.3 shall be provided by carbon monoxide detection systems complying with Section 915.5 electrically supervised by the fire alarm control unit. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 111 Section 915.5 Carbon monoxide detection systems is replaced as follows: 915.5 Carbon monoxide detection systems shall be provided for buildings containing a central fuel- burning appliance. The carbon monoxide detection system shall be monitored by the building fire alarm system, where provided. This requirement applies to any new equipment installation for which a permit is required by the Building Department. Where carbon monoxide detection is provided in buildings with a fire alarm emergency/voice communication system, use of three pulse temporal pattern signal is permitted. Exception: Carbon monoxide detectors are not required for listed fuel-burning cooking appliances. Section 915.5.2 Locations is replaced as follows: 915.5.2 Locations. System carbon monoxide detectors are required for each room containing a central fuel- burning appliance and shall be located within 25 feet of any fuel-burning appliance. This requirement supersedes the locations specified in NFPA 720. Section 915.7 Carbon monoxide (CO) detection and alarm systems is added as follows: 915.7 Carbon monoxide (CO) detection and alarms systems. CO alarms and detectors shall be installed and maintained in buildings with a fuel-burning appliance or an attached garage or both, and contain a dwelling unit, Section 915.7.1 is amended as follows: 915.7.1 Definitions. The following terms are defined for in Chapter 2. CENTRAL FUEL-BURNING APPLIANCE ROOM CO (CARBON MONOXIDE) CO ALARM CO DETECTOR FUEL-BURNING APPLIANCE MULTIPLE-PURPOSE ALARM MULTIPLE STATION ALARM OWNER PLUG-IN SINGLE STATION ALARM TENANT 915.7.2 Standards. CO alarms and detectors shall comply with the applicable provisions NFPA 70 (NEC), NFPA 72 and NFPA 720, including standards referenced therein. Wherever CO alarms and detectors are specified, multiple-purpose devices are permitted, provided they meet the requirements of all applicable NFPA standards, and: 1. The device is listed for use as a CO alarm/detector (e.g., UL 2034), and 2. Where other sensors are permitted and being utilized to satisfy other alarm/functionality provisions of adopted codes, the device is also listed for those operations, e.g. a. UL 217 for Single and Multiple Station Smoke Alarms DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 112 b. UL 268 for Smoke Detectors for Fire Alarm Signaling Systems c. UL 864 for Control Units for Fire-Protective Signaling Systems d. UL 1484 for Residential Gas Detectors e. UL 1971 for Safety and Signaling Devices for Hearing Impaired f. UL 2017 for General Purpose Signaling Devices and Systems g. UL 2075 for Gas and Vapor Detectors and Sensors 915.7.3 When required. CO alarms and detectors shall be installed in dwelling units as specified in Section 915.7.4 in buildings identified in Section 915.7.4.1 and 915.7.4.2, and for which a building permit is issued after July 1, 2009 for any one or more of the following: 1. New building 2. Addition or relocation of a sleeping room 3. Interior remodel of a dwelling unit 4. Installation of a fuel-burning appliance 5. Change in owner or tenant of a dwelling unit 915.7.4 Installation. Required CO alarms and detectors shall be installed in accordance with this Section. CO alarms required in dwelling units in R2, R3, and R4 occupancies and Family Child Care Homes managed by a homeowners association or other common management that will maintain the system may be monitored by an alarm control unit, provided individual devices function autonomously as single- and multiple-station devices in the event the alarm control unit fails. Additional or redundant CO alarms and detectors shall be in accordance with Section 915.7.5. 915.7.4.1 Location. CO alarms shall be installed in dwelling units in all the following locations: 1. Outside of every sleeping room within 15 ft of the sleeping room 2. In a central location on every occupiable level, and 3. In a central location in every sleeping room that contains a fuel-burning appliance. A single device is permitted to fulfill multiple criteria on a single level, provided it meets all of the applicable location requirements. 915.7.4.2 In existing buildings. CO alarms may be hard-wired, battery-powered, or plug-in, and may be single-or multiple-station. Approved battery-only alarms shall comply with Section 1103.9 Exception: Low power radio systems installed in accordance with NFPA 72, NFPA 720 and listed in accordance with UL 864 may be battery powered. 915.7.4.3 In new buildings. CO alarms shall be multiple-station and hard-wired with battery backup. Exception: Low power radio systems installed in accordance with NFPA 72, NFPA 720 and listed in accordance with UL 864 may be battery powered. 915.7.4.4 Central fuel burning appliance rooms. CO detectors monitored by the building fire alarm system shall be installed in all central fuel-burning appliance rooms in new buildings for which a building permit was issued after July 1, 2009, and in central fuel burning appliance rooms in existing buildings containing a fuel burning appliance for which an installation permit was issued by the Building Department after July 1, 2009. Each central fuel-burning appliance room shall be annunciated on its own zone. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 113 Exception: In existing buildings, battery-powered or plug-in single- or multiple-station CO alarms may be installed in central fuel-burning appliance rooms in lieu of system detectors and need not be monitored by a fire alarm system. Approved battery-only alarms shall comply with Section 1103.9. Devices shall be installed within 25 feet of every fuel-burning appliance and initiate an alarm condition when activated. A single device is permitted to fulfill multiple location criteria in a single central fuel- burning appliance room. 915.7.4.5 Visual notification. Where occupant visual notification is installed or accommodated in accordance with Sections 907.5.2.3.2 and 907.5.2.3.3 for smoke alarms, visual notification shall be similarly installed or accommodated for CO alarms and detectors. 915.7.4.6 System type carbon monoxide detectors. Carbon monoxide detectors shall transmit to the central station as a separate/distinct signal and be relayed to DFD Dispatch as such. 915.7.5 Non-required CO alarms and detectors. CO alarms and detectors installed in buildings or occupancies not meeting the criteria identified in Section 915.7 or installed in addition to those required by Sections 915.7.3 or 915.7.4.4, that are monitored by a central station or used for occupant notification shall comply with this Section. Subject to the fire code official, non-required CO alarms do not need to function autonomously in case of alarm control unit failure. SECTION 916 GAS DETECTION SYSTEMS Section 916.2.1 Construction documents is replaced as follows: 916.2.1 Construction documents. Documentation of the gas detection system design and equipment to be used that demonstrates compliance with the requirements of this code shall be provided with the application for permit. Shop drawings for gas detection systems shall be submitted for permit application as a deferred submittal in accordance with Section 133.5 of the Englewood Building Code. Plan review and approval are required prior to issuance of a permit for system installation. Submittals shall comply with Appendix N. Section 916.3 Equipment is replaced as follows: 916.3 Equipment. Gas detection system equipment shall be designed for use with the gases being detected and shall be installed in accordance with manufacturer’s instructions. Separate gas detection system control panels monitored by the building fire or sprinkler alarm control panel, or gas detection system control panels installed in buildings without a fire or sprinkler alarm system are permitted. Where permitted, separate gas detection system control panels shall be installed in approved location outside of the potentially contaminated areas. Multiple separate gas detection system alarm control panels are permitted; however, areas protected by a single gas detection system alarm control panel shall be contiguous. Section 916.4 Power connections is replaced as follows: 916.4 Power Connections. Gas detection systems shall be permanently connected to the building electrical power supply on a locked dedicated circuit or shall be permitted to be cord connected to an unswitched receptacle using an approved restraining means that secures the plug to the receptacle. Section 916.8 System Activation is replaced as follows: 916.8 System Activation. A gas detection alarm shall be initiated where any sensor detects a concentration of gas exceeding the following thresholds: 1. For flammable gases, as gas concentration exceeding 25 percent of the lower flammability limit (LFL). 2. For nonflammable gases, a gas concentration exceeding one-half of the IDLH, unless a different DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 114 threshold is specified by the section of this code requiring a gas detection system. Upon activation of a gas detection alarm, alarm signals or other required responses shall be as specified by the section of the code requiring a gas detection system. Section 916.8.1 Audible and visible alarm signals is added as follows: 916.8.1 Audible and visible alarm signals. Audible and visible gas detection system notification appliances shall be installed on the interior and exterior of the areas required by this code to have a gas detection system per the notification requirements of the NFPA 72 with the exception of CO2 and inert gases in section 5307. Audible and visible notification appliances along with clearly legible signage shall be installed inside and outside of these occupancies in approved locations to alert all occupants possibly inside or entering the potentially contaminated area. Audible gas detection system notification shall have tone and pattern distinctly different from fire alarm and carbon monoxide alarm signals. Visible notification appliances shall be amber strobes or beacons. Subject to the approval of the fire code official, complete notification in accordance with NFPA 72 throughout a building or facility beyond the potentially contaminated areas is not required provided the potential for migration of the hazard to other occupied areas is small. Section 916.9 Signage is replaced as follows: 916.9 Signage. Signs shall be provided adjacent to gas detection system alarm signaling devices that advise occupants of the nature of the signals and actions to take in response to the signal. Signage shall be placed adjacent to the amber strobes/horns. The sign shall have a minimum 2-inch block lettering with a minimum ½-inch stroke unless otherwise approved by the fire code official. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. Language shall be as approved by the fire code official. Section 916.10 Fire alarm system connections is replaced as follows: 916.10 Fire alarm system connections. Gas detection systems shall be monitored by the building fire or sprinkler alarm control panel, where provided. A gas detection system shall be annunciated as a separate zone on the building annunciator and transmitted to the central station as a separate and distinct signal and be relayed to DFD dispatch as such. Where multiple gas detection systems are installed, each shall be monitored annunciated separately. Where the fire or sprinkler alarm control panel is not monioted by a supervising station, annunciation shall be provided in an approved location. Floor plans of the area protected by a gas detection system shall be provided in accordance with the requirements of Section 907.6.4.1.1.1. If two or more zones are provided on a gas detection system, directory-style LED annunciation shall be provided at the emergency alarm control panel. Supervisory and trouble signals shall be annunciated separately with yellow LEDs and alarm signals shall be annunciated with red LEDs. Section 919 Central Alarm Stations is added as follows: SECTION 919 CENTRAL ALARM STATIONS 919.1 General. Where required by Section 907.1.6 as amended, monitored protected premises systems shall be connected to an approved central alarm station. A Class I central alarm station shall comply with this section. Signals shall be transmitted, received and managed in accordance with NFPA 72. Approved central alarm stations shall be listed to UL 827 and as approved by the fire code official. All central alarm stations shall obtain an annual operating license from the Fire Marshal’s Office and meet the facility construction and operational requirements of NFPA 72. Central alarm stations shall be subject to Fire Department inspection during normal DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 115 business hours. Installations found not to maintain facility requirements and/or operating procedures in accordance with NFPA 72 or the certificated listing, shall be subject to license revocation by the Fire Department. Exception: Approved protected premises connected directly to Englewood Police Department Dispatch. 919.2 Communication methods. Communication from a protected premises to a central alarm station shall be by digital alarm communicator transmitter (DACT), two-way RF multiplex system or one-way private radio alarm system in accordance with NFPA 72. Alternative performance-based communication technologies may be presented for consideration by the fire code official for application in the jurisdiction. Performance-based systems shall be submitted for approval under Section 104. Provisions of Section 104 for technical assistance, may be required at the discretion of the fire code official, for determination of the adequacy of the proposed technology to the requirements of NFPA 72 and this code. Fees for department evaluation of performance- based systems shall apply in accordance with the Englewood Building Department fee schedule for “Application for consideration of Alternate Materials, Methods, or Equipment. 919.3 Transmission channels. Transmission channels between a protected premises and central alarm stations shall consist of one of the methods of Sections 919.3.1, 919.3.2, 919.3.3 or as approved in accordance with Section 919.2 for performance-based technologies. Transmission channels shall be monitored for integrity in accordance with NFPA 72. 919.3.1 DACT transmission shall consist of a minimum of one seizable public phone line and an approved NFPA 72 Type 4 or Type 5 two-way RF multiplex system, with a network connectivity (Net/Con) of 6 or less, a minimum one-way private radio alarm system complying with Section 919.3.3 or an approved alternative communication technology in accordance with Section 919.2. 919.3.2 RF multiplex systems shall consist of sufficient UL-listed fire system transmitter/receivers to establish and maintain a minimum Net/Con of 5 or less as measured by manufacturer-approved test equipment. Primary RF multiplex systems shall meet NFPA 72 requirements for a Type 4 network. RF systems that cannot achieve this required level of reliability shall only be permitted as a secondary communication means in accordance with Section 919.3.1. RF communications of fire alarm signals shall only be permitted over a network dedicated to and listed for transmission and receipt of fire alarm signals. Upon application for a system installation permit for any subscriber unit, the central station licensee shall provide documentation verifying that their network complies with the requirements for a listed, dedicated fire alarm signal network for the protected premises. 919.3.3 One-way private radio alarm systems shall consist of a network of radio alarm supervising station receivers, radio alarm repeating station receivers and radio alarm transmitters. The system shall be configured for Type 6 or Type 7 operation in accordance with NFPA 72. Radio communications of fire alarm signals shall only be permitted over a network dedicated to and listed for transmission and receipt of fire alarm signals. Upon application for a system installation permit for any subscriber unit, the central station licensee shall provide documentation verifying that their network complies with the requirements for a listed, dedicated fire alarm signal network for the protected premises. Signal quality shall be supervised and maintained in accordance with NFPA 72. Section 919.4 Runner service is added as follows: 919.4 Runner service. Central stations licensed shall provide runner service to all properties monitored, in accordance with NFPA 72, National Fire Alarm and Signaling Code, and Section 117.6 of the International Fire Code. Section 920 Transmission of City Microwave Signals is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 116 SECTION 920 TRANSMISSION OF CITY MICROWAVE SIGNALS 920.1 General. Construction permits or Certificates of Occupancy shall not be issued for any building or structure exceeding 60 feet (18.3m) in height which interferes or may interfere with the transmission or reception of City microwave communication signals unless the owner of the building or structure provides for installation of equipment to retransmit or redirect the signal as necessary to eliminate any interference. Such equipment shall be approved by and installed at the direction of the Fire Marshal. A service agreement must also be approved by the Fire Marshal where transmission is affected by the proposed building or structure prior to the issuance of any permit or Certificate of Occupancy. Such agreements shall include provisions for easements and access for maintenance, electricity for operation, and replacement of equipment. Section 921 Elevators and Conveying Systems is added as follows: SECTION 921 ELEVATORS AND CONVEYING SYSTEMS 921.1 General. Elevators and other conveyances shall comply with this code, codes and standards as referenced in International Fire Code Chapter 80, Colorado State Regulation 7CCR 1101-8 and the applicable equipment installation and maintenance standards. 921.1.1 Modification or alteration in conveyance structural elements. Engineered installation shop drawings, specifications, analysis and calculations for structural field modification or alteration to a conveyance shall be submitted to City of Englewood Fire Marshal’s Office for review and approval. Drawings shall include all connections impacted by the modification or alteration. All submittals shall bear the stamp and signature of a structural engineer registered in the State of Colorado. Technical assistance shall be provided as required by the fire code official to evaluate submittals for adequacy. Special inspection of all field welds shall be required for quality control. All welding shall be performed by appropriately certified personnel. Costs for technical assistance and special inspections shall be borne by the installation contractor. Field modification or alteration of conveyance structural elements is not permitted without Department approval. 921.2 New installations. Installation shop drawings shall be submitted for approval prior to installation of any conveyance. Conveyances shall be registered with the State of Colorado Division of Oil and Public Safety before issuance of any installation permit. Shop drawing submittal shall comply with this section and Appx N. Colorado State registration is not required for residential conveyances and temporary construction elevators. 921.3 Alterations to existing conveyances. Alterations to existing conveyances as defined in Colorado Code of Regulations 7CCR1101-8 shall require submittal of shop drawings for approval in accordance with Section 921.2. Conveyances shall have a valid Colorado State registration number, a current Certificate of Operation, and Operational Permit prior to approval of any alterations. Colorado State registration is not required for residential conveyances and temporary construction elevators. Operational permits are not required for dormant conveyances. 921.4 Removal from service. Permits shall be obtained from the fire department prior to any conveyance being removed from service, made dormant or otherwise rendered inoperable. If an entire building is being demolished “scraped” a valid demolition permit issued by the City of Englewood shall be accepted as verification of a conveyance being removed from service and may eliminate the need for a permit for removal to be obtained. 921.5 Annual conveyance operating permit. All buildings or facilities where an elevator, escalator, or AGTS are located shall obtain an annual conveyance operating permit prior to issuance of a Certificate(s) of Operation. No conveyance shall be operated without a valid Certificate of Operation. Exceptions: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 117 1. Conveyances issued a Construction Use Certificate of Operation when operating under the terms of that Certificate. 2. Residential elevators complying with Section 921.20. 921.5.1 Change in contact information. The conveyance owner shall be responsible for notifying the Administrator of any change in ownership or management contact information within 30 days of the change. 921.6 Standardized key switches. All elevators shall be provided with standardized key switches for emergency operation in accordance with Section 606.8.1. 921.7 Venting of hydraulic tanks located in hoistways. New and existing elevators permitted to have a hydraulic tank located in the hoistway in accordance with ASME A17.1 shall e provided with tank venting. 921.8 Emergency and standby power. Where emergency or standby power is provided to elevators or other conveyances as required by this code, the International Building Code, other applicable standards or voluntarily, installation and operation shall comply with Sections 604 and 606. Exception: Where emergency or standby power is required for platform lifts as part of an accessible means of egress in accordance with Section 1009.5 of the International Building Code, battery-powered units are acceptable where the battery capacity meets the requirements of ASME A18.1. Battery-powered units shall be provided directly by the platform lift manufacturer in accordance with the equipment listing. 921.8.1. Auxiliary power lowering operation provided in accordance with ASME A17.1 shall be permitted and shall not be considered as an emergency or standby power source. 921.9 Fire service access elevators. Where required by the International Building Code, fire service access elevators shall be provided. Elevator system monitoring, electrical power, sprinkler protection, protection of wiring or cables and standpipe hose connection access shall comply with Section 3007 of the International Building Code. Elevator monitoring panels shall be submitted for approval prior to installation and shall monitor and display the conditions in accordance with NFPA 72, 21.5.1. Occupancy of elevator cars shall be continuously monitored by CCTV or other means approved by the fire code official. The CCTV screen shall be integrated into the elevator status panel and shall measure a minimum of 9-inch diagonally. Shunt trip operation shall not be permitted for fire service access elevators. 921.9.1 Fire Service Access Elevators. A pictorial symbol designating the fire service access elevator(s) shall be installed on the jambs at the designated landing. Existing Fire Service Access Elevators shall have this symbol installed at the designated landing by June 1, 2017. 921.10 Elevators with destination dispatch. Where elevators with destination dispatch are provided, they shall be provided with a common Phase I recall key switch and indicator located in the lobby within sight of the elevator or all elevators in that group and shall be readily accessible. 921.11 “TWIN” type elevators. Installation of “TWIN” elevators shall be as approved by the State of Colorado Division of Oil and Public Safety and the fire code official. 921.12 Elevator firefighter indicator. The operation of the elevator firefighter indicator (firefighter hat symbol) shall comply with Section 907.3.3.5 as amended. 921.13 Elevator in-car communications. Where required by ASME A17.1, two-way in-car communications shall be provided from the car to an approved location. Authorized personnel at the receiving station shall notify the Englewood Fire Marshal in accordance with Section 401.3.2 of any indication of a trapped party medical emergency or non-responsive occupant or presence of smoke or fire. Communication from the elevator car to an off-site monitoring station shall be by a loop-start seizable phone line. 921.14 Elevator building communications for elevator rise of 60 feet (18.5m) or more. Where required by ASME A17.1, two-way communications shall be provided for emergency personnel to communicate directly with occupants of the elevator car. Communications equipment for emergency responder use shall be located DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 118 in the Fire Command Center, where provided, or adjacent to the fire alarm control unit. Where elevators within a building are required to comply with this section, these elevators shall be identified at the emergency responder communication means. Two-way communication system from the elevator to the Fire Command Center shall be incorporated on the elevator status panel. 921.15 Inspections. Conveyance annual and periodic inspections shall comply with State Conveyance Regulations 7CCR 1101-8, manufacturer’s specifications, the Maintenance Control Program and this code. 921.15.1 Inspection. All conveyances shall be inspected annually. 921.15.2 Certificate of operation. A conveyance shall not operate unless the conveyance owner maintains a current certificate of operation for the conveyance. The certificate of operation shall be available for review at the property where the conveyance is located. 921.15.3 Inspection submittal. Licensed Conveyance Inspectors shall submit complete and accurate inspection reports to the Fire Marshal’s Office within 5 business days of the inspection 921.16 Alterations to elevator car dimensions and/or hoistway openings. Alterations to dimensions of existing elevator cars and hoistway openings is subject to approval by the fire code official. Alterations to imensions of elevator cars and/or hoistway openings shall not be permitted unless such alterations meet the requirements for a new installation. 921.17 Conveying systems. Escalators, moving walks, conveyors, platform lifts, dumbwaiters, stairway chair lifts, personnel hoists, material lifts and material hoists shall comply with the provisions of this code and Chapter 30 of the International Building Code. 921.18 Automated Guideway Transportation Systems (AGTS). AGTS shall comply with Sections 921.2, 921.3, 921.5, and ASME 21 as adopted by the State of Colorado. 921.19 Conveyances used during construction. Elevators and personnel hoists used during construction shall comply with ASME A17.1 Section 5.10, ANSI A10.4. Upon installation or modification, certification shall be provided to the Department that the required acceptance test was performed in accordance with the approved plans, ANSI A10.4 and the manufacturer’s installation instructions. Such certification shall also be provided for each periodic inspection required at intervals not to exceed 90 days. Certifications shall bear the signature and license number of a Englewood licensed inspector. 921.19.1 Door locking devices. Electro-mechanical hoistway door interlocks shall be provided at all landings. 921.20 Residential elevators. All elevators used in private residences shall comply with ASME A17.1 Section 5.3. Installation or alteration of an elevator in a private residence shall be submitted for approval in accordance with Section 921.2 or Section 921.3. 921.20.1 Certificate of operation. Residential elevators are required to have a current Certificate of Operation issued by a licensed elevator inspector. Certificates shall be valid for a period of three years and shall require submission to the Fire Marshal as an inspection affidavit signed by a licensed inspector prior to issuance or renewal. 921.21 Elevator Identification. Where more than one elevator exists, the alphabetical or numerical identification of the elevator shall be placed on both doorjambs of every elevator entrance at the designated level, alternate level, level where means necessary for tests is provided, and level test panel is provided; this identification shall be a minimum of 50 mm (2 in.) in height and shall be located immediately below the floor designation, where provided. 921.22 Elevator contractor response. Following an elevator entrapment where fire crews have responded and require the assistance of elevator personnel, the onsite incident commander (IC) or building responsible party shall notify the elevator contractor of record through the contractor’s emergency dispatch center that a licensed DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 119 conveyance mechanic is required onsite to give guidance to emergency personnel on extracting entrapped passengers. In response, elevator contractor of record shall: 1. Dispatch a licensed conveyance mechanic to the site; and, 2. The elevator mechanic shall be onsite within one hour. Building owners or their designee are responsible for posting the name of the elevator contractor of record and its emergency dispatch center or other contact number(s). The elevator contractors contact information shall be provided in durable construction, easily readable in normal lighting, protected by a smooth, transparent, plastic surface and be located at the following locations. 1. Fire Command Center (FCC) where provided or, 2. Adhered to the inside cover of the Fire Alarm Control Panel (FACP) when no FCC is present, or, in the elevator Machine Room, if no FACP is present. Only a licensed conveyance mechanic shall restore power and place the conveyance back into service after verifying the conveyance is safe for public use in accordance with Section 919.5, following an event where power to a conveyance was removed by Fire Department personnel. 921.23 Disconnect location. The Licensed Elevator Contractor shall ensure the location of each elevator electrical disconnect is detailed on a matrix & posted within a display of durable construction, easily readable in normal lighting, protected by a smooth, transparent plastic surface and shall include the following information. 1. The floor number(s) that the disconnect(s) are located 2. Which elevator the disconnect operates 3. Room name/number This display shall be located in the Fire Command Center adjacent to elevator panels where provided or next to the Fire Alarm Control Panel. The fire alarm graphic map shall also note such locations. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 120 CHAPTER 10 MEANS OF EGRESS Chapter 10 of the International Fire Code is amended in accordance with the amendments to Chapter 10 of the International Building Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 121 CHAPTER 11 CONSTRUCTION REQUIREMENTS FOR EXISTING BUILDINGS SECTION 1101 GENERAL Section 1101.1 Scope is replaced as follows: 1101.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to the adoption of this code when the applicable requirements for such buildings cannot be ascertained by the following: 1. The building and fire codes in effect when the building was permitted for construction and no change of occupancy occurred since that time. 2. The building and fire codes in effect when the building was last certified for occupancy 3. All applicable retrofit ordinances, including retroactive regulations contained elsewhere in this Code 4. Modification under Section 106 of the Administration of the 2019 Englewood Building Code. 5. Subject to approval by the fire code official, existing life safety features that exceed the requirements for new buildings shall be permitted to be decreased to those required for new buildings. 6. Existing life safety features that do not meet the requirements for new buildings, but that exceed the requirements for existing buildings, shall not be further diminished. 1101.1.1 Existing buildings. Existing buildings shall comply with the requirements of Sections 1103.2, 1103.3, 1103.7.5, 1103.9, 1107, and 1108. Section 1101.2 Intent is replaced as follows: 1101.2 Intent. The intent of this chapter is to provide a minimum degree of fire and life safety to persons occupying existing buildings by providing minimum construction requirements where such existing buildings do not comply with the minimum requirements of the Englewood Building Code. It is intended for existing buildings to comply under the Code which it was constructed, certified for occupancy, any alternate means of Code compliance approvals, and retrofit / retroactive Codes previously adopted. SECTION 1103 FIRE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS Section 1103.1 Required construction is amended by adding Exception 3 as follows: 3. See Section 3211 for requirements for existing buildings constructed prior to October 1990 and used for high-piled or rack storage. Section 1103.2 Emergency responder radio coverage in existing buildings is replaced as follows: 1103.2 Emergency responder radio coverage in existing buildings. See Section 918.1.2. Section 1103.3.1 Elevators, escalators and moving walks is replaced as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 122 1103.3.1 Elevators, escalators and moving walks. Existing elevators, escalators and moving walks in Group I-2 Condition 2 occupancies shall comply with Colorado State Regulations, as amended from time to time. Section 1103.3.2 Elevator emergency operation is replaced as follows: 1103.3.2 Elevator emergency operation. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with Colorado State Regulations,. Exceptions 1 and 2 to remain; Exception 3 is amended as follows: 3. Freight elevators in buildings provided with automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the International Fire Code. Section 1103.7.1 Group E is amended by adding Exception 3 as follows: 3. As of January 1, 2019, all approved installations of battery-operated smoke alarms shall be replaced with UL 217 listed battery-operated smoke alarms provided with permanent integral 10-year lithium batteries and resistance to nuisance alarms. Continued use of battery-operated smoke alarms shall be subject to approval by the fire code official. Section 1103.8.3 Power source is amended by adding the following at the end of the section: As of January 1, 2019, all approved installations of battery-operated smoke alarms shall be replaced with UL 217 listed battery-operated smoke alarms provided with permanent integral 10-year lithium batteries and resistance to nuisance alarms. Continued use of battery-operated smoke alarms shall be subject to approval by the fire code official. Section 1103.9 Carbon monoxide alarms is amended by adding the following at the end of the section: Effective upon adoption of this code by the authority having jurisdiction, existing I and R occupancies with approved battery-operated CO alarms shall replace such units upon activation of the unit end-of-life signal or in accordance with the manufacturer’s recommendation. Where approved, replacement and new CO alarms shall be UL 2034 listed battery-operated CO alarms provided with permanent integral 10-year lithium batteries. Installation of new CO alarms in existing R occupancies where required by State of Colorado regulations shall comply with this requirement. Use of battery-operated CO alarms shall be subject to approval by the fire code official. Listed combination smoke/CO alarms that comply with these requirements shall be permitted. SECTION 1105 CONSTRUCTION REQUIREMENTS FOR EXISTING GROUP I-2 Section 1105.1 General is amended by adding an Exception as follows: Exception: The requirements of Section 1105 of the International Fire Code shall not apply for Group I-2 occupancies which comply with the 2012 NFPA 101 Chapter 19 provisions for existing hospitals, nursing homes, and limited care facilities. For the purposes of this exception; the term hospital, shall include general hospitals, psychiatric hospitals, and specialty hospitals, the term nursing home, shall include nursing and convalescent homes, skilled nursing facilities, intermediate care facilities, and infirmaries in homes for the aged. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 123 Section 1107 Requirements for Compressed Gas Systems is added as follows: SECTION 1107 REQUIREMENTS FOR COMPRESSED GAS SYSTEMS 1107.1 Compressed gas systems. Existing compressed gas systems located within existing buildings shall be retrofitted and modified in accordance with Sections 1107.1.1 through 1107.1.4 of the International Building Code. 1107.1.1 Carbon dioxide (CO2) systems used in beverage dispensing applications. Existing carbon dioxide (CO2) systems used in beverage dispensing applications shall comply with Section 5307. 1107.1.2 Inert gas systems used in commercial, manufacturing or industrial applications. Existing inert gas systems used in commercial, manufacturing or industrial applications shall comply with Section 5309. 1107.1.3 Carbon dioxide (CO2) gas enrichment systems using on-site supply tanks and/or cylinders in plant growing (husbandry) applications. Existing carbon dioxide (CO2) gas enrichment systems using on-site supply tanks and/or cylinders in plant growing (husbandry) applications shall comply with Section 5310. 1107.1.4 Carbon dioxide (CO2) gas enrichment systems using a natural gas burner in plant growing (husbandry) applications. Existing carbon dioxide (CO2) gas enrichment systems using a natural gas burner in plant growing (husbandry) applications shall comply with Section 5311. SECTION 1108 Firefighter Fall Protection is added as follows: SECTION 1108 FIREFIGHTER FALL PROTECTION 1108.1 Firefighter fall protection. The following precautions are required to ensure safe and effective rooftop access for rooftop maintenance and firefighting operations. Materials shall comply with UL 1994. Signs or decals shall be posted in English and in the predominant language of workers. Signs, decals and striping affixed to the exterior of the building shall be suitable for the environment. 1. Self-luminous or reflective signs or decals approved by the fire code official are required on building exterior walls when the locations of rooftop access landing areas are not apparent from the street. 2. Self-luminous or reflective signs or decals approved by the fire code official shall be attached to each skylight, trap door, roof hatch, and scuttle cover; the sign or decal shall be on the surface, with striping around the entire perimeter. 3. Self-luminous or reflective signs or decals approved by the fire code official shall be placed at entries (doors, stairs, ladders, or roof hatches) to areas containing skylights, trap doors, roof hatches, and scuttle covers. 4. Existing non-metallic panels with curb heights eight inches or less that are present between metal panels on roofs shall be replaced with metal panel(s) with the equivalent gauge and material properties as the existing roof panels. Perimeter guardrails or fall protection can be used in lieu of replacement of existing non-metallic panels when these systems comply with OSHA 29 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 124 CFR1926.502. Self-luminous or reflective signs or decals approved by the fire code official shall be placed on perimeter guardrails. Exception: One-family, two-family and townhome dwellings constructed in accordance with the International Residential Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 125 CHAPTER 12 ENERGY SYSTEMS SECTION 1203 EMERGENCY AND STANDBY POWER SYSTEMS Section 1203.1.1 Stationary generators is amended by adding the following to the last sentence: Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200 and operated by a diesel-fueled prime mover. Section 1203.1.1.1 Optional standby generators is added as follows: 1203.1.1.1 Optional standby generators. Optional standby generators shall be permitted in accordance with NFPA 70 (NEC) Article 702. Generators shall be fueled by a diesel or natural gas fuel source. Gaseous fuels shall be provided by a public utility and piped to the unit. Where diesel-fueled generators are located at other than grade level, individual fuel tank capacity shall not exceed 120 gallons, with a total capacity not to exceed 660 gallons on any building story or level. Section 1203.1.3 Installation is amended by adding the following after the last sentence: All generators shall be provided with a remote status panel in accordance with NFPA 110 and complying with Section 907.2.12.7. Optional standby generators shall also be provided with a remote status panel. Panel location shall be in an area approved by the fire code official. Section 1203.1.5 Load duration is replaced as follows: 1203.1.5 Load duration. Emergency power systems and standby power systems shall be designed to provide the required power for a minimum duration of 2 hours without being refueled or recharged, unless specified otherwise in this code. If fuel pumping is required from a main fuel tank to a day tank, a duplex pumping system shall be provided. Fuel storage and handling shall comply with Chapter 57 of the International Fire Code. Fuel supplies for emergency or required standby systems shall be located on-site. Exception: Emergency generators supplying fire pumps shall have a fuel supply for eight hours of simultaneous operation of all connected emergency equipment. Section 1203.1.6 Uninterruptible power source is replaced as follows: 1203.1.6 Stored energy emergency or standby power systems. Stored energy emergency and standby power systems required by this code shall be installed in accordance with Section 1206 of the International Fire Code, and NFPA 111 and shall have sufficient capacity to operate under full load for 90 minutes. Section 1203.1.10 Location is added as follows: 1203.1.10 Location. All generators required by this code shall be located at grade level, or one level below grade with the filling connection located in accordance with Chapter 57 of the International Fire Code. Enclosure provisions shall comply with NFPA 110. Exceptions: 1. Stationary emergency and legally required standby power generators in a stand-alone open parking garage less than 55' in height, shall be permitted to be located on the topmost atmospheric level. 2. Stationary emergency generators located in a stand-alone utility plant are permitted to be located one level above the level of exit discharge with a fuel capacity of not more than 240 gallons on that level. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 126 3. Stationary emergency and legally required standby power generators shall be permitted to be located at one level above grade where all of the following are met: a. Individual fuel tank capacity shall not exceed 120 gallons at the generator day tank. b. Supply tank shall be provided at grade level with filling connection located in accordance with Chapter 57 of the International Fire Code. c. Duplex pumping system shall be provided between the supply tank and generator day tank. d. The aggregate capacity of fuel tanks shall not exceed 660 gallons. Section 1203.1.10.1 Outdoor locations is added as follows: 1203.1.10.1 Outdoor locations. Where generators are located outside of a building, the following provisions shall apply. a. Generators shall be located at least 5 feet from the exterior wall of the building. Where a generator location within 5 feet of the building is approved, the exterior wall shall be non-combustible and shall have a 2-hour fire resistance rating. The separation distance of the generator to the exterior wall shall be maintained as required by NFPA 70 and the manufacturer’s recommendations. The fire resistance rated exterior wall shall extend at least 3 feet above the generator enclosure. b. A minimum 10-foot separation shall be maintained between a generator and any transformer, or a 2- hour fire resistance rated masonry or concrete wall shall be provided between the generator and the transformer. The separation wall shall be no less than 6 foot above the highest ground elevation on either side of the wall and not less than 2 feet above the top of the generator or transformer whichever is lower. Separation distance between this equipment and the exterior wall shall comply with NFPA 70. Section 1203.2.2 Elevators and platform lifts is amended by adding the following to the end of the paragraph: Standby power for platform lifts shall comply with ASME A18.1. Section 1203.2.3 Emergency responder radio coverage systems is replaced as follows: 1203.2.3 Emergency responder radio coverage systems. Emergency power shall be provided for emergency responder radio coverage systems in accordance with Section 510.2. Section 1203.2.10 High-rise buildings is replaced as follows: 1203.2.10 High-rise buildings. Emergency power shall be provided for high-rise buildings as required in Section 403 of the International Building Code and shall be in accordance with Section 1203 of the International Fire Code. Section 1203.2.17 Smoke control systems is replaced as follows: 1203.2.17 Smoke control systems. Standby power shall be provided for smoke control systems as required in Section 909.7 of the International Fire Code. Section 1203.2.19 Covered mall buildings is added as follows: 1203.2.19 Covered mall buildings. Covered mall buildings exceeding 50,000 square feet (4,645 m2) shall be provided with emergency power systems which are capable of operating the emergency voice/alarm communication system, the smoke control system, where provided, in accordance with Section 909, the fire pump and one accessible elevator. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 127 Section 1203.7 Emergency and standby (required or optional) power generator shop drawings is added as follows: 1203.7 Emergency and standby (required or optional) power generator shop drawings. Shop drawings for emergency and standby (required or optional) power generator systems shall be submitted for permit application as a deferred submittal in accordance with Section 133.5 of the International Building Code. Plan review and approval are required prior to issuance of a generator construction permit for system installation. Two sets of scaled, engineered installation shop drawings shall be submitted. Documents shall be of sufficient clarity and detail to fully describe the scope of work. Handwritten notes and comments on reproduced drawings are not acceptable. Submittals shall comply with Appendix N. SECTION 1206 ELECTRICAL ENERGY STORAGE SYSTEMS Section 1206.2.11.5 Spill control and neutralization is replaced as follows: 1206.2.11.5 Spill control and neutralization. An approved method and materials for the control and neutralization of a spill of electrolyte shall be provided in areas containing lead-acid, nickel-cadmium or other types of batteries with free-flowing liquid electrolyte. Each rack of batteries or groups of racks shall be provided with a liquid-tight 4-inch (101.6mm) minimum spill-control barrier which extends at least 1- inch (25.4 mm) beyond the battery rack in all directions. For the purposes of this paragraph, a “spill” is defined as any unintentional release of electrolyte. Exception: VRLA, lithium-ion or other types of sealed batteries with immobilized electrolyte shall not require spill control. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 128 CHAPTER 20 AVIATION FACILITIES SECTION 2001 GENERAL Section 2001.1 Scope is replaced as follows: 2001.1 Scope. Airports, heliports, helistops, and aircraft hangers shall be in accordance with this Chapter and applicable sections of Appendix S of the International Building Code. Section 2001.3 Permits is replaced as follows: 2001.3 Permits. For permits to operate aircraft -refueling vehicles, application of flammable or combustible finishes, hot work, aviation fuel dispensing facilities – maintenance and inspection, and emergency fuel shut off (EFSO) impairment fire watch, see Section 105.6. SECTION 2005 PORTABLE FIRE EXTINGUISHERS Section 2005.6 At fuel-dispensing stations is replaced as follows: 2005.6 At fuel-dispensing stations. Portable fire extinguishers for ramps where fueling operations are conducted are intended to provide an immediate means of fire protection in an area likely to contain a high concentration of personnel and valuable equipment. The prominent and strategic positioning of portable fire extinguishers is critical for them to be of maximum value in the event of an emergency. Portable fire extinguishers shall not be located in probable spill areas. To provide accessibility from adjoining gates, portable fire extinguishers shall be located approximately midway between gate positions. Portable fire extinguishers at fuel-dispensing stations shall be located such that pumps or dispensers are not more than 50 feet from an extinguisher. The maximum distance between extinguishers shall not be over 200 feet. Where the specified portable fire extinguishers are brought into the aircraft fuel servicing areas prior to the fueling operation, they shall be located upwind not over 50 feet from the aircraft being serviced. Fire extinguishers shall be provided as follows: 1. Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute, a minimum of two listed portable fire extinguishers complying with Section 906 and having a minimum rating of 20-B:C shall be provided. 2. Where the open-hose discharge of the fueling system is more than 200 gallons per minute but not more than 350 gallons per minute, a minimum of two listed wheeled extinguishers complying with Section 906 and having a minimum extinguishing rating of 80-B:C and a minimum agent capacity of 125 pounds shall be provided. 3. Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute, a minimum of three listed wheeled extinguishers complying with Section 906 of the International Fire Code, and having a minimum rating of 80-B:C each and a minimum capacity agent of 125 pounds each shall be provided. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 129 SECTION 2006 AIRCRAFT FUELING Section 2006.6 Emergency fuel shutoff is amended by adding the following at the end of the paragraph: The emergency fuel shutoff system (EFSO) is an emergency alarm and shall comply with this section and Section 908.4 of the International Fire Code. Emergency fuel shutoff switches shall be of a yellow back plate with a red, mushroom head type, listed for use, with a protective cover to prevent inadvertent contact and shall only be reset by a key accessible only to authorized personnel. Activation of the emergency alarm system shall activate a local blue strobe or beacon. Locations, performance and marking shall comply with NFPA 407. Section 2006.12.1 Auxiliary power unit (APU) is added as follows: 2006.12.1 Auxiliary power unit (APU). Fuel servicing shall not be performed on a fixed-wing aircraft while an onboard engine, APU or heater, is operating. Exception: In an emergency resulting from the failure of an onboard auxiliary power unit on a jet aircraft, and in the absence of suitable ground support equipment, a jet engine mounted at the rear of the aircraft or on the wing on the side opposite the fueling point shall be permitted to be operated during fueling or defueling to provide power, provided that the operation follows written procedures approved by Englewood Fire Marshal. SECTION 2007 HELISTOPS AND HELIPORTS Section 2007.9 Helistops on roofs is added as follows: 2007.9 Helistops on roofs. In addition to other applicable portions of this Code, helistops located on roofs shall comply with the following: 1. Smoking is prohibited on the roof operating area during landing and takeoff operations. 2. Persons, other than helistop personnel, shall be restricted to designated protected or fenced waiting areas during landing and take-off operations. 3. Loose material such as gravel is prohibited. 4. Openings in the roof shall not be permitted in the immediate landing area. 5. Major repair and maintenance operations are not permitted on the helistop except in cases of emergency, and only with prior notification to the Fire Department. 6. Communication facilities shall be provided from the helistop to the department and building personnel for emergency notification. 7. Helistop personnel shall be trained in the use of communication and fire extinguishing equipment. 8. The storage of flammable liquids or highly combustible materials on the roof is prohibited. 9. An exterior (weatherproof) manual pull station shall be provided by each exit and shall be connected to the building alarm system. 10. At least 100 feet of approved 1.5-inch hose equipped with an approved fog nozzle and a 2.5-inch male NST reduced to a 1.5-inch male Englewood thread shall be provided in a weatherproof cabinet adjacent to the roof standpipe. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 130 CHAPTER 23 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES SECTION 2303 LOCATION OF DISPENSING DEVICES Section 2303.2 Emergency disconnect switches is replaced as follows: 2303.2 Emergency disconnect switches. An approved clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be located in an accessible location outside in accordance with this section. Emergency disconnect switches shall be of a red, mushroom head type, listed for use, with a protective cover to prevent inadvertent contact and shall only be reset by a key located on premises accessible to authorized personnel. Installation of emergency disconnect switches shall comply with NFPA 70 (NEC). Emergency disconnects shall be located within 100 feet (30 480 mm) of but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. All emergency disconnect switches shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations. Access to emergency disconnect switches shall be unobstructed. Removal of equipment, merchandise, vehicles, storage, etc., to reach the emergency disconnect does not meet the requirement for a "readily accessible" location. SECTION 2304 DISPENSING OPERATIONS Section 2304.2.5 Communications is replaced as follows: 2304.2.5 Communications. The attendant shall be able to communicate with persons in the dispensing area at all times with a two-way hard-wired communication system. An approved method of communicating with the fire department shall be provided for the attendant. Section 2304.3 Unattended self-service motor fuel-dispensing facilities is replaced as follows: 2304.3 Unattended self-service motor fuel-dispensing facilities. Unattended public self-service motor fuel-dispensing facilities are prohibited. SECTION 2305 OPERATIONAL REQUIREMENTS Section 2305.6.1 Lettering is added as follows: 2305.6.1 Lettering. Warning signs shall have the word “WARNING” in red letters of not less than 1.5 inches in height and the remainder of the signs shall have red letters of not less than one (1) inch in height on a white background. Exception: Existing approved signs consisting of contrasting lettering and background. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 131 SECTION 2306 FLAMMABLE AND COMBUSTIBLE LIQUID MOTOR FUEL-DISPENSING FACILITIES Section 2306.7.3 Mounting of dispensers is replaced as follows: 2306.7.3 Mounting of dispensers. In motor fuel-dispensing facilities the dispensing devices except those installed on top of a protected above-ground tank that qualifies as vehicle-impact resistant, shall be protected against physical damage by mounting on a concrete island 6 inches (152 mm) or more in height and in accordance with Section 312. Dispensing devices shall be installed and securely fastened to their mounting surface in accordance with the dispenser manufacturer’s instructions. Dispensing devices installed indoors shall be located in an approved position where they cannot be struck by an out-of-control vehicle descending a ramp or other slope. SECTION 2308 COMPRESSED NATURAL GAS MOTOR FUEL-DISPENSING FACILITIES Section 2308.7 Emergency shutdown control is amended by adding the following after the last sentence. The emergency shutdown control switch shall be of a type complying with Section 2303.2. SECTION 2309 HYDROGEN MOTOR FUEL-DISPENSING AND GENERATION FACILITIES Section 2309.5.3 Emergency shutdown control is amended by adding the following after the last sentence. The emergency shutdown control switch shall be of a type complying with Section 2303.2. SECTION 2311 REPAIR GARAGES Section 2311.4.3 Ventilation is replaced as follows: 2311.4.3 Ventilation. Where Class I liquids or LP-gas are stored or used within a building having a basement or pit wherein flammable vapors could accumulate, the basement or pit shall be provided with mechanical ventilation in accordance with the International Mechanical Code, at a minimum rate of 1.5 cubic feet per minute per square foot (cfm/ft2) [0.008 m3/(s . m2)] to prevent the accumulation of flammable vapors. The fan shall be configured in such a way that it runs continuously, and the exhaust inlet is placed within 12 inches of the pit floor. Sections 2311.4.4 Fire protection systems is added as follows: 2311.4.4 Fire protection systems. In buildings equipped with an automatic sprinkler system, pits and below-grade work areas shall be protected. Sprinkler systems in pits and below-grade work areas shall be separately zoned and the control valve shall be located outside the pit or below-grade work area. 2211.4.5 Flammable vapor monitoring is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 132 2311.4.5 Flammable vapor monitoring. Pits and below-grade work areas shall be equipped with a flammable vapor-monitoring alarm. Alarm notification shall be local only and provided in an approved location(s). 2311.4.6 Warning signs is added as follows: 2311.4.6 Warning sign(s). Pits and below grade work areas shall be identified as required. Doors or openings leading to a pit or below grade work area shall be plainly marked with the words “OPEN PIT” in red letters at least six (6) inches high on a white background. Such warning signs shall be placed so as to be readily discernible. Section 2311.8.9 Gas detection system is replaced as follows: 2311.8.9 Gas detection system. Repair garages used for repair of vehicles fueled by non-odorized gases, including, but not limited to, hydrogen and non-odorized LNG, shall be provided with a flammable gas detection system in accordance with Sections 2311.7.2.1 through 2311.7.2.3, of the International Fire Code. Emergency alarms shall be provided in accordance with Section 916 of the International Fire Code.. Section 2311.8.9.2 System activation - Item 1 is replaced as follows: 1. Initiation of distinct audible and visual alarm signals in the repair garage in accordance with Section 916. Signage required by Section 916 shall state outside of the room: “DO NOT ENTER WHEN LIGHT IS FLASHING – NONODORIZED FLAMMABLE GAS LEAK DETECTED” and inside of the room: “FLASHING LIGHT MEANS NONODORIZED FLAMMABLE GAS LEAK DETECTED – EVACUATE ROOM AND BUILDING.” Section 2312 Existing Motor Fuel-Dispensing Facilities is added as follows: SECTION 2312 EXISTING MOTOR FUEL-DISPENSING FACILITIES 2312.1 Mounting of dispensers. Existing motor fuel dispensing facilities shall have the dispensing devices, except those installed on top of a protected above-ground tank that qualifies as vehicle-impact resistant, protected against physical damage in accordance with Section 312 of the International Fire Code. Dispensing devices shall be securely fastened to their mounting surface in accordance with the dispenser manufacturer’s instructions. Dispensing devices installed indoors shall be located in an approved position where they cannot be struck by an out-of-control vehicle descending a ramp or other slope. 2312.2 Emergency disconnect switches. Existing motor fuel-dispensing facilities shall have an approved clearly identified and readily accessible emergency disconnect switch provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be located in an accessible location outside in accordance with this section. Emergency disconnect switches shall be of a red, mushroom head type, listed for use, with a protective cover to prevent inadvertent contact and shall only be reset by a key located on premises accessible to authorized personnel. Installation of emergency disconnect switches shall comply with NFPA 70 (NEC). Emergency disconnects shall be located within 100 feet (30480 mm) of but not less than 20 feet (6096 mm) from, the fuel dispensers. All emergency disconnect switches shall be distinctly labeled as “EMERGENCY FUEL SHUTOFF.” Signs shall be provided in approved locations. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 133 CHAPTER 24 FLAMMABLE FINISHES SECTION 2401 GENERAL Section 2401.1 Scope, Item 4, is amended as follows: 4. Floor surfacing or finishing operations using Class I or II liquids Section 2401.3.1 Water-based finishes is added as follows: SECTION 2404 SPRAY FINISHING Section 2404.6.1.2.1 Interlocks Item 3 is replaced as follows: 3. Have the ventilating system maintain a concentration 25 percent below the lower flammable limit (LFL) within the spray booth or spray room during the drying process and automatically shut off drying apparatus in the event of a failure of the ventilating system. SECTION 2405 DIPPING OPERATIONS Section 2405.7 Ventilation is replaced follows: 2405.7 Ventilation of flammable vapor areas. Mechanical ventilation shall be provided to maintain airborne concentrations below 25 percent the lower flammability limit (LFL). Required ventilation systems shall be arranged such that the failure of any ventilating fan shall automatically stop the dipping conveyor system. SECTION 2410 FLOOR SURFACING AND FINISHING OPERATIONS Section 2410.1 Scope is replaced as follows: 2410.1 Scope. Floor surfacing and finishing operations using Class I or Class II liquids shall comply with Sections 2410.2 through 2410.5 of the International Fire Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 134 CHAPTER 25 FRUIT AND CROP RIPENING SECTION 2503 ETHYLENE GAS Sections 2503.3 Storage and 2503.4 Piping are added as follows: 2503.3 Storage. Containers other than those connected for use shall be stored outside of ripening process buildings or in a special building. Exception: Storage of not more than two portable containers complying with Section 5303.1 of the International Fire Code and approved for transportation is allowed in ripening process buildings. 2503.4 Piping. Piping containing ethylene shall be constructed of iron. Flexible connectors and hose, when used, shall be of an approved type. Tubing shall be of brass, copper, or stainless steel with not less than 0.049-inch (1.2 mm) wall thickness. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 135 CHAPTER 26 FUMIGATION AND INSECTICIDAL FOGGING SECTION 2601 GENERAL Section 2601 Replaced as follows: Section 2601.2 License is added as follows: 2601.3 License. No person shall conduct fumigation or insecticidal operations without first being licensed. SECTION 2603 FIRE SAFETY REQUIREMENTS Section 2603.1.1 Storage warning signs is added as follows: 2603.1.1 Storage warning signs. Where fumigants and insecticidal fogging products are stored NFPA 704 placard guidelines shall be followed. Section 2603.3.1 Warning signs is amended by adding the following after the first sentence: Where fumigants and insecticidal fogging products are used, approved warning signs bearing the “skull and crossbones” emblem with the warning “DANGER! POISON GAS! KEEP OUT!” shall be posted. Section 2603.3.1.1 Storage warning signs is added as follows: 2603.3.1.1 Storage warning signs. Where fumigants and insecticidal fogging products are stored, NFPA 704 placard guidelines shall be followed. Section 2603.8 Fumigations restricted is added as follows: 2603.8 Fumigations restricted. Heated elemental sulfur processes creating sulfur dioxide shall be prohibited. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 136 CHAPTER 27 SEMICONDUCTOR FABRICATION FACILITIES SECTION 2703 GENERAL SAFETY PROVISIONS Section 2703 12.1 General safety provisions is replaced as follows: 2703.12.1 Where required. Emergency alarm systems shall be provided in accordance with Section 908.8 in the areas indicated in 2703.12.1.1 through 2703.12.1.3 of the International Fire Code. Section 2703.12.3.1 Emergency alarm signage is added as follows: 2703.12.3.1 Emergency alarm signage. Signage required by Section 908.4 shall state, Outside the room: “DO NOT ENTER WHEN LIGHT IS FLASHING – HAZARDOUS PRODUCTION MATERIAL SPILL DETECTED.” Inside the room: “FLASHING LIGHT MEANS HAZARDOUS PRODUCTION MATERIAL SPILL DETECTED – EVACUATE ROOM AND BUILDING.” Section 2703.13.2.1.1 Emergency alarm signage is added as follows: 2703.13.2.1.1 Emergency alarm signage. Signage required by Section 916 shall state, Outside the room: “DO NOT ENTER WHEN LIGHT IS FLASHING – HAZARDOUS PRODUCTION MATERIAL SPILL DETECTED.” Inside the room: “FLASHING LIGHT MEANS HAZARDOUS PRODUCTION MATERIAL SPILL DETECTED – EVACUATE ROOM AND BUILDING.” DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 137 CHAPTER 28 LUMBER YARDS AND AGRO-INDUSTRIAL, SOLID BIOMASS AND WOODWORKING FACILITIES SECTION 2804 FIRE PROTECTION Section 2804.3 Portable fire extinguishers or standpipes and hose is replaced as follows: 2804.3 Portable fire extinguishers and standpipes. Portable fire extinguishers or standpipes supplied from an approved water system shall be provided within 50 feet (15240 mm) of travel distance to any machine producing shavings or sawdust. Extinguishers shall be provided in accordance with Section 906 of the International Fire Code for extra-high hazards. SECTION 2809 EXTERIOR STORAGE OF FINISHED LUMBER AND SOLID BIOFUEL PRODUCTS Section 2809.5 Fire protection is replaced as follows: 2809.5 Fire protection. An approved hydrant and portable fire-extinguishing equipment suitable for the fire hazard involved shall be provided for open storage yards. Hydrant systems shall be installed in accordance with NFPA 24. Portable fire extinguishers complying with Section 906 of the International Fire Code. shall be located so that the travel distance to the nearest unit does not exceed 75 feet (22,860 mm). Portable fire extinguishers located in open storage yards shall be protected from weather and shall be maintained in accordance with NFPA 10. Portable fire extinguishers complying with Section 906 of the International Fire Code. and with a minimum rating of 4-A:40-B:C shall be provided on all vehicles operating in a lumber storage yard. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 138 CHAPTER 30 INDUSTRIAL OVENS SECTION 3003 LOCATION Section 3003.5 Location is added as follows: 3003.5 Location. Ovens, oven heaters and related equipment shall be located with due regard to the possibility of fire resulting from overheating or the escape of fuel gas or fuel oil and the possibility of damage to the building and injury to persons resulting from explosion. 1. Ovens shall be located at or above grade. Exception: Ovens shall be permitted in basements where at least 50% of the wall area of the room in which the oven is located is above grade. 2. Ovens shall be located to be readily accessible for inspection and maintenance and with adequate clearances to permit the proper functioning of explosion vents. Section 3003.6 Relief (explosion) vents is added as follows: 3003.6 Relief (explosion) vents. Ovens which may contain flammable air-gas mixtures shall be equipped with relief vents for freely relieving internal explosion pressures. Section 3003.7 Ductwork is added as follows: 3003.7 Ductwork. All ductwork shall be constructed of approved non-combustible material. Ducts shall be made tight throughout and shall have no openings other than those required for the proper operation and maintenance of the system. Ducts passing through combustible walls, ceilings, floors or roofs shall provide adequate insulation and clearances to prevent surface temperatures from exceeding 160 degrees F. Exhaust ducts shall not discharge within 10 feet of doors, windows or other air intakes in a manner that will permit re-entry of vapors into the building. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 139 CHAPTER 31 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 3103 TEMPORARY TENTS AND MEMBRANE STRUCTURES Section 3103.2 Approval required is replaced as follows: 3103.2 Approval required. Tents and membrane structures having an area in excess of 200 square feet shall not be erected, operated, or maintained for any purpose without first obtaining a permit and approval from the fire code official in accordance with Section 105. Exceptions: 1. Tents used exclusively for recreational camping purposes. 2. Tents open on all sides that comply with all of the following: 2.1 Individual tents having a maximum size of 400 square feet (65 m2). 2.2 The aggregate area of multiple tents placed side by side without a fire break clearance of 12 feet (3658 mm), not exceeding 400 square feet (37 m2) total. 2.3 A minimum clearance of 12 feet (3658 mm) to all structures and other tents. Section 3103.9 Anchorage required is amended by replacing the last sentence as follows: Documentation of structural stability in accordance with Section 3102.7 of the International Building Code shall be furnished to the fire code official on request. SECTION 3107 OPERATIONAL REQUIREMENTS Section 3107.17 Standby personnel is replaced as follows: 3107.17 Standby personnel. When, in the opinion of the fire code official, it is essential for public safety in a tent, or membrane structure used as a place of assembly or any other use where people congregate, or any building premise or property where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest, or activity, or when potentially hazardous conditions exist, or an occupant load varies due to large crowd movement from one building to another building or one area of a building to another area of the building, or there is a reduction in a life safety feature, or there is an impairment to a fire protection feature, the owner, agency, or lessee shall employ and compensate one or more qualified individuals , as required by the fire code official. Such qualified individuals shall be subject to the fire code official's orders at all times when so employed and shall remain on duty during the times such places are open to the public or when such activity is being conducted or, in the case of residential occupancies, whenever occupied. Section 3107.17.3 Permit required is added as follows: 3107.17.3 Permit required. A fire watch operational permit shall be acquired in accordance with Section 105 prior to any occupancy of the tent or membrane structure. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 140 CHAPTER 32 HIGH-PILED COMBUSTIBLE STORAGE SECTION 3201 GENERAL Section 3201.3 Construction documents is replaced as follows: 3201.3 Construction documents. A construction permit shall be required in accordance with Section 105 for the installation or reconfiguration of all high-piled storage systems. Installation plans and specifications shall be submitted for review and approval and shall include the information specified in Appendix N. Approved plans shall be maintained on the premises in an approved location and available to Englewood Fire Marshal’s office personnel upon request. SECTION 3206 GENERAL FIRE PROTECTION AND LIFE SAFETY FEATURES Table 3206.2 General Fire Protection and Life Safety Requirements is replaced as follows: TABLE 3206.2 GENERAL FIRE PROTECTION AND LIFE SAFETY REQUIREMENTS COMMODITY CLASS SIZE OF HIGH- PILED STORAGE AREA a (square feet) (see IFC Sections 3206.2 and 3206.4) ALL STORAGE AREAS (See IFC Sections 3206, 3207, and 3208) b SOLID -PILED STORAGE, SHELF STORAGE AND PALLETIZED STORAGE (See IFC Section 3207.3) Automatic fire- extinguishing system (see IFC Section 3206.4) Building Access (see IFC Section 3206.6) Smoke and heat removal (see IFC Section 3206.7) Maximum pile dimension c (feet) Maximum permissible storage height d (feet) Maximu m pile volume (cubic feet) I-IV 0-500 Not Required a Not Required e Not Required Not Required Not Required Not Required 501-2,500 Yes a,i Not Required e Not Required 100 40 100,000 2,501-12,000 Yes Not Required e Not Required 100 40 400,000 12,001- 20,000 Yes Yes Yes j 100 40 400,000 20,001- 500,000 Yes Yes Yes j 100 40 400,000 Greater than 500,000 g Yes Yes Yes j 100 40 400,000 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 141 High hazard 0-500 Not Required a Not Required e Not Required 50 Not Required Not Required 501-2,500 Yes Not Required e Not Required 50 30 75,000 2,501- 300,000 Yes Yes Yes j 50 30 75,000 300,001- 500,000 g, h Yes Yes Yes j 50 30 75000 For SI: 1 foot = 304.8mm, 1 cubic foot = 0.02832m3, 1 square foot = 0.0929m2 a. When automatic sprinklers are required for reasons other than those in Chapter 32 of the International Fire Code, the portion of the sprinkler system protecting the high-piled storage area shall be designed and installed in accordance with Sections 3207 and 3208. b. For aisles, see Section 3206.9 of the International Fire Code c. Piles shall be separated by aisled complying with Section 3206.9 of the International Fire Code d. For storage in excess of the height indicated, special fire protection shall be provided in accordance with Note g where required by the fire code official. See Chapters 51 and 57 of the International Fire Code, for special limitations for aerosols and flammable and combustible liquids, respectively. e. Section 503 of the International Fire Code shall apply for fire apparatus access. f. Intentionally deleted. g. Special fire protection provisions including, but not limited to, fire protection of exposed steel columns; increased sprinkler density; additional in rack sprinklers, without associated reductions in ceiling sprinkler density; or additional fire department hose connections shall be provided when required by the fire code official. h. High-piled storage areas shall not exceed 500,000 square feet. A 2-hour fire wall constructed in accordance with Section 706 of the International Building Code shall be used to divide high-piled storage exceeding 500,000 square feet in area. i. Sprinkler protection is not required for storage of Class I commodities. Sprinkler protection in accordance with NFPA 13 or automatic fire detection shall be provided in accordance with Section 3206.5 of the International Fire Code for Class II, III and IV commodities. j. Not required where storage areas are protected by early suppression fast response (ESFR) sprinkler systems or control mode special application sprinklers with a response time index of 50 (m s) ½ or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers and installed in accordance with NFPA 13. Section 3206.7.5 Number of doors required - Exception is replaced as follows: Exception. The linear distance between adjacent access doors is allowed to exceed 100 feet but not to exceed 200 feet in existing buildings constructed prior to May 2011 where no change in occupancy is proposed. The number and distribution of access doors in existing buildings shall be approved by the fire code official. Section 3206.7.5.1 Storage above doors is added as follows: 3206.7.5.1 Storage above doors. The clear height in accordance with Section 3206.10.2 shall be maintained to the access doors. No racking components shall be located in the clear height. Exceptions: 1. Rack structure provided for lateral bracing or rack stability and not able to be utilized for storage. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 142 2. A single 24-inch catwalk as permitted by Section 3206.10.1 of the International Fire Code., Exception 1. Section 3211 Existing Buildings is added as follows: SECTION 3211 EXISTING BUILDINGS 3211.1 Scope - Existing buildings constructed prior to October 1990. This section is applicable to high- piled or rack storage in existing buildings as follows: 1. Any modification to the existing commodities stored in an existing tenant space where storage height is increased, or classification of the commodities is placed in a higher category in accordance with Section 3203. 2. New tenant spaces in existing buildings. 3. Existing tenant spaces with new tenants. 4. In buildings that were built and occupied by a tenant with high-piled combustible stock prior to the adoption of the Uniform Codes on October 1, 1990; as long as that tenant remains in operation, it will be up to the Fire Department inspection to identify any unsafe conditions in accordance with Section 110. 3211.2 Storage of Class I commodity – as defined by NFPA 13. 3211.2.1 Automatic sprinklers. Where an automatic sprinkler system is required by Table 3206.2, an approved automatic sprinkler system shall be provided in accordance with NFPA 13. Exception: Existing automatic sprinkler systems shall be accepted provided that the system has been certified by a qualified Colorado professional engineer to provide a minimum design density to a minimum of 70% of that required by NFPA 13 but not less .2 gpm over 2,000 sq. ft. Density reductions or adjustments permitted by NFPA 13 shall not apply for determination of the 70% minimum density. 3211.2.2 Building access. Building access from fire apparatus access roads in accordance with Section 503 shall be provided within 200 feet of all portions of the exterior walls of a building used for high- piled storage. 3211.2.2.1 Access doors. Fire Department access doors shall be provided in accordance with Section 3206.7.1. 3211.2.3 Aisles. Shall be in accordance with Section 3206.10 or 903.3.1; the most restrictive shall govern. 3211.2.4 Portable fire extinguishers. Shall be in accordance with Section 3206.11 of the International Fire Code. 3211.3 Storage of Class II and III commodity - as defined by NFPA 13. 3211.3.1 Automatic sprinklers. Where an automatic sprinkler system is required by Table 3206.2, an approved automatic sprinkler system shall be provided in accordance with NFPA 13. Exception: Existing automatic sprinkler systems shall be accepted provided that the system has been certified by a qualified Colorado professional engineer to provide a minimum design density DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 143 to a minimum of 70% of that required by NFPA 13, but not less .2 gpm over 2,000 sq. ft. Density reductions or adjustments permitted by NFPA 13 shall not apply for determination of the 70% minimum density. 3211.3.2 Building access. Building access from fire apparatus access roads in accordance with IFC Section 503shall be provided within 200 feet of all portions of the exterior walls of a building used for high-piled storage. 3211.3.2.1 Access doors. Fire Department access doors shall be provided in accordance with Section 3206.7. 3211.3.3 Smoke and heat removal. Smoke and heat vents shall be provided in accordance with Table 3206.2 with a minimum vent area of 1:200. Exceptions: Existing roof openings such as skylights may be used as smoke vents in accordance with Section 1108 - Item 4. 3211.3.4 Aisles. Shall be in accordance with Section 3206.10 or 903.3.1; the most restrictive shall govern. 3211.3.5 Portable fire extinguishers. Shall be in accordance with Section 3206.11. 3211.4 Storage of Class IV, high-hazards and plastics commodities - as defined by NFPA 13. 3211.4.1 Automatic sprinklers. Where an automatic sprinkler system is required by Table 3206.2, an approved automatic sprinkler system shall be provided in accordance with NFPA 13. 3211.4.2 Building access. Building access from fire apparatus access roads in accordance with Section 503 shall be provided within 150 feet of all portions of the exterior walls of building used for high-piled storage. 3211.4.2.1 Access doors. Fire Department access doors shall be provided in accordance with Section 3206.7. 3211.4.3 Smoke and heat removal. Smoke and heat vents shall be provided in accordance with Table 3206.2 with a minimum vent to floor area ratio of 1:200. 3211.4.4 Aisles. Shall be in accordance with Section 3206.10. 3211.4.5 Portable fire extinguishers. Shall be in accordance with Section 3206.11. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 144 CHAPTER 33 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 3301 GENERAL Section 3301.3 Permit required is added as follows: 3301.3 Permit required. Permits shall be required as set forth in Section 105 for the activities or uses regulated by Sections 3303 – Temporary Heating Equipment, 3304.3 – Burning of combustible debris, rubbish and waste, 3304.4 - Open Burning, 3304.5 – Fire Watch, 3304.6 – Cutting and Welding, 3305.1 Storage of Flammable and Combustible Liquids, 3305.2–Class I and Class II Liquids, 3306.1 – Storage and Handling (Flammable Gases), 3307.1 – Storage and Handling (Explosive Materials), 3317- Safeguarding Roofing Operations, and 3318 – Asbestos Operations of the International Fire Code. SECTION 3311 MEANS OF EGRESS Section 3311.1 Stairways required is amended as follows: 3311.1 Stairways required. Where a building has been constructed to a building height of 40 feet (15 240 mm) or four stories, or where an existing building exceeding 40 feet (15 240 mm) in building height is altered, not less than one temporary lighted stairway shall be provided unless one or more of the permanent stairways are erected as the construction progresses. SECTION 3313 STANDPIPES Section 3313.1 Where required is replaced as follows: 3313.1 Where required. Buildings four or more stories in height shall be provided with not less than one standpipe for use during construction. Such standpipes shall be installed when the progress of construction is not more than 30 feet in height above the lowest level of Fire Department vehicle access or where the floor level of the lowest story is located more than 30 feet below the highest level of Fire Department vehicle access. Such standpipes shall be provided with Fire Department hose connections at accessible locations adjacent to usable stairs. Such standpipes shall be extended as construction progresses to within one floor of the highest point of construction having secured decking or flooring. One fire department connection [not less than two (2) 2.5-inch inlets with 4-inch piping] shall be provided for buildings less than 200 feet in height. Where building exceeds 200 feet in height, two (2) separate 6-inch manual dry standpipes shall be required. These standpipes shall be located adjacent to a usable stair with a 200 feet maximum separation between standpipes. Each standpipe shall be connected to two (2) 2.5-inch inlet fire department connections. Each fire department connection shall be signed indicating which standpipe it serves. The fire department connection(s) shall be provided in accordance with Section 912 of the International Fire Code., at a location visible from the public way, accessible to fire apparatus and approved by Fire Prevention personnel. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 145 CHAPTER 34 TIRE REBUILDING AND TIRE STORAGE SECTION 3405 OUTDOOR STORAGE Section 3405.4 Distance from lot lines and buildings is amended by adding an Exception as follows: Exception: Outside storage shall be limited to 5,000 square feet (464.5 m 2) of tire storage. Storage in excess of 5,000 square feet (464.5 square meters) does not meet this exception. Tire storage piles shall be located at least 10 feet (3048 mm) from lot lines and buildings if storage is no higher than six (6) feet (1836 mm). Storage heights from six feet (1836 mm) to 10 feet (3048 mm) shall be no closer to lot lines and buildings than 20 feet (6096 mm). SECTION 3408 FIRE PROTECTION Section 3408.3 Automatic sprinkler systems is added as follows: 3408.3 Automatic sprinkler systems. Automatic sprinkler systems shall be installed in accordance with Section 903.2.9.2. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 146 CHAPTER 35 WELDING AND OTHER HOT WORK SECTION 3501 GENERAL Section 3501.3 Restricted areas is amended by adding Item 6 as follows: 6. Areas where uncleaned or improperly prepared drums, tanks, or other containers and equipment that have previously contained materials that could develop explosive atmospheres. SECTION 3505 GAS WELDING AND CUTTING Section 3505.2 Cylinder and container storage, handling and use is replaced as follows: 3505.2 Cylinder and container storage, handling and use. Storage, handling and use of compressed gas cylinders, containers and tanks shall be in accordance with this section and Chapter 53. Ordinary rope slings or electromagnets shall not be used. SECTION 3508 ACETYLENE GENERATORS Section 3508.1 Use of acetylene generators is replaced as follows: 3508.1 Use of acetylene generators. The use of acetylene generators shall comply with this Section and NFPA 51 and 51A. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 147 Chapter 39 Processing and extraction facilities is replaced in its entirety as follows: CHAPTER 39 MARIJUANA OPERATIONS SECTION 3901 GENERAL 3901.1 Scope. This section shall apply to all occupancies engaging in marijuana (i.e. cannabis and extract derivatives) sales locations, growing, processing, extraction, and/or testing. These occupancies shall comply with this chapter and other applicable provisions of this Code. 3901.2 Permits. Permits shall be required as set forth in Section 105 and in accordance with City of Englewood Fire Marshal’s Office. 3901.3 Existing Operations. Buildings containing existing growing or extraction operations shall comply with this code by October 1, 2016. SECTION 3902 DEFINITIONS 3902.1 Definitions. The following terms are defined in Chapter 2. CHEMICAL FUME HOOD EXTRACTION POST OIL PROCESSING SECTION 3903 EXTRACTION OPERATIONS 3903.1 Construction Requirements. 3903.1.1 Location. Extraction processes shall be performed in a room dedicated to the extraction process. Extraction processes utilizing flammable liquefied gas shall not be located in any building containing Group A, E, I, or R occupancies. 3903.1.2 Egress. Exit doors from extraction rooms utilizing hazardous materials shall swing in the direction of egress and be self-closing. Panic hardware shall be provided on doors in liquefied petroleum gas (LPG) extraction rooms. Where latching door hardware is provided on extraction rooms utilizing hazardous materials, panic hardware shall be provided. 3903.1.3 Extraction Rooms. Extraction room shall be fully enclosed. The floor, ceiling, and walls of extraction rooms shall be constructed in accordance with the Englewood Building Code and be continuous, non-combustible, and smooth. Rooms designed in accordance with Section 3903.4.1.1 shall be constructed to permit the free passage of exhaust air from all parts of the room. Exceptions: 1. Enclosed booths constructed in accordance with Section 2404.7.3.2 of the International Fire Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 148 2. CO2 extraction rooms and extraction rooms containing processes not utilizing hazardous materials. 3903.1.4 Openings and penetrations. Openings and penetrations into extraction rooms utilizing hazardous materials shall only be provided for egress, mechanical, electrical, or plumbing systems serving the extraction room. Penetrations into LPG extraction rooms shall be sealed vapor tight. Non-operable glazing is permitted where glazing does not interfere with required exhaust systems. 3903.1.5 Extraction room illumination. Luminaires inside the extraction room shall comply with Section 3903.2.2. Luminaires attached to the walls or ceilings of an extraction room or booth, but outside of any classified area and separated from the flammable vapor areas by vapor-tight glass panels, shall be suitable for use in ordinary hazard locations. Such luminaires shall be serviced from outside the flammable vapor areas. 3903.1.6 Fire protection. Extraction rooms, booths, or hoods, including ductwork where required for hazardous exhaust systems, shall be protected by an approved automatic fire extinguishing system complying with Chapter 9 where any of the following exist: 1) Extraction processes utilizing LPG or off gassing LPG from spent plant material or oil 2) Vapors are released exceeding 25% of the lower flammable limit from flammable liquid extraction processes or flammable liquid post oil processing. 3903.2 Sources of ignition. Extraction or post oil processing operations which use flammable liquids or liquefied petroleum gas (LPG) shall comply with Sections 3903.2.1 through 3903.2. 3903.2.1 Open flame and sparks. Smoking, open flames, direct fired heating devices, etc. shall be prohibited in areas where flammable vapors exist. 3903.2.2 Electrical equipment. Electrical equipment installed in rooms designed in accordance with Section 3903.4.1.1, hoods, or booths containing LPG extraction processes shall be in accordance with NFPA 70 (NEC) as a Class I Division I location. Areas adjacent to classified locations shall be in accordance with NFPA 70 (NEC). Electrical equipment installed in areas of flammable liquid extractions or post oil processing shall be in accordance with Chapter 50 of the International Fire Code, and NFPA 70 (NEC). Exception: Subject to approval of the fire code official, rooms or booths containing LPG extraction equipment that is not normally opened within the room or booth for oil or plant material retrieval, and frequent leakage in the closed system does not occur, may be considered a Class I Division II location. 3903.2.3 Grounding and Bonding. Precautions shall be taken within LPG extraction rooms to minimize the possibility of ignition by static electrical sparks through static bonding and grounding of extraction equipment, ducts, and piping etc. installed in accordance with NFPA 70 (NEC). 3903.3 Equipment. Extraction process equipment utilizing hazardous materials shall be listed or approved. 3903.4 Exhaust required. Extraction and post oil processing, utilizing LPG or flammable liquids shall be provided with an exhaust system in accordance with Section 3903.4.1 or 3903.4.2. The exhaust system shall be in operation at all times when extractions or post oil processing is being performed and until LPG is off gassed from oil and/or plant material removed from LPG extraction equipment. Fans shall be of the type approved for use when flammable or explosive vapors are present in accordance with the International Mechanical Code, Section 503. Capture and containment air velocity shall be provided across booths, hoods, or exhausted enclosures to capture and convey emissions to the exhaust system and shall be no less than 75 fpm. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 149 3903.4.1 Exhaust for LPG extraction processes. A hazardous exhaust system engineered in accordance with the Englewood Building and Fire Code shall be provided for LPG extraction processes including LPG degassing from processed plant material or oil removed from extraction equipment. 3903.4.1.1 Exhausted enclosure. Where the extraction room is used as the exhausted enclosure, the exhaust system shall be designed to provide capture and containment air velocity across all areas of the enclosure. 3903.4.1.2 Electrical Interlocks. The exhaust system shall be interlocked with the room power, such that when the exhaust system is not operating, power and lighting will be disabled. 3903.4.2 Exhaust for Flammable Liquid Extraction processes. A hazardous exhaust system in accordance with the Englewood Building and Fire Code shall be provided for flammable liquid extraction processes. Exceptions: 1. Distillation process with less than 5 gallons of flammable liquid performed under a chemical fume hood installed in accordance with the Englewood Building and Fire Code unless a hazardous exhaust system is required by the Englewood Building and Fire Code. 2. Solvent distillation units in compliance with Section 5705.4 of the International Fire Code. 3. Extractions performed in accordance with Englewood Ordinance No. 629-14, § 1, 11-10-14 3903.5 Gas Detection. A continuous gas detection system shall be provided within rooms, booths or hoods, containing CO2 or LPG extraction processes. Actuation of the gas detection system shall initiate a local alarm within the room. CO2 gas detection systems shall alarm at 5000ppm. LPG gas detection systems shall alarm at no greater than 20% of the LFL. Portable LPG gas detection shall be utilized by the extraction system operator to verify local hydrocarbon levels, including system leaks. 3903.6 CO2 Extraction Equipment Process discharge. CO2 discharges shall be piped to the exterior. 3903.7 Refrigeration and Cooling Equipment. Refrigerators, freezers, and other cooling equipment used to store, or process flammable liquids shall be in accordance with NFPA 45 and applicable provisions of the Englewood Building and Fire Code. 3903.8 Stand-by power systems. For new or modified hazardous exhaust systems, a stand-by power system complying with Chapter 12, shall be provided for the following items, when installed: 1. Extraction room lighting 2. Extraction room ventilation system 3. Solvent gas detection system Exception: Stand-by power shall not be required where it can be shown by engineering analysis that the hazardous process conducted will not create hazardous conditions when normal power is lost. SECTION 3904 MARIJUANA GROWING OPERATIONS 3904.1 CO2 Enrichment Systems. CO2 enrichment systems shall comply with Section 5305. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 150 Chapter 40 ALCOHOL BEVERAGE PRODUCTION FACILITIES is added as follows: CHAPTER 40 ALCOHOL BEVERAGE PRODUCTION FACILITIES SECTION 4001 GENERAL 4001.1 Scope. Buildings and portions thereof where ethanol mixtures are produced, stored, handled or dispensed in the production of alcohol beverages shall be regulated in accordance with this Chapter and the Englewood Building and Fire Code. The intent of this Chapter is to establish minimum requirements consistent with nationally recognized good practice for providing a reasonable level of life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing alcohol beverage production facilities (ABPFs) such as distilleries, breweries, and wineries, and to provide safety to fire fighters and emergency responders during emergency operations. The objective is to consolidate regulations for materials, systems, processes, and conditions most commonly found in ABPFs to facilitate compliance with the intent of this chapter. The fire and building code officials are authorized to enforce applicable provisions of the Englewood Building and Fire Code, referenced standards, and recommended practices not specifically addressed in this chapter provided they are consistent with the intent and objective of this chapter. Consideration shall be given to the unique materials and equipment utilized in this industry such as wooden casks (typically barrels) and high quality but as-yet, unlisted, stills. Unless otherwise noted, where provisions in this chapter conflict with provisions in other sections of the Englewood Building and Fire Code for ABPFs, the provisions of this chapter shall supersede the provisions in those sections. 4001.2 Referenced standards. The Fire and Building code officials are authorized to enforce applicable provisions of the standards listed in Chapter 80 of the International Fire Code and Chapter 35 of the International Building Code to ensure the safe operation of ABPFs. Table 3801.2 lists the standards most often utilized for ABPFs. TABLE 4001.2 REFERENCED STANDARDS DOCUMENT TITLE NFPA 13 Standard for the Installation of Sprinkler Systems NFPA 30 Flammable and Combustible Liquids Code NFPA 61 Standard for the Prevention of Fires and Dust Explosions in Agricultural and Food Processing Facilities NFPA 69 Standard on Explosion Prevention Systems NFPA 70 National Electrical Code (NEC) DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 151 NFPA 72 National Fire Alarm and Signaling Code NFPA 505 Fire Safety Standard For Powered Industrial Trucks Including Type Designations, Areas Of Use, Conversions, Maintenance, And Operations NFPA 704 Standards System for Identification of the Hazards Materials for Emergency Response NFPA 780 Standard for the Installation of Lightning Protection Systems 4001.3 Recommended practices. The Fire and Building code officials shall have the authority to utilize the recommended practices listed in Table 4001.3 to render interpretations and develop policies and procedures in the application of the provisions of the Englewood Building and Fire Code and referenced standards. Such interpretations, policies, and procedures shall be in compliance with the intent and objective of this chapter. TABLE 4001.3 RECOMMENDED PRACTICES NFPA 77 Recommended Practice on Static Electricity NFPA 497 Recommended Practice for the Classification of Flammable Liquids, Gases, or Vapors and of Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas NFPA 499 Recommended Practice for the Classification of Combustible Dusts and of Hazardous Locations for Electrical Installations in Chemical Process Areas The Distilled Spirits Council of the United States, Inc. Recommended Fire Protection Practices for Distilled Spirits Beverage Facilities 4001.4 Construction Documents. Construction documents shall be submitted for review and permit prior to the installation, construction, or modification of ABPFs or the operational equipment therein. 4001.5 Operational Permits. Operational permits shall be required as set forth in Section 105 . SECTION 4002 DEFINITIONS, ACRONYMS AND ABBREVIATIONS 4002.1 Definitions. The following terms are defined in Chapter 2. ALCOHOL BEVERAGE ALCOHOL BEVERAGE PRODUCTION FACILITY (ABPF) ALCOHOL BY VOLUME (ABV) DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 152 BEVERAGE SPIRIT (TTB) BREWERY BULK STORAGE CASK CLASS 1 LIQUIDS CONTAINER ENGLEWOOD BUILDING CODE ENGLEWOOD BUILDING AND FIRE CODE ENGLEWOOD FIRE CODE DISTILLATION DISTILLERY (ALSO “DISTILLED SPIRITS PLANT – BEVERAGE”) DISTILLED SPIRITS PLANT – INDUSTRIAL DISTILLED SPIRITS PLANT – INDUSTRIAL / BEVERAGE DISTILLED SPIRITS PLANT – EXPERIMENTAL ETHANOL (ALSO, “ETHYL ALCOHOL” OR “GRAIN ALCOHOL”) ETHANOL MIXTURE FERMENTATION HAZMAT HAZMAT INVENTORY STATEMENT (HMIS) HAZMAT MANAGEMENT PLAN (HMMP) HAZMAT REPORT (HMR) INTERMEDIATE BULK CONTAINER LOWER FLAMMABLE LIMIT (LFL) MASH MINIMUM EXPLOSIVE CONCENTRATION (MEC) NORMALLY CLOSED NORMALLY OPEN PILE PORTABLE TANK PROCESS DESCRIPTION PRESSURE VESSEL DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 153 PROCESSING VESSEL RACK REMOTE AREA SPIRIT STATIONARY TANK STILL STORAGE AREA TANK USE AREA VAT (ALSO FOUDRE) WASH (ALSO BEER, MALT LIQUOR) WINE WINERY WORT VESSEL 3802.2 Acronyms and abbreviations. The following acronyms and abbreviations shall, for the purposes of this chapter, have the meanings identified below: ABPF. Alcohol Beverage Production Facility. ABV. Alcohol by Volume. ASME. American Society of Mechanical Engineers. ASTM. American Society for Testing and Materials. HMIS. HazMat Inventory Statement. HMMP. HazMat Management Plan. HMPA. HazMat Permit Application. HMR. HazMat Report. LEL. Lower Explosive Limit. LFL. Lower Flammable Limit. MAQ. Maximum allowable quantity per control area in accordance with Section 5003.1.1 of the International Fire Code. MEC. Minimum Explosive Concentration. MSDS. Material Safety Data Sheet NEC. National Electrical Code DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 154 TTB. Alcohol and Tobacco Tax and Trade Bureau SECTION 4003 GENERAL REQUIREMENTS 4003.1 Material classification. Hazard classifications and analyses of ethanol mixtures shall account for altitude-dependent properties based on an elevation of 5,280 feet (1,609 m) above sea level. Ethanol mixtures that have no fire point when tested in accordance with ASTM D 92, Standard Test Method for Flash and Fire Points, by Cleveland Open Cup Tester and ethanol mixtures with 16 percent or less ABV with the remainder comprised of materials with hazards not regulated by the Englewood Building and Fire Code shall not be regulated as flammable or combustible liquids. Ethanol mixtures with greater than 16 percent ABV and less than or equal to 34 percent ABV, and the remainder comprised of water and other materials with hazards not regulated by the Englewood Building and Fire Code, shall be classified as Flammable 1C liquids. Ethanol mixtures with greater than 34 percent ABV, and the remainder comprised of water and other materials with hazards not regulated by the Englewood Building and Fire Code, shall be classified as flammable 1B liquids. 4003.2 Occupancy classification. The occupancy classification of use areas and storage areas including grain- handling and bottling/packaging systems and processes shall be classified in accordance with Sections 4003.2.1 through 4003.2.3. 4003.2.1 H-2 occupancy classification. An H-2 occupancy classification shall be assigned to buildings or portions thereof in accordance with Sections 4003.2.1.1 and 4003.2.1.2. 4003.2.1.1 Combustible dust producing operations. ABPFs or portions thereof containing equipment, systems and processes where grains are stored, transferred or milled in such a manner that the confinement conditions and dust concentrations create a fire or explosion hazard shall be in accordance with Chapter 22 and Chapter 50 of the International Fire Code. The fire and building code officials are authorized to require technical assistance in accordance with Section 104 to establish whether the building or portion thereof is required to be assigned an H-2 occupancy classification and to determine explosion and deflagration hazard reduction criteria. 4003.2.1.2 Flammable liquids. ABPFs and portions thereof with quantities of Class 1 Liquids in excess of the MAQs, that are stored or processed in normally open vessels or systems, or vessels or systems that are pressurized at more than 15 pounds per square inch gauge (psig; 103.4 kPa), or where a Class 1 Liquid is released to atmosphere at or above its flash point temperature as part of normal operations shall be assigned an H-2 occupancy classification. 4003.2.2 H-3 occupancy classification. ABPFs and portions thereof with quantities of Class 1 Liquids in excess of the MAQs, that are stored or processed in normally closed vessels or systems pressurized to 15 pounds per square inch gauge (psig; 103.4 kPa) or less, shall be classified as H-3 occupancies. Exception: Quantities of ethanol mixtures beverages exceeding the MAQs but packaged in individual containers not exceeding 1.3 gallons (5 L) in volume shall not cause the ABPF or portion thereof to be assigned an H-3 occupancy classification. 4003.2.3 Non-high hazard occupancy classification. Control areas with Class 1 Liquids, combustible dust production, or other regulated hazards shall be assigned an occupancy classification in accordance with the Englewood Building and Fire Code according to the fire safety and relative hazard involved. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 155 4003.3.1 Hazardous materials report (HMR). An HMR in an approved format is required for all facilities using or storing HazMat. It shall contain at a minimum, critical personnel contact information, pertinent building construction and occupancy information, and an HMIS. 4003.3.2 Hazardous materials management plan (HMMP). An HMMP in accordance with Section 5001.5.1 and Appendix H101 shall be provided in an approved format. 4003.3.3 Process description. A process description shall be provided in an approved format. All relevant process and storage operations in all Control Areas and Group H Occupancies shall be identified. The quantities of all materials with regulated hazards in each area at each step of all processes shall be calculated. The maximum capacity of all Class 1 Liquid bulk storage vessels, processing vessels and stills shall be used in the quantity calculation. The capacities of all such vessels and stills that can be used simultaneously shall be counted as being simultaneously full. 4003.3.4 Emergency Planning. Fire safety and evacuation plans in accordance with Section 404 of the International Fire Code shall be prepared and maintained. 4003.3.5 Storage plan. Aisle and storage plans shall be submitted in accordance with Chapter 50 of the International Fire Code. 4003.3.6 Material safety data sheets. MSDS shall be readily available on the premises for HazMat therein. 4003.3.7 Unauthorized Discharges Preparation. Plans and provisions shall be made for controlling and mitigating unauthorized discharges. 4003.3.8 Personnel training and written procedures. Persons responsible for the operations in Class 1 Liquid storage areas or use areas shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of fire, leak, or spill. 4003.3.9 Fire department liaison. Responsible persons shall be designated and trained to be liaison personnel to the fire department. They shall aid the fire department in preplanning emergency responses and identifying the locations of HazMat, shall have access to MSDS and be knowledgeable in the site's emergency response procedures. 4003.4 Unauthorized discharges. When Class 1 Liquids are released in quantities reportable under state, federal or local regulations, the fire code official shall be notified and action shall be taken in accordance with Sections 4003.4.1 and 4003.4.2 of the International Fire Code. 4003.4.1 Records. Accurate records shall be kept of all unauthorized discharges of Class 1 Liquids by the permittee. 4003.4.2 Responsibility for cleanup. The person, firm or corporation responsible for an unauthorized discharge shall institute and complete all actions necessary to remedy the effects of such unauthorized discharge, whether sudden or gradual, at no cost to the jurisdiction. When deemed necessary by the fire code official, cleanup may be initiated by the fire department or by an authorized individual or firm. Costs associated with such cleanup shall be borne by the owner, operator or other person responsible for the unauthorized discharge. 4003.5 Construction. The construction of ABPFs shall be in accordance with Sections 4003.5.1 and 4003.5.2. 4003.5.1 General. Special detailed requirements, building heights, allowable areas, construction types, control areas, rated assemblies, finishes, means of egress, accessibility, interior environment, energy DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 156 efficiency, exterior walls, roofing, structural design, fire service features, building services and systems, and fire and smoke protection shall be in accordance with the Englewood Building and Fire Code for the assigned occupancy classifications and this Chapter. 4003.5.2 Floors. Floors of use areas and storage areas for Class 1 Liquids shall be of noncombustible construction. Floor surfacing shall not be reactive with ethanol. 4003.6 Systems, features and components. Systems, features and components shall be provided in accordance with Sections 4003.6.1 through 4003.6.13. 4003.6.1 Deflagration prevention by combustible concentration reduction. Atmospheric concentration of flammable vapors shall be maintained at or below 25 percent of the LFL, and combustible dusts at or below 25 percent of the MEC, in all areas of the ABPF or portion thereof where they could collect or migrate. Good housekeeping shall be exercised to prevent accumulation of combustible dust on all exposed surfaces at all levels throughout the building. Indoor storage areas and use areas are permitted to be provided with natural ventilation where it can be shown to maintain the atmospheric concentrations at or below 25 percent of the LFL and MEC for the materials under consideration. Where natural ventilation is not adequate, Class 1 Liquid use areas, storage areas and equipment, machinery, and operations which produce or emit combustible dust, shall be provided with an approved mechanical collection and exhaust system in accordance with Sections 501, 502.1, 502.8, 502.9.5 and 503 of the International Mechanical Code. Use areas and storage areas in ABPFs or portions thereof where Class 1 Liquid vapor concentrations cannot be maintained at or below 25 percent of the LFL, or confined enclosures where the concentration of combustible dust cannot be maintained at or below 25 percent of the MEC, shall be provided hazardous exhaust in accordance with Sections 510 and 511 of the International Mechanical Code. 4003.6.1.1 System requirements. Exhaust ventilation systems shall comply with all of the following: 1. Installation shall be in accordance with the International Mechanical Code. 2. Mechanical ventilation over the storage area or use area shall be at a rate of not less than 1 cubic foot per minute per square foot [cfm/ft2; 0.00508 cms/m2)] of floor area. Exception: Areas where Class 1 Liquids are stored in casks are permitted to be provided with an engineered ventilation system in accordance with Chapter 4 of the International Mechanical Code. The air flow rate shall not be less than the greater of (1) that required to maintain the flammable vapor concentration in the storage area at or below 25 percent of the LFL, or (2) 0.06 cubic feet per minute per square foot (cfm/ft2; 0.000305 cms/m2). 3. Systems shall operate continuously unless alternative designs are approved. 4. A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room, or in an approved location. The switch shall be a break-glass or other approved type and shall be labeled, “VENTILATION SYSTEM EMERGENCY SHUTOFF.” 5. Exhaust ventilation shall be designed to consider the density of the material released. For ethanol vapor, inlet air shall be introduced, and exhaust shall be taken, from a point within 12 inches (305 mm) of the floor. For dust, inlet air shall be introduced at a point within 12 inches (305 mm) of the floor and exhaust shall be taken as close to the dust generation source as possible. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 157 6. The location and configuration of both the inlet and exhaust air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of flammable vapors and suspended dust. 7. Exhaust air shall not be recirculated to occupied areas. 4003.6.2 Spill control and secondary containment. Spill control and secondary containment shall be provided in accordance with Sections 4003.6.2.1 through 4003.6.2.2. 4003.6.2.1 Indoor. Spill control and secondary containment shall be provided for H-2 and H-3 occupancies in ABPFs where: 1. The capacity of any single normally closed vessel or system with Class 1 Liquids exceeds 55 gallons (208 L); 2. The aggregate capacity of multiple normally closed vessels or systems with Class 1 Liquids exceeds 1,000 gallons (3,785 L); or 3. Class 1 Liquids are dispensed into or from a normally open vessel or system exceeding a 5.3- gallon (20 L) capacity. 4003.6.2.1.1 Design. The drainage system shall be in accordance with the International Plumbing Code and the following: 1. All portions of the drainage system including floors shall be liquid-tight and constructed of noncombustible materials compatible with ethanol. Exception: Where approved by the fire and building code officials, and in compliance with federal, state, and local government agencies’ regulations and permits, floors of buildings or portions thereof used for the bulk storage of Class I Liquids are permitted to be exposed earth. Combustible materials such as tilled organic matter are permitted to be mixed with the dirt provided the mixture is non- combustible. 2. The drains and drainage system capacity shall be sized to carry the volumetric flow of water discharged from the automatic sprinkler system without backing up at the drains or pooling to a depth greater than ¼” (6.5mm). The sprinkler coverage area used to calculate the required volumetric flow is permitted to be based on the smaller of (1) the remote area in accordance with NFPA 13 – provided it is located in the area served by the drains – or (2) the area of the building or portion thereof served by the drains. Exception: When released onto the ground within a fire area, the volumetric flow of water is permitted to be reduced to account for the percolation into the soil. An engineering analysis shall be provided to establish the reduction. 3. Floors shall slope to drains. Impermeable curbs and floor slope shall be designed to prevent spilled Class I Liquids and water discharged from the automatic sprinkler system from flowing to adjoining areas. Floor slope shall not be less than 2%. Exceptions: 1. Floors in existing buildings with less than 2% slope are permitted to be used provided they are made liquid tight and floor sinks are installed as necessary to preclude water discharged from the automatic sprinkler system from pooling in low spots. These drains shall be installed in addition to the drains required in Item 2 of this section. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 158 2. Where trench drains or a combination of impermeable curbs and trench drains surround the sprinkler coverage area, the floors shall slope to the drains at a rate of not less than 1%. Where a combination of impermeable curbs and trench drains is used, no less than 50% of the perimeter shall be protected by trench drains. 4. Drainage systems shall terminate in an approved secondary containment reservoir designed to contain a spill from the largest vessel in the area served by the drains plus the volumetric flow of water calculated in Item 2 above for a period of 20 minutes. An approved automatic monitoring method shall be provided to detect material in the reservoir. Monitoring devices shall be connected to approved visual and audible alarms. Reservoir capacity to accommodate the required secondary containment volume shall be maintained at all times. Exception: Release of Class 1 Liquids and fire protection water directly into a sanitary or storm-water drainage system, onto the ground, or a combination thereof is permitted when in compliance with federal, state, and local governmental agencies’ regulations and permits. 4003.6.2.2 Outdoor. Secondary containment for outdoor storage areas shall be in accordance with Chapter 50 of the International Fire Code. 4003.6.3 Occupant and property protection. Occupant and property protection shall be provided in accordance with Sections 4003.6.3.1 through 4003.6.3.4. 4003.6.3.1 Automatic sprinklers. An automatic sprinkler system shall be installed throughout ABPF H-2 and H-3 fire areas in accordance with Sections 4003.6.3.1.1 through 4003.6.3.1.3. 4003.6.3.1.1 Flammable liquids. Sprinkler discharge criteria for Class 1 Liquid use areas and storage areas in ABPFs or portions thereof shall be in accordance with NFPA 30 but shall not be less than that required in accordance with NFPA 13 for Ordinary Hazard Group 2 with a minimum design area of 3,000 square feet (279 m2). Exception: H-2 and H-3 occupancies with storage of Class 1 Liquids in casks shall be protected by a sprinkler system designed for Extra Hazard 2 in accordance with NFPA 13, or by an approved engineered design. 4003.6.3.1.2 Combustible dust producing operations. Automatic sprinkler protection criteria for H-2/Combustible Dust Producing Operations shall be determined in accordance with Section 4003.2.1.1. 4003.6.3.1.3 Non-high hazard occupancies. Sprinkler discharge criteria for ABPFs or portions thereof not classified as a division of the high-hazard occupancy classification and where Class 1 Liquids are not present in quantities or conditions required to be regulated by NFPA 30 or this chapter, shall be in accordance with NFPA 13. 4003.6.3.2 Sprinkler system supervision and alarms. Automatic sprinkler systems shall be electrically supervised in accordance with Section 903.4 of the International Fire Code. Audible and visible occupant notification upon activation of water flow shall be provided in accordance with Section 907.5 of the International Fire Code throughout all areas in ABPFs with automatic sprinkler protection. 4003.6.3.3 Emergency alarm. In addition to automatic sprinkler system flow detection and all fire safety functions required by other sections of this code, an approved manual fire alarm system in accordance with Sections 4003.6.3.3.1 through 4003.6.3.3.3 shall be provided in H-2 and H-3 occupancies in ABPFs. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 159 4003.6.3.3.1 Initiation. Manual fire alarm boxes shall be installed in accordance with Section 907.4.2 of the International Fire Code outside of each interior exit or exit access door in the fire barrier walls separating the H-2 or H-3 occupancies, and in the exterior walls surrounding the H- 2 or H-3 occupancies. Exception: On exterior walls of H-2 or H-3 occupancies, fire alarm boxes are permitted to be installed inside of each interior exit, exit access, or exit discharge door in the exterior wall. Manual fire alarm boxes shall be installed at not more than 150-foot (45,720 mm) intervals along corridors, interior exit stairways or ramps, or exit passageways where Class 1 Liquids are transported. 4003.6.3.3.2 Notification. Emergency alarm audible and visible occupant notification shall be provided in accordance with Section 907 of the International Fire Code throughout fire areas containing H-2 or H-3 occupancies. 4003.6.3.3.3 Annunciation. The emergency alarm system shall be monitored and annunciated as a separate zone at the Fire Alarm Control Panel (FACP). A separate emergency alarm panel is required when prescribed by other sections of the Englewood Building and Fire Code for regulated hazards other than, or in addition to, Class 1 Liquids or combustible dust production in the manufacture of ethanol mixtures. When the emergency alarm system is activated, information shall be communicated to the supervising station that the zone in alarm contains flammable liquids or combustible dust, or both. 4003.6.3.4 Portable fire extinguishers. A minimum of one approved portable fire extinguisher complying with Section 906 of the International Fire Code and having a rating of not less than 20-B shall be located not less than 10 feet (3048 mm) or more than 50 feet (15 240 mm) from any Class 1 Liquid storage area or use area or combustible dust production area. 4003.6.4 Electrical. Electrical wiring, equipment and systems shall be installed and maintained in ABPFs in accordance with NFPA 70 (NEC) and Section 605 and Sections 4003.6.4.1 through 4003.6.4.4 of the International Fire Code. 4003.6.4.1 Classified electrical equipment. Classified electrical equipment per NFPA 70 (NEC) shall be installed in accordance with Section 5703.1.1 of the International Fire Code. in areas of ABPFs or portions thereof where it cannot be justified to the fire and building code official during design review, and subsequently demonstrated to the fire code official on annual inspections, that an atmospheric concentration at or below 25 percent of the LFL or MEC can be maintained. A classified area shall not be required to extend beyond an unpierced floor, roof or other solid partition that prevents the migration of liquids, vapors and dust. 4003.6.4.1.1 Stills. Electrical equipment attached to or part of stills in H-2 or H-3 occupancies shall be Class 1, Division 1 in accordance with NFPA 70 (NEC). 4003.6.4.1.2 Electric motors. Electric motors located 8 feet (2438 mm) or less from any edge of equipment where Class 1 Liquid vapor/air mixtures could exist under normal operations and 3 feet (914 mm) or less above the floor or grade level within 25 feet (7620 mm) horizontally from any equipment with Class 1 Liquids shall be considered Class 1, Division 2 in accordance with NFPA 70 (NEC). 4003.6.4.1.3 Other applications. The fire code official is authorized to determine the extent of the Class 1 electrical equipment and wiring location when a condition is not specifically covered by this chapter, Section 5703.1.1 of the International Fire Code or NFPA 70 (NEC). DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 160 4003.6.4.1.4 Industrial trucks. Powered industrial trucks used in areas designated as classified electrical locations in accordance with Section 4003.6.4.1 shall be listed and labeled for use in the intended environment in accordance with NFPA 505. 4003.6.4.2 Grounding. Equipment used for grain or Class 1 Liquids shall be electrically connected in accordance with NFPA 70 (NEC) and NFPA 77, and Sections 4003.6.4.2.1 and 4003.6.4.2.2 to prevent the accumulation of static electricity and sparking. 4003.6.4.2.1 Conveyance equipment. All conveyance equipment including that used for grain or Class 1 Liquid transfer and shall be electrically connected by bond wires, ground cables, piping or similar means to a static grounding system. Conveyor belts shall be electrically conductive and equipped with static eliminators. Nozzles and vessels used for the transfer of Class 1 Liquids shall be electrically interconnected by: 1. Metallic floor plates on which vessels stand while filling, when such floor plates are electrically connected to the fill stem; or 2. Where the fill stem is bonded to the container during filling by means of a bond wire. Exceptions: 1. Vats or casks without internal metal or plastic components that could hold a potential difference. 2. Equipment used in post bottling operations such as packaging and box storage shall be grounded in accordance with standards applicable to that equipment and industry practice. 4003.6.4.2.2 Storage equipment. Plastic and metal grain storage bins or silos and Class 1 Liquid stationary tanks that are drawn down and refilled on a regular basis or are otherwise subjected to processes that could create an electric potential difference and sparking, shall be grounded. 4003.6.4.3 Lightning protection. Lightning protection in accordance with NFPA 780 shall be provided on ABPFs with an H-2 occupancy; on miscellaneous structures with a combustible dust production hazard due to the storage, handling, or processing of grains; and on ABPFs with an H-2 occupancy and a still having a 750 gallon (2839L) or larger capacity, or aggregate bulk storage of Class I Flammable Liquids of 7,800 gallons (29,526L) or greater. 4003.6.4.4 Standby or emergency power. Where mechanical ventilation, treatment systems, limit controls, alarm, detection or other electrically operated systems are required, such systems shall be provided with an emergency or standby power system in accordance with NFPA 70 (NEC) and Section 604.1 of the International Fire Code. Exception: Subject to the fire and building code officials, standby power for mechanical ventilation and limit control systems shall not be required where an approved fail-safe engineered system is installed. 4003.6.5 Location of stills and vessels. Stills and vessels in Class 1 Liquid use areas shall be located with respect to the lot lines of adjoining property which can be built on, in accordance with Tables 5703.4(1) and 5703.4(2) of the International Fire Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 161 Exceptions: 1. Where the exterior wall facing the adjoining lot line is without openings, has a fire-resistance rating of not less than 2 hours, and the ABPF is protected throughout with an automatic sprinkler system in accordance with Section 4003.6.3.1, the fire and building code officials are authorized to reduce the minimum separation distances to not less than 1 foot (305 mm), or the minimum separation distances required by other provisions of the Englewood Building and Fire Code, whichever is greater. 2. Where the capacity of the largest still or vessel within the minimum separation distance is 250 gallons (946 L) or less, the aggregate volume of all stills and vessels within the minimum separation distance is 750 gallons (2839 L) or less, the normal operating pressure of all vessels within the minimum separation distance is 2.5 psig (17.2 kPa) or less, and the ABPF is protected throughout with an automatic sprinkler system in accordance with Section 4003.6.3.1, the minimum separation distance to lot lines is permitted to be 1 foot (305 mm), or the minimum separation distances required by other provisions of the Englewood Building and Fire Code, whichever is greater. 4003.6.6 Security. Class 1 Liquid use areas and storage areas shall be secured against unauthorized entry and safeguarded in a manner approved by the fire code official. 4003.6.7 Protection from vehicles. Bollards in accordance with Section 312 of the International Fire Code or other approved means shall be provided to protect all vessels, stills, and piping which handle Class 1 Liquids and are subject to vehicular, including industrial truck, damage. 4003.6.8 Labeling and signage. When a permit is required in accordance with Section 105, visible hazard identification markings, labels, signs and placards shall be placed on vessels and process piping used for Class 1 Liquids, and in Class 1 Liquid storage areas, use areas and combustible dust production areas, and at the entrances thereto in accordance with applicable federal, state, and standards regulations, Sections 4003.6.8.1 through 4003.6.8.6 and Chapters 50 and 57 of the International Fire Code, and NFPA 704, or as approved. Content shall be in English, symbols permitted by this code and referenced standards, or both. Placards shall be in accordance with NFPA 704. The fire code official is authorized to require additional signs and placards at specific entrances and locations. Markings, labels, signs, and placards shall not be obscured or removed. Exception: Casks are not required to be labeled. 4003.6.8.1 Warning signs. Warning signs shall be of a durable material, have a yellow background with black or red text or symbols, and shall convey the danger being identified. Warning sign text shall not be less than 3 inches (76 mm) in height with a 5/8-inch (15 mm) stroke. 4003.6.8.2 Information signs. Information signs shall be of a durable material, have a blue background with white or red text or symbols, or a white background with blue text, and shall convey the information required. Information sign text shall not be less than 3 inches (76 mm) in height with a 5/8-inch (15 mm) stroke. Exception: Where otherwise specified by applicable regulations or standards. 4003.6.8.3 Location. Placards shall be located in accordance with NFPA 704 and shall be provided on the outside of each interior exit or exit access door in the fire barrier walls separating the H-2 or H-3 occupancies, and in the exterior walls surrounding the H-2 or H-3 occupancies. 4003.6.8.4 Piping. Piping and tubing conveying Class 1, 2, or 3 flammable or combustible liquids between vessels including heat transfer fluids shall be identified in accordance with ASME A13.1 to indicate the material conveyed. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 162 4003.6.8.5 Individual containers, packages and cartons. Individual containers, intermediate bulk containers, packages and cartons shall be conspicuously identified in accordance with federal regulations and applicable state laws. 4003.6.8.6 Tank marking. Every tank shall bear a permanent nameplate or marking indicating the standard used as the basis of design. Stationary tanks more than 100 gallons (379 L) in capacity used for the storage of Class 1 Liquids shall bear a warning sign and placard in accordance with Section 4003.6.8 corresponding to the material therein. Exception: Vats. 4003.6.9 Sources of ignition. Control of sources of ignition shall be in accordance with Sections 4003.6.8.1 and 4003.6.8.2. 4003.6.9.1 Smoking. Smoking areas shall be in accordance with Section 310 of the International Fire Code and shall be prohibited in Class 1 Liquid storage areas or use areas and in combustible dust production areas. "No Smoking" warning signs in accordance with Sections 310.3 of the International Fire Code shall be provided in such areas and at all entrances to them. Exception: Where designated smoking areas within ABPFs are permitted. Designated smoking areas shall be separated from Class 1 Liquid storage areas and use areas and combustible dust production areas by a minimum of 25 feet (7620 mm) and shall be clearly identified with information signs in accordance with Section 4003.6.8. 4003.6.9.2 Open flames. Open flames including barrel charring operations, and devices operating at temperatures above 680 °F (360 °C) are prohibited throughout fire areas containing Class 1 Liquid storage areas or use areas or combustible dust production areas. Exceptions: 1. Areas designated as smoking. 2. Areas where hot work permits have been issued in accordance with this Section 105. 3. Listed and labeled gas fired or electric unit heaters installed in accordance with the International Mechanical Code, International Fuel Gas Code and NFPA 70 (NEC), located more than eight feet (2438 mm) from any edge of equipment where Class 1 Liquid vapor/air mixtures could exist under normal operations and more than three feet (914 mm) above the floor or grade level within 25 feet (7620 mm) horizontally from any equipment with Class 1 Liquids. 4003.6.10 Separation of incompatible materials. Incompatible materials shall be separated in accordance with Section 5003.9.8 of the International Fire Code. 4003.6.11 Seismic protection. All equipment in ABPFs including machinery, racks, piping, and stationary tanks shall be braced and anchored in accordance with the seismic design requirements of the International Building Code for the seismic zone in which the ABPF is located 4003.6.12 Protection from corrosion. Machinery, piping, tank, process vessel, and container materials exposed to Class 1 Liquids shall be protected in accordance with Sections 4003.6.12.1 and 4003.6.12.2 of the International Fire Code. 4003.6.12.1 Protection from external corrosion and galvanic action. Where subject to external corrosion or galvanic action, machinery, piping, tank, process vessel, and container holding or conveying Class 1 Liquids shall be fabricated from noncorrosive materials or provided with corrosion protection. Dissimilar metallic parts subject to galvanic action shall not be joined. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 163 4003.6.12.2 Chemical protection. Machinery, piping, tank, process vessel, and container materials used for Class 1 Liquids shall be protected from all chemicals to which they are exposed including ethanol. Clean-in-place (CIPs) fittings shall be compatible with the cleaning agents used on the vessels and piping to which they are attached. Tank lining shall be in accordance with Section 4004.1.2.6 of the International Fire Code. 4003.6.13 Limit controls. Limit controls shall be provided in accordance with Sections 4003.6.13.1 through 4003.6.13.3. 4003.6.13.1 Pressure control. Machinery, piping, tanks, vessels, and stills containing or conveying Class 1 Liquids shall be designed for the pressures they will be subjected to in accordance with applicable standards. Machinery, piping, tanks, containers, processing vessels, and stills containing or conveying Class 1 Liquids that can generate pressures exceeding design limits because of exposure fires or internal reaction shall have an approved means to relieve excessive positive and negative internal pressure. Vents provided to relieve excessive positive pressure shall discharge to an approved location. 4003.6.13.2 High-liquid-level control. Stationary tanks and process vessels with Class 1 Liquids having a capacity greater than 500 gallons (1893 L) shall be equipped with a device or other means to prevent overflow into the building including, but not limited to a float valve, preset meter on the fill line, valve actuated by the weight of the tank's contents, low-head pump incapable of producing overflow, or a liquid-tight overflow pipe at least one pipe size larger than the fill pipe and discharging by gravity back to an approved location. Exception: Liquid-level sight gauges or other manual means approved by the fire code official to determine fill level are permitted in ABPFs where the use area or storage area is small enough that the stationary tank or process vessel is effectively under constant observation during filling operations. 4003.6.13.3 Low-liquid-level control. Approved safeguards shall be provided to prevent a low- liquid level in stationary tanks, processing vessels and stills from creating a hazardous condition, including but not limited to overheating. 4003.6.14 Handling and transportation. Containers, portable tanks, and casks holding more than 5 gallons (19 L) of Class 1 Liquids being transported in a corridor or enclosed exit shall be on a cart or truck in accordance with Sections 5003.10.2 and 5003.10.3 of the International Fire Code. SECTION 4004 EQUIPMENT 4004.1 General. Equipment utilized for the production, storage, dispensing, blending or handling of Class 1 Liquids shall be listed or approved and shall be in accordance with Sections 4004.1.1 through 4004.1.4.4.2. 4004.1.1 Piping systems. Piping systems for conveying Class 1 Liquids including piping, tubing, valves, pumps, and fittings shall be designed, installed, and maintained in accordance with Sections 4004.1.1.1 through 4004.1. 1.7, Section 5703.6 of the International Fire Code, and ASME B31. The use of other standards is permitted when approved. 4004.1.1.1 Component design and construction. Piping, tubing, hoses, valves, fittings and related components conveying Class 1 Liquids shall be in accordance with the following: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 164 1. Piping, tubing, hoses, valves, pumps, fittings and related components shall be designed and fabricated from materials of adequate strength and durability to withstand the structural and environmental conditions to which they are subjected. 2. Piping, tubing, hoses, valves, pumps, fittings and related components used in liquid transfer operations shall be approved or listed for the intended use. 3. Where provided, in-line flame arresters in piping systems shall be installed and maintained in accordance with their listing or API 2028. 4. Where Class 1 Liquids are carried in piping pressurized above 15 pounds per square inch gauge (psig; 103 kPa), an approved means of leak detection shall be provided. Exception: Piping for overpressure relief devices. 4004.1.1.2 Piping supports. Piping systems shall be substantially supported and protected against physical damage and excessive stresses arising from seismic activity, settlement, vibration, expansion and contraction. Piping supports shall be protected against exposure to fire by: 1. Draining spilled liquid away from the piping support system at a minimum slope of not less than 2 percent; 2. Providing protection with a fire-resistance rating of not less than 2 hours; or 3. Other approved methods. 4004.1.1.3 Pipe joints. Pipe joints shall be in accordance with Sections 5703.6.9 and 5703.6.10 of the International Fire Code. Exception: Where located in concealed spaces within buildings, joints in piping systems used to convey Class 1 liquids shall be welded. 4004.1.1.4 Valves. Piping systems with and without pumps shall contain a sufficient number of manual-control, auto-control, and check valves to protect the ABPF and properly control the flow of Class 1 Liquids; in normal operation, in the event of physical damage, or the condition of fire exposure, and shall be in accordance with the following: 1. Readily accessible manual valves, automatic remotely-activated fail-safe emergency shutoff valves, or excess flow control shall be installed on gravity-fed supply piping and tubing and in systems pressurized above 15 pounds per square inch gauge (psig; 103 kPa) as close to the source as practical. 2. Manual emergency shutoff valves and controls for remotely activated emergency shutoff valves shall be clearly visible and readily accessible. Information signage in accordance with Section 4003.6.8 shall be provided identifying the emergency shutoff valves and controls. 3. Backflow prevention or check valves shall be provided when backflow could create a hazardous condition or cause an unauthorized discharge. 4004.1.1.5 Pumps. Solid or liquid fueled pumps are not permitted in Class 1 Liquid use areas or storage areas. Exception: Fire pumps separated from the Class 1 Liquid use areas and storage areas by 2- hour fire-resistance rated fire barriers in accordance with Section 707 of the International Building Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 165 Positive-displacement pumps shall be provided with pressure relief discharging back to the vessel, pump suction or other approved location, or shall be provided with interlocks to prevent over- pressure. 4004.1.1.6 Pressurized transfer systems. Gases introduced to provide for transfer of Class 1 Liquids shall be inert. Controls, including pressure relief devices, shall be provided to limit the pressure so the maximum working pressure of vessels cannot be exceeded. Where devices operating through pressure within a tank, intermediate bulk container, or container are utilized, the tank, intermediate bulk container, or container shall be a pressure vessel approved for the intended use. 4004.1.1.7 Maintenance. Piping and appurtenances shall be maintained in a safe operating condition and in accordance with their applicable listings and standards. Damage to piping or appurtenances shall be repaired using materials having equal or greater strength and fire resistance or the equipment shall be replaced, taken out of service, repaired or disposed of in an approved manner. The repair, alteration or reconstruction, including welding, cutting and hot tapping of piping that has been placed in service, shall be in accordance with NFPA 30. 4004.1.2 Vessels. The design and construction of vessels used in ABPFs for Class 1 Liquids shall comply with the applicable Sections 4004.1.2.1 through 4004.1.2.13.4 and NFPA 30 or shall be of an approved type. Pressure vessels shall comply with the ASME Boiler and Pressure Vessel Code. 4004.1.2.1 Underground storage of Class 1 Liquids. Underground storage of Class I liquids in tanks shall comply with Chapters 50 and 57 of the International Fire Code. Vaults shall be in accordance with Chapter 57 of the International Fire Code. Underground storage of Class I liquids in other vessels is prohibited. 4004.1.2.2 Outdoor storage of Class 1 Liquids. Outdoor storage shall be in accordance with Chapters 50 and 57 of the International Fire Code. 4004.1.2.3 Tank vehicles and tank cars. Tank vehicles and tank cars shall not be used as storage or processing vessels. 4004.1.2.4 Design of supports. The supporting structure for stationary tanks and portable tanks with capacity greater than 660 gallons (2498 L) shall be designed in accordance with the International Building Code and NFPA 30. 4004.1.2.5 Locations subject to flooding. Where a portable tank or intermediate bulk container with capacity in excess of 660 gallons (2498 L), or a stationary tank is located in an area where it is subject to a rise in the water table, flooding or accumulation of water from fire suppression operations, uplift protection shall be provided in accordance with NFPA 30, Sections 22.14 and 23.14. 4004.1.2.6 Tank lining. Steel stationary tanks and steel portable tanks with capacity greater than 660 gallons (2498 L) are permitted to be lined only for the purpose of protecting the interior from corrosion or providing compatibility with a material to be stored. Only those liquids tested for compatibility with the lining material are permitted to be stored in lined tanks. 4004.1.2.7 Manual drainage. Manual drainage control valves shall be provided on stationary tanks and portable tanks with capacity greater than 660 gallons (2498 L). Manual drainage control valves on stationary tanks shall be located at approved locations remote from the tanks to ensure their operation in a fire condition. 4004.1.2.8 Connections. Filling and emptying connections to vessels shall be provided with liquid-tight caps, covers, plugs, or valves which shall be closed when not in use. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 166 Connections located below normal Class 1 Liquid levels in stationary tanks with capacity of 500 gallons (1893 L) or more shall be provided with internal or external isolation valves located as close as practical to the shell of the tank. 4004.1.2.9 Materials used in tank construction. The materials used in tank construction shall be in accordance with NFPA 30. 4004.1.2.10 Separation between adjacent tanks. The separation between stationary tanks containing Class 1 Liquids shall be in accordance with NFPA 30, Table 22.4.2.1. Exceptions: 1. Where a group of no more than 4 stationary tanks are aligned in a single row, the minimum separation distance between tanks is permitted to be reduced to 18” (457 mm) provided no single tank is over 960 gallons (3634 L) and clear access of 3 feet (914 mm) is provided around the group. 2. Where stationary tanks are in the drainage path of Class 1 Liquids, and are compacted in three or more rows or in an irregular pattern, the fire code official is authorized to require greater separation than specified in NFPA 30, Table 22.4.2.1 or other means to make tanks in the interior of the pattern accessible for emergency response including firefighting purposes. 4004.1.2.11 Maintenance. Vessels and their appurtenances shall be maintained in a safe operating condition in accordance with their listings, applicable standards, and industry practice. Damage and malfunctions shall be repaired using materials having equal or greater strength and fire resistance. Vessels leaking Class 1 Liquids shall be promptly emptied, repaired and returned to service. Stationary tanks not returned to service shall be abandoned in accordance with Section 5704.2.13 or removed in accordance with Section 5704.2.14 of the International Fire Code. 4004.1.2.12 Vent lines. Portable tanks with a storage capacity of 660 gallons (2498 L) or more and stationary tanks shall be provided with normal and emergency vents in accordance with Sections 4004.1.2.12.1 through 4004.1.2.12.5 to relieve positive and negative pressures such as those created from filling and draining. Vent lines shall not be used for purposes other than venting unless approved. 4004.1.2.12.1 Installation of vent piping. Vent pipes shall be designed, sized, constructed and installed in accordance with Sections 5703.6 of the International Fire Code, 5704.2.7.3 and 5704.2.7.4. Vent pipes shall be installed to drain toward the tank without sags or traps in which liquid can collect. Vent pipes shall be protected from physical damage and vibration. 4004.1.2.12.2 Vent-line flame arresters and pressure-vacuum vents. Normal vents shall be equipped with vent-line flame arresters and pressure-vacuum vents in accordance with Section 5704.2.7.3.2 of the International Fire Code. 4004.1.2.12.3 Vent pipe outlets. To facilitate atmospheric dispersion, vent outlets shall be located so vapors are released at a safe point outside of buildings, directed upward or horizontally away from adjacent walls so vapors will not be trapped by eaves or other obstructions. Vent outlets shall not be less than 12 feet (3658 mm) above the finished ground level and shall not be less than 5 feet (1524 mm) from building openings or lot lines of properties that can be built upon. 4004.1.2.12.4 Manifolding. Subject to the approval of the fire code official, vent pipes are permitted to be manifolded only for special purposes such as vapor recovery, vapor DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 167 conservation or air pollution control. Manifolded vent pipes shall be adequately sized to prevent system pressure limits from being exceeded when manifolded tanks are subject to the same fire exposure. 4004.1.2.12.5 Emergency venting. Tanks shall be equipped with additional venting that will relieve rapid overpressure due to fire. Emergency vents shall not discharge inside buildings. The venting shall be installed and maintained in accordance with NFPA 30, 22.7. 4004.1.2.13 Vessel openings other than vents. Vessel openings other than vents shall comply with Sections 4004.1.2.13.1 through 4004.1.2.13.4 4004.1.2.13.1 Filling and emptying connections. Filling and emptying connections to stationary tanks shall be properly identified in accordance with Section 4003.6.8. 4004.1.2.13.2 Fill pipes and discharge lines. For top-loaded stationary tanks and portable tanks with capacity greater than 660 gallons (2498 L), a metallic fill pipe shall be designed and installed to minimize the generation of static electricity by terminating the pipe within 6 inches (152 mm) of the bottom of the tank. It shall be installed in a manner which avoids excessive vibration. 4004.1.2.13.3 Manual gauging. Vessel openings for manual gauging, if independent of the fill pipe, shall be provided with a liquid-tight cap, cover, or plug. Covers shall be kept closed when not gauging. Such openings shall be protected against liquid overflow and possible vapor release by means of a spring-loaded check valve or other approved device. 4004.1.2.13.4 Protection against vapor release. Tank openings provided for purposes of vapor recovery shall be protected against possible vapor release by means of a spring-loaded check valve or dry-break connection, or other approved vapor-tight device. Openings designed for combined fill and vapor recovery shall be protected against vapor release. Exceptions: 1. Where the opening is a pipe connected to a vapor processing system. 2. Where connection of the liquid delivery line to the fill pipe simultaneously connects the vapor recovery line. 4004.1.3 Stairs, platforms and walkways. Stairs, platforms and walkways installed to facilitate access to vessels, storage, pipes, and process equipment shall be noncombustible and designed and constructed in accordance with NFPA 30 and the International Building Code. 4004.1.4 Testing. Equipment, devices and systems shall be tested in accordance with Sections 4004.1.4.1 through 4004.1.4.4.2. 4004.1.4.1 Piping systems. Before being covered, enclosed or placed in use, piping shall be hydrostatically tested to 150 percent of the maximum anticipated pressure of the system, or pneumatically tested to 110 percent of the maximum anticipated pressure of the system, but not less than 5 pounds per square inch gauge (psig; 34.5 kPa) at the highest point of the system. This test shall be maintained for a sufficient time period to complete visual inspection of joints and connections. For a minimum of 10 minutes, there shall be no leakage or permanent distortion. Storage tanks shall be tested independently from the piping. Exception: Piping tested in accordance with the applicable section of ASME B31.9. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 168 4004.1.4.1.1 Existing piping. Existing piping shall be tested in accordance with this section when the fire code official has reasonable cause to believe a leak exists. Piping used for Class 1 Liquids shall not be tested pneumatically. Exception: Vapor-recovery piping is permitted to be tested using an inert gas. 4004.1.4.2 Tanks. Prior to being placed into service, tanks shall be tested in accordance with NFPA 30, 21.5. 4004.1.4.3 Safety systems. Automatic sprinkler systems, automatic sprinkler system monitoring, fire alarm systems, all limit controls, and all other fire- and life-safety systems shall pass the commissioning or acceptance tests in accordance with their respective design, installation, and testing standards prior to occupancy and use of the facility. Emergency alarms and limit-control monitoring shall be tested as for fire alarm systems in accordance with NFPA 72. 4004.1.4.4 Periodic testing. Equipment and safety systems shall be periodically tested in accordance with Sections 4004.1.4.4.1 and 4004.1.4.4.2. Written records of the tests conducted or maintenance performed shall be maintained in accordance with the provisions of Section 107. Exceptions: 1. Periodic testing shall not be required when approved written documentation is provided substantiating testing will damage the equipment, device or system and the equipment, device or system is maintained as specified by the respective manufacturer. 2. Periodic testing shall not be required when the equipment and systems are utilized routinely as part of normal operations and maintained in good operating condition. 3. Periodic testing shall not be required for equipment, devices and systems that fail in a fail-safe manner. 4. Periodic testing shall not be required for equipment, devices and systems that self- diagnose and report trouble. Records of the self-diagnosis and trouble reporting shall be made available to the fire code official. 5. Periodic testing shall not be required if system activation occurs during the required test cycle for the components activated during the test cycle. 6. Approved maintenance in accordance with Section 5003.6 of the International Fire Code that is performed not less than annually or in accordance with an approved schedule shall be permitted to meet the testing requirements set forth in Sections 5003.2.9.1 and 5003.2.9.2 of the International Fire Code. 4004.1.4.4.1 Equipment. The following equipment shall be tested periodically: 1. Piping 2. Limit controls required by Section 4003.6.13 4004.1.4.4.1.1 Testing frequency. The equipment listed in Section 4004.1.4.4.1 shall be tested at one of the frequencies listed below: 1. Not less than annually; 2. In accordance with the approved manufacturer's requirements; 3. In accordance with approved recognized industry standards; or DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 169 4. In accordance with an approved schedule. 4004.1.4.4.2 Safety systems. Safety systems listed in Section 4004.1.4.3 shall be periodically tested in accordance with their design, installation and testing standards. Emergency alarms and limit-control monitoring shall be tested as for fire alarm systems in accordance with NFPA 72. 4004.2 Storage and use areas. Storage and process operations shall be in accordance with the Englewood Building and Fire Code and Sections 4004.2.1 through 4004.2.3.3. 4004.2.1 Storage areas. Storage of Class 1 Liquids shall be in accordance with Sections 4004.2.1.1 through 4004.2.1.4, Chapter 32 of the International Fire Code and NFPA 30. 4004.2.1.1 General. Storage of vessels in closely packed piles, on pallets, in racks, or on shelves shall be in accordance with Sections 4004.2.1.1.1 through 4004.2.1.1.3. 4004.2.1.1.1 Basement storage. Storage in excess of the MAQs is prohibited in basements. 4004.2.1.1.2 Limited combustible storage. Limited quantities of class 1 through 4 commodities are permitted to be stored in the same non-separated area, room, or building as Class 1 Liquids provided the combustibles, other than those used for packaging the Class 1 Liquids, are separated from the Class 1 Liquids in storage by a minimum of 8 feet (2438 mm) horizontally either by open aisles, open racks, or racks filled with noncombustible commodities. 4004.2.1.1.3 Shelf storage. Shelving shall be of substantial construction and shall be braced and anchored in accordance with the seismic design requirements of the International Building Code for the seismic zone in which the ABPF is located. Shelving, chocks, scuffboards, floor overlay and similar installations shall be of noncombustible construction or of wood not less than a 1-inch (25 mm) nominal thickness; treatments, coatings and construction materials shall be compatible with ethanol. Shelves shall be provided with a lip or guard when used for the storage of individual containers or casks. Exception: Storage in flammable liquid storage cabinets specifically designed for such use. 4004.2.1.1.4 Separation and aisles. Aisles shall be provided in storage areas such that all storage vessels are located no more than 20 feet (6096 mm) horizontally from a main aisle or access aisle. Main aisles shall be a minimum of 8 feet (2438 mm) wide in high piled combustible storage areas and a minimum of 4 feet wide in non-high piled combustible storage areas. Access aisles shall be a minimum of 4 feet (1219 mm) wide in high piled combustible storage areas and a minimum of 44 inches (1118 mm) wide in non-high piled combustible storage areas. Aisles utilized for manual stocking, separation between piles, separation between adjacent rows of racks, and separation between racks and adjacent pile storage shall be main aisles or access aisles. Aisles utilized for mechanical stocking shall be main aisles. All piles including palletized storage shall border a main aisle on a minimum of one side or end. Additional aisles shall be provided for access to doors, required windows and ventilation openings, standpipe connections, fire extinguishers, mechanical equipment and switches. Such aisles shall be a minimum of 3 feet (914 mm) in width. A single aisle is permitted to serve multiple functions provided its minimum width is the largest of the widths required for the functions served. 4004.2.1.1.5 Material handling equipment. Material handling equipment shall be suitable to manipulate vessels at the highest tier level. 4004.2.1.1.6 Housekeeping. Storage shall be maintained in an orderly manner. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 170 4004.2.1.1.7 Dunnage, scuffboards, floor overlay. Dunnage, scuffboards, floor overlay and similar installations shall be of noncombustible construction or of wood not less than a 1-inch (25 mm) nominal thickness. 4004.2.1.1.8 High piled combustible storage. Storage of vessels in closely packed piles, on pallets, in racks, or on shelves, where the top of storage is greater than 6 feet (1829 mm) in height, shall be considered high piled combustible storage. Where applicable requirements in Chapter 32 of the International Fire Code are in conflict with those in Section 4004.2.1, the more restrictive shall govern. 4004.2.1.2 Pile storage. Pile storage including palletized storage shall be in accordance with Sections 4004.2.1.3.1 through 4004.2.1.3.2.2. 4004.2.1.2.1 Stabilizing and supports. Intermediate bulk containers, containers, and portable tanks shall be stored in accordance with NFPA 30. Horizontally oriented casks stored in piles shall be supported by stackable racks or cradles of substantial construction designed for that purpose. Lateral bracing shall be provided for horizontally oriented casks stored in piles where the height of the pile exceeds three times the least dimension of the base rack or cradle. Storage height of horizontally oriented casks in this configuration shall not exceed the lesser of the rack manufacturer’s recommendations or industry standards. Exception: Where an approved engineering analysis is submitted demonstrating taller storage configurations are stable against overturning in accordance with the seismic design requirements of the International Building Code for the seismic zone in which the ABPF is located. 4004.2.1.2.2 Palletized storage. Palletized storage shall be in accordance with Sections 4004.2.1.3.2.1 and 4004.2.1.3.2.2. 4004.2.1.3.2.1 Stabilizing and supports. Casks stacked vertically for storage shall be separated by pallets or other dunnage that spreads the weight of the casks on the tier above over the casks on the tier below. A lower tier shall not have less than four casks and shall not have an empty cask when a tier above has a cask that is not empty. No more than two tiers of casks are permitted to be stacked vertically in this configuration. Exceptions: 1. Where the collapse strength of the casks on the lowest tier is not exceeded, palletized storage of vertically oriented casks are permitted to be stacked to a height of four tiers where the casks are bound together in a square pattern groups of no less than four, by a steel band or other approved binding. 2. Where the collapse strength of the casks on the lowest tier is not exceeded, palletized storage of vertically oriented casks are permitted to be stacked to a height of six tiers where the casks are bound together in a square pattern in groups of no less than nine, by a steel band or other approved binding. 3. Where the collapse strength of the casks on the lowest tier is not exceeded, an engineered overturning analysis shall be provided demonstrating stability in accordance with the seismic design requirements of the International Building Code for the seismic zone in which the ABPF is located for storage configurations other than permitted in Exceptions 1 and 2. 4004.2.1.2.2.2 Idle combustible pallets. Storage of idle wood pallets shall be limited to a maximum pile size of 2,500 square feet (232 m2) and to a maximum storage height of 6 feet DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 171 (1829 mm). Storage of idle plastic pallets shall be in accordance with Section 3206.4.1.1 of the International Fire Code and as limited by the capacity of the automatic sprinkler system in accordance with NFPA 13. Pallet storage shall be separated from liquid storage by aisles that are a minimum of 8 feet (2438 mm) wide. 4004.2.1.3 Portable tank, intermediate bulk container, and container storage. Portable tanks and intermediate bulk containers stored over one tier in height shall be designed to nest securely without dunnage. Stacked containers shall be separated by pallets or dunnage to provide stability and to prevent excessive stress to container walls. The storage height and configuration shall be in accordance with NFPA 30. 4004.2.2 Grain storage. Grain storage shall be in accordance with Section 4003.2.1.1. 4004.2.3 Use areas. Use areas for Class 1 Liquids in amounts exceeding the MAQ shall be in accordance with Sections 4004.2.3.1 through 4004.2.3.3. 4004.2.3.1 General. Systems shall be suitable for the use intended and shall be designed by persons competent in such design. Controls shall be designed to prevent materials from entering or leaving the process or reaction system at other than the intended time, rate or path. Where failure of an automatic control could result in a dangerous condition or reaction, the automatic control shall be fail-safe. Use areas with Class 1 Liquids in excess of the MAQs are prohibited in basements. 4004.2.3.2 Non-listed appliances. Stills where internal operating vapor pressures normally exceed 2.5 psig (103.4 kPa) or could potentially exceed 2.5 psig (103.4 kPa) due to failures in operating methods such as clogged head packing or other materials held on column plates shall be provided with a listed pressure relief valve piped to discharge to the exterior in an approved location. Exception: Stills listed for operation above 2.5 psig (103.4 kPa) and, where approved, stills constructed in accordance with the ASME Boiler and Pressure Vessel Code. 4004.2.3.3 Class 1 Liquid transfer. Class 1 liquids shall be transferred by one of the following methods: 1. From safety cans in accordance with NFPA 30. 2. Through an approved closed piping system. 3. From vessels by an approved pump taking suction through an opening in the top of the vessel. 4. By gravity from a tank, intermediate bulk container, or container through an approved self- closing or automatic-closing valve. 5. Approved engineered liquid transfer systems. Exception: Liquids transferred into and from containers not exceeding a 5.3-gallon (20 L) capacity . DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 172 CHAPTER 50 HAZARDOUS MATERIALS—GENERAL PROVISIONS SECTION 5001 GENERAL Section 5001.1 Scope is amended by replacing Exception 10 and adding Exceptions 12 and 13 as follows: 10. The manufacture, storage, dispensing, and use of alcoholic beverages with 16% or less alcohol by volume and the remainder of the beverage not being flammable shall not be limited. 11. To remain. 12. The manufacture, storage, dispensing, and use of alcoholic beverages not meeting the criteria of Exception 10, shall be in accordance with Chapter 38 of the International Fire Code. 13. Battery powered industrial trucks regulated by Section 309. Section 5001.3 Performance-based design alternative is replaced as follows: 5001.3 Performance-based design alternative. When approved by the fire code official, buildings and facilities where hazardous materials are stored, used or handled shall be permitted to comply with this section as an alternative to compliance with the other requirements set forth in this Section and Chapters 51 through 67 of the International Fire Code. Written approval shall be obtained from the fire and building code officials prior to submitting a performance-based design. Section 5001.5.2.1 Preparation is added as follows: 5001.5.2.1 Preparation. The fire code official is authorized to require HMIS submittals to be prepared by a qualified individual or firm acceptable to the fire code official in accordance with Section 104. Section 5001.7 Laboratories using chemicals is added as follows: 5001.7 Laboratories using chemicals. Laboratory buildings, laboratory units, and laboratory work areas in which chemicals are handled or stored shall be in accordance with NFPA 45 and this code. SECTION 5002 DEFINITIONS Section 5002.1 Definitions is amended as follows: 5002.1 Definitions. The following terms are defined in Chapter 2: BIOHAZARD CARCINOGEN OTHER HEALTH HAZARD MATERIAL RADIOACTIVE MATERIAL RELEASE/UNAUTHORIZED DISCHARGE SENSITIZER DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 173 SECTION 5003 GENERAL REQUIREMENTS Section 5003.4 Material Safety Data Sheets is replaced as follows: 5003.4 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) shall be readily available on the premises (hard copy shall always be required) for hazardous materials regulated by this chapter. Material Safety Data Sheets shall be located at the main entrance or a location approved by the Fire Marshal’s Office. When a hazardous substance is developed in a laboratory, available information shall be documented and maintained at a Fire Marshal approved location. The Fire Marshal’s Office serves as the reporting agency for the City of Englewood, the authority having jurisdiction (AHJ). SECTION 5004 STORAGE Section 5004.9 Emergency alarm is replaced as follows: 5004.9 Emergency alarm. An approved manual emergency alarm system shall be provided in buildings, rooms and areas used for the storage of hazardous materials in accordance with Section 908.4. Signage required by Section 908.4 shall state outside of the room: “DO NOT ENTER WHEN LIGHT IS FLASHING – HAZMAT SPILL EMERGENCY ALARM ACTIVATED”, and inside of the room: “FLASHING LIGHT MEANS HAZMAT SPILL EMERGENCY ALARM ACTIVATED – EVACUATE ROOM AND BUILDING.” Section 5004.10 Supervision is replaced as follows: 5004.10 Supervision and monitoring. Emergency alarm, detection and automatic fire-extinguishing systems required by Section 5004 of the International Fire Code, shall be electrically supervised. System shall be monitored by an approved Class I central station service. Section 5004.12 Noncombustible floor is replaced as follows: 5004.12 Noncombustible floor. Except for surfacing, floors, walkways, ramps, structures for walkways and ramps of storage areas shall be of noncombustible construction. SECTION 5005 USE, DISPENSING AND HANDLING Section 5005.1.2 Noncombustible floor is replaced as follows: 5005.1.2 Noncombustible floor. Except for surfacing, floors, walkways, ramps, structures for walkways and ramps of areas where liquid or solid hazardous materials are dispensed or used in open systems shall be of noncombustible, liquid-tight construction. Section 5005.2.1.1 Ventilation is replaced as follows: 5005.2.1.1 Ventilation. Where gases, liquids or solids having a hazard ranking of 3 or 4 in accordance with NFPA 704 are dispensed or used, mechanical exhaust ventilation shall be provided to capture fumes, mists or vapors at the point of generation. A reference for determining exhaust capture requirements can be found in the “Industrial Ventilation, A Manual of Recommended Practice”, 29th edition, published by the American Conference of Governmental Industrial Hygienists (ACGIH). Exception: Gases, liquids or solids which can be demonstrated not to create harmful fumes, mists or vapors under the conditions in which they are handled. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 174 CHAPTER 53 COMPRESSED GASES SECTION 5307 COMPRESSED GASES NOT OTHERWISE REGULATED Section 5307.2.2 Insulated liquid cryogenic fluid systems is added as follows: 5307.2.2 Insulated liquid cryogenic fluid systems. Areas containing insulated liquid cryogenic fluid systems used in commercial, manufacturing or industrial applications shall comply with Section 5307.6. Section 5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications and all subsections are replaced as follows: 5307.3 CO2 Systems Used in Beverage Dispensing Applications. CO2 systems with more than 100 pounds (45.4 kg) of CO2 or any system using any amount of CO2 below grade used in beverage dispensing applications shall comply with Sections 5307.3.1 through 5307.3.8. Definitions Asphyxiation: to lose consciousness by impairing normal breathing, to suffocate or smother. Dewar: a vacuum flask that holds a cryogenic or liquefied gas. CO2 Detector: a device to measure the concentration of CO2 in the air. CO2 Gas Detection Control Unit: a system component that monitors inputs and controls outputs through various types of circuits. Indoor use of CO2: Rooms or areas sheltered from the weather and environmental conditions. Subject to review by the fire code official. Liquid CO2 Systems: An assembly of equipment consisting of one or more CO2 supply containers, interconnecting piping, pressure regulators, and pressure relief devices. PEL: Permissible Exposure Limit for CO2 gas is 5,000 PPM (0.5%) Time Weighted Average (TWA) @ 8 hours a day, 40 hours per week. STEL: Short-Term Exposure Limit for CO2 is 30,000 PPM (3.0%) for less than 15 minutes. IDLH: Immediately Dangerous to Life & Health for CO2 is 40,000 PPM (4.0%). 5307.3.1 Permits. Permits shall be required as set forth in Section 105. 5307.3.2 Equipment. The storage, use, and handling of carbon dioxide shall be in accordance with Chapter 53 of the International Fire Code, and the applicable requirements of NFPA 55, Chapter 13. All equipment utilized in compressed gas systems shall be compatible with the intended gas and use. 5307.3.2.1 Containers, cylinders and tanks. Gas storage containers, cylinders and tanks shall be designed, fabricated, tested, labeled and installed in accordance with manufactures’ specifications and shall be maintained in accordance with the regulations of DOTn 49 CFR, Parts 100-185 or the ASME Boiler and Pressure Vessel Code, Section VIII. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 175 5307.3.2.1.1 Location. Location of gas storage containers, cylinders and tanks, inside or outside the building, shall be at an approved location. 5307.3.2.1.2 Security. Gas storage containers, cylinders and tanks shall be secured in an approved manner to prevent overturning. Containers, cylinders and tanks located outside shall be secured and safeguarded against tampering and protected from physical damage if exposed to vehicle traffic. 5307.3.2.1.3 Design and construction. Bulk tank installations over 2,000 pounds will require an engineered foundation and construction permit in accordance with the Englewood Building Code or other approved method. 5307.3.3 Piping systems. Piping, tubing, fittings, valves and pressure regulating devices shall be designed and installed in accordance with approved standards and manufacturers’ recommendations. 5307.3.3.1 Piping, tubing and hoses. Piping, tubing and hose materials shall be compatible with carbon dioxide and rated for the temperatures and pressures encountered in the system. All hoses and tubing used in carbon dioxide service shall be designed for a bursting pressure of at least four times their design pressure. PVC/ABS and other types of rigid plastic piping are not approved materials. Acceptable piping for carbon dioxide shall be the following: 1. Stainless steel A269 grade, which is either seamless or welded drawn over mandrel 2. Copper K grade, hard drawn seamless 3. Copper ACR grade (1/2 inch outside diameter or less) annealed seamless 4. Plastic/polymer materials rated for use with carbon dioxide and compliant with Code of Federal Regulations Title 21 FDA Part 177 Indirect Food Additives Polymers. 5. Additional approved piping, tubing and hoses found in the Compressed Gas Association (CGA) standards for carbon dioxide 5307.3.3.2 Support. Gas piping shall not be attached or supported by any electrical light supports or wiring. 5307.3.3.3 Identification. Markings for carbon dioxide (CO2) piping systems shall consist of the content’s name (carbon dioxide or CO2) and direction-of-flow arrow. Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at not less than every 20 feet or fraction thereof throughout the piping run. 5307.3.3.4 Fittings, joints and connections. Fittings, joints and connections shall be subject to the approval of the fire and building departments. 5307.3.3.4.1 Fittings and joints between gas supply containers and automatic shutoff valve. Joints and fittings on the supply piping or tubing between the CO2 supply source and the automatic system shutoff valve shall be threaded, compression or welded. 5307.3.3.4.2 Unused connections. Unused piping or tubing connected to the supply system shall be capped or plugged. A closed valve will not be allowed in lieu of a cap or plug. 5307.3.3.4.3 Concealed connections. All fittings and joints shall be exposed and located adjacent to the supply source or points of use and shall be protected by a detector. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 176 5307.3.3.5 Valves. Piping systems shall be provided with valves in accordance with Sections 5307.3.2.3.1 through 5307.3.2.3.5. 5307.3.3.5.1 Pressure relief valves. Pressure relief valves shall be provided and piped to the outdoors. 5307.3.3.5.2 System shutoff valve. An automatic system shutoff valve shall be provided as near to the supply pressure regulator as possible and shall be designed to fail to a closed condition closing on loss of electrical power to the valve and gas detection. Automatic shutoff valves shall be designed and located so that all phases (i.e., gas, liquid and solid) of a carbon dioxide (CO2) will not interfere with the operation of the device. 5307.3.3.5.3 Appliance shutoff valves. Each appliance shall be provided with a shutoff valve within 3 feet of the appliance. All shutoff valves shall be capable of being locked or tagged in the closed position for servicing. 5307.3.3.5.4 Check valves. One-way flow check valves shall be installed at the most downstream end of copper runs that are used for beverage consumption. 5307.3.3.5.5 Accessibility and identification. Valves and controls shall be readily accessible at all times. Normal and emergency system shut-off valves shall be clearly identified. All valves shall be designed or marked to indicate clearly whether it is open or closed. 5307.3.3.6 Venting. Venting of gases shall be directed to an approved location outside the building. Insulated liquid carbon dioxide systems shall have pressure relief devices vented in accordance with NFPA 55. 5307.3.3.6.1 Beverage pumps. Beverage pumps shall be vented to the outside. 5307.3.4 Protection from damage. Carbon dioxide systems shall be installed so the storage tanks, cylinders, piping and fittings are protected from damage by occupants or equipment during normal facility operations. 5307.3.5 Required protection. Where carbon dioxide storage tanks, cylinders, piping and equipment are located indoors, rooms or areas containing carbon dioxide storage tanks, cylinders, piping and fittings and other areas where a leak of a carbon dioxide system can collect shall be provided with either ventilation in accordance with Section 5307.5.1 or an emergency alarm system in accordance with Section 5307.5.2. 5307.3.5.1 Ventilation. Mechanical ventilation shall be in accordance with the International Mechanical Code and shall comply with all of the following: 1. Mechanical ventilation in the room or area shall be at a rate of not less than 1 cubic foot per minute per square foot [0.00508 m3/(s • m2)]. 2. Exhaust shall be taken from a point within 12 inches (305 mm) of the floor. 3. The ventilation system shall be designed to operate at a negative pressure in relation to the surrounding area. 4. Ventilation shall run continuously or be activated by a sensor or detector to maintain an atmosphere of less than 5,000 ppm. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 177 5307.3.5.2 Gas Detection System: A gas detection system shall comply with all of the following: 1. Continuous gas detection shall be provided to monitor areas where carbon dioxide (CO2) can accumulate. Detection equipment shall be provided to indicate carbon dioxide (CO2) levels at each point of use and in each storage area/room. 2. Detectors shall be: a. listed or approved devices b. permanently mounted c. installed at a height of between 12 - 24 inches above the floor or as approved by the fire code official d. directly connected to building electrical and fire alarm systems and protected from accidental disconnection or damage e. auto calibrating and self “zeroing” devices are not permitted unless they can be zeroed and spanned f. located within manufacturers specified detection range for each point of use and storage location 3. Alarm set points shall be set at: a. 5,000 PPM (TWA) Time Weighted Average – Self re-setting (non-latching) alarm ● Notification for employees only in approved locations with instructional signage b. 15,000 PPM – Latching Alarm ● Notification for employees only in approved locations ● Requires a service company or approved trained employees to investigate, repair and reset c. 30,000 PPM – Latching Alarm ● Initiate amber strobes and audible horns provided in the vicinity of each interior storage container, cylinder or tank and at each point of use. Additional amber strobes and audible horns shall be placed at the entrances to below grade locations, confined spaces, and at walk-in coolers. The notification devices shall be rated a minimum of 80cd for a visible effect and 75 dBA for an audible effect and shall be mounted in accordance with NFPA 72 requirements. ● Activation of automatic system shutoff valve ● Evacuate room/area and call 911 ● Alarm Signal* *In buildings with a monitored sprinkler or fire alarm/detection system, the carbon dioxide (CO2) emergency alarm system shall be connected to the building fire alarm control panel. A fire alarm permit is required in accordance with the Englewood Building Code. 4. Signage shall be required adjacent to each horn/strobe as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 178 Outside the storage or point of use area/room: “DO NOT ENTER WHEN LIGHT IS FLASHING - CARBON DIOXIDE LEAK DETECTED – CALL 911” Inside the storage or point of use area/room: “FLASHING LIGHT MEANS CARBON DIOXIDE LEAK DETECTED – EVACUATE IMMEDIATELY AND CALL 911” The sign shall have a minimum 1-inch block lettering with a minimum ¼-inch stroke. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. Additional warning signs shall be posted at the entrances to a room or confined area where the container is located. The warning sign shall be at least 8 inches (200 mm) wide and 6 inches (150 mm) high and state the following: CAUTION – CARBON DIOXIDE GAS Ventilate the area before entering. A high carbon dioxide (CO2) gas concentration in this area can cause suffocation. NFPA 704 placards for Simple Asphyxiants shall also be provided at the main entrance to storage rooms, areas or confined spaces. 5307.3.6 Transfilling. Filling and transfilling of gases between storage containers, cylinders and tanks and delivery vehicles shall be performed by qualified personnel using equipment and operating procedures in accordance with CGA P-1. Interior storage containers, cylinders and tanks shall be filled via remote fill ports on the exterior of the building at grade level. Exterior remote fill ports shall be fitted with a vent line to the outside. Delivery personnel shall have access to interior storage areas to inspect valves and piping prior to initiating filling operations. 5307.3.7 Inspection and testing. All piping installations shall be visually inspected, calibrated, and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 5307.3.7.1 Records. A written record of all required inspections, testing, calibration, and maintenance shall be maintained in a log book on the premises containing the three (3) most current years of records and be available for review by fire inspection personnel. 5307.3.7.2 Required inspections and testing. All piping installations shall be tested and inspected in accordance with Sections 5307.7.2.1 through 5307.7.2.5. 5307.3.7.2.1 Acceptance testing. Appliances and equipment shall not be placed in operation until after the piping system has been checked for leakage and detectors, notification devices and automatic shutoff valves have been tested by a qualified service company. All piping installations shall be visually inspected and pressure tested prior to initial operation. The test pressure downstream of the pressure regulator shall be not less than 110% of the operating pressure. Joints shall be checked with a bubble-forming solution. Acceptance testing is required to be witnessed by Fire and/or Building Code Officials. Provide an inspection report to the fire and/or building officials for the piping and joint visual inspection and pressure test. 5307.3.7.2.2 Daily inspections. All detectors and alarms shall be visibly inspected daily. These inspections are permitted to be conducted by trained employees. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 179 5307.3.7.2.3 Monthly inspections. All storage vessels, piping, and appurtenances shall be visibly inspected monthly. These inspections are permitted to be conducted by trained employees. 5307.3.7.2.4 Semi-annual inspections. Systems shall be visually inspected, gas detectors calibrated in accordance with manufacturer specification, alarms tested, and tested for leaks semi-annually by a qualified service company. 5307.3.7.2.5 Alterations and repair. In the event alterations, repairs or additions are made, the affected piping shall be retested in accordance with Section 5307.4.6 5307.3.7.3 Reserved. 5307.3.7.4 Calibration. Detectors shall be checked for accuracy, calibrated to a reference gas concentration, and span reset. 5307.3.7.5 Pressure testing. Pipe joints shall be exposed for examination during the test. 5307.3.7.5.1 Test medium. The test medium shall be air, nitrogen, carbon dioxide, or an inert gas. 5307.3.7.5.2 Section testing. Piping systems shall be permitted to be tested as a complete unit or in sections. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure. 5307.3.7.5.3 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping systems in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Test records shall be maintained in accordance with Section 5307.4.7 5307.3.7.5.4 Test preparation. All joints and fittings shall be exposed for examination during and after the test. 5307.3.7.5.4.1 Pipe clearing. Prior to testing, the interior of the pipe shall be cleared of all foreign material. 5307.3.7.5.4.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be isolated from the piping by closing the appliance shutoff valve. 5307.3.7.5.4.3 Test pressure measurement. Test pressure shall be measured with a pressure-measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure. 5307.3.7.5.4.4 Test pressure. The test pressures shall be as specified in Section 5307.6.6.5. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 180 shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe or tubing. Pressures shall be adjusted smoothly and slowly to avoid pressure spikes. 5307.3.7.5.5 Test duration. The test duration shall be not less than 10 minutes. 5307.3.7.5.6 Visual inspection and cleaning. After testing is complete and the pressure is reduced to at or below operating pressure, all joints shall be cleaned of bubble-forming solution and visually inspected. 5307.3.7.5.7 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak. 5307.3.7.5.8 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 5307.3.8 Training. All employees shall receive annual training in hazard identification, physical properties, inspection, and emergency procedures. Training records shall be maintained on site and be available to fire inspectors upon request. Section 5307.4 Carbon dioxide enrichment systems and all subsections are replaced as follows: 5307.4. Carbon Dioxide (CO2) gas enrichment systems using on-site supply tanks and/or cylinders in plant growing (husbandry) application. CO2 enrichment systems using on-site supply tanks and/or cylinders with more than 100 pounds (45.4 kg) of CO2 or any system using any amount of CO2 below grade used in plant growing (husbandry) applications shall comply with Sections 5307.4.1 through 5307.4.12. 5307.4.1 Permits. Permits shall be required in accordance with Sections 105 and in accordance with Englewood Fire Marshal policy. 5307.4.2 Equipment. The storage, use, and handling of CO2 shall be in accordance with Chapter 53 of the International Fire Code, and the applicable requirements of NFPA 55, Chapter 13. All equipment utilized in compressed gas systems shall be compatible with the intended gas and use. 5307.4.2.1 Containers, cylinders and tanks. Gas storage containers, cylinders and tanks shall be designed, fabricated, tested and labeled with manufactures’ specifications and shall be maintained in accordance with the regulations of DOTn 49 CFR, Parts 100-185 or the ASME Boiler and Pressure Vessel Code, Section VIII. 5307.4.2.1.1 Location. Location of gas storage containers, cylinders and tanks, inside or outside the building, shall be at an approved location. 5307.4.2.1.2 Security. Gas storage containers, cylinders and tanks shall be secured in an approved manner to prevent overturning. Containers, cylinders and tanks located outside shall be secured and safeguarded against tampering and protected from physical damage if exposed to vehicle traffic. 5307.4.2.1.3 Design and construction. Bulk tank installations over 2,000 pounds will require an engineered foundation and construction permit in accordance with the Englewood Building Code, or other approved engineered solutions. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 181 5307.4.2.2 Piping systems. Piping, tubing, fittings, valves, and pressure regulating devices shall be designed and installed in accordance with approved standards and manufacturers’ recommendations. 5307.4.2.2.1 Piping, tubing and hoses. Piping, tubing, and hose materials shall be compatible with CO2 and rated for the temperatures and pressures encountered in the system. All hoses and tubing used in CO2 service shall be designed for a bursting pressure of at least four times their design pressure. PVC/ABS and other types of rigid plastic piping are not approved materials. Acceptable piping for CO2 shall be the following: a. Stainless steel A269 grade, which is either seamless or welded drawn over mandrel. b. Copper K grade, hard drawn seamless. c. Copper ACR grade (1/2 inch outside diameter or less) annealed seamless. d. Plastic/polymer materials rated for use with CO2. e. Additional approved piping, tubing and hoses found in the Compressed Gas Association (CGA) standards for CO2. 5307.4.2.2.2 Support. Gas piping shall not be attached or supported by any electrical light supports or wiring. All gas piping shall be supported by the building structures or other approved means. 53074.2.2.3 Identification. Markings for CO2 piping systems shall consist of the content’s name CO2 and direction-of-flow arrow. Markings shall be provided at each valve; at wall, floor or ceiling penetrations; at each change of direction; and at not less than every 20 feet or fraction thereof throughout the piping run. 5307.4.2.3 Fittings, joints and connections. Fittings, joints, and connections shall be subject to the approval of the fire code official. 5307.4.2.3.1 Fittings and joints between gas supply containers and automatic shutoff valve. Joints and fittings on the supply piping or tubing between the CO2 supply source and the automatic system shutoff valve shall be threaded, compression or welded. 5307.4.2.3.2 Unused connections. Unused piping or tubing connected to the supply system shall be capped or plugged. A closed valve will not be allowed in lieu of a cap or plug. 5307.4.2.3.3 Concealed connections. All fittings and joints shall be exposed and located adjacent to the supply source or points of use and shall be protected by a detector. 5307.4.2.4 Valves. Piping systems shall be provided with valves in accordance with Sections 5307.4.2.4.1 through 5307.4.2.4.4. 5307.4.2.4.1 Pressure relief valves. Pressure relief valves shall be provided and piped to the outdoors. 5307.4.2.4.2 System shutoff valve. An automatic system shutoff valve shall be provided as near to the supply pressure regulator as possible and shall be designed to fail to a closed condition closing on loss of electrical power to the valve and gas detection. Additional automatic shutoff valves may be provided at each point of use. Automatic shutoff valves shall be designed and located so that all phases (i.e., gas, liquid and solid) of CO2 will not interfere with the operation of the device. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 182 5307.4.2.4.3 Appliance shutoff valves. Each appliance shall be provided with a shutoff valve within 3 feet of the appliance. All shutoff valves shall be capable of being locked or tagged in the closed position for servicing. 5307.4.2.4.4 Accessibility and identification. Valves and controls shall be readily accessible at all times. Normal and emergency system shut-off valves shall be clearly identified. All valves shall be designed or marked to indicate clearly whether it is open or closed. 5307.4.2.5 Venting. Venting of gases shall be directed to an approved location outside the building. Insulated liquid CO2 systems shall have pressure relief devices vented in accordance with NFPA 55. 5307.4.3 Protection from damage. systems shall be installed so the storage tanks, cylinders, piping and fittings are protected from damage by occupants or equipment during normal facility operations. 5307.4.4 Required protection. Where CO2 storage tanks, cylinders, piping and equipment are located indoors, rooms or areas containing CO2 storage tanks, cylinders, piping and fittings and grow room/areas where CO2 is released and can collect shall be provided with an emergency alarm system in accordance with Section 5307.4.4.1. 5307.4.4.1 Gas detection system. A gas detection system shall comply with all of the following: 1. Continuous gas detection shall be provided to monitor areas where CO2 can accumulate. Detection equipment shall be provided to indicate CO2 levels in each grow cultivation area/room and interior CO2 storage location. 2. Detectors shall be: a. Listed or approved devices. b. Permanently mounted. c. Installed at a height of no more than 48 inches above the floor or as approved by the fire code official. d. Directly connected to building electrical supply and or fire alarm systems and protected from accidental disconnection or damage. e. Auto calibrating and self “zeroing” devices are not permitted unless they can be zeroed and spanned. f. Located within manufacturers specified detection range for each point of use and storage location. g. Listed to operate under environmental conditions such as temperature, humidity, and velocity variations. 3. Activation of the gas detection system shall initiate amber horn/strobes provided in the vicinity of each interior storage container, cylinder or tank and at each point of release. Additional amber horn/strobes shall be placed at the entrances to below grade locations and confined spaces. The notification appliances shall be rated a minimum of 80cd for a visible and 75 dBA for audibility. Notification appliances shall be mounted per NFPA 72 requirements with the entire lens mounted between 80 inches and 96 inches above finished floor. Notification appliances shall be listed to operate in special environments, such as outdoors, indoors, high or low temperatures, and high humidity. Provide notification appliances at the following locations: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 183 a. Inside an interior storage room/area and outside the room/area at each entrance. b. Inside grow cultivation room/areas. 4. Local alarm set points shall be set at: 5,000 PPM – Latching Alarm a. Visual and audible notification in approved locations at room or area in alarm. b. Activation of automatic system shut off valve. c. Evacuate the room in alarm and contact a qualified service company to investigate and address the condition. d. Reset of the emergency alarm to be conducted by qualified personnel. 5. Signage shall be required adjacent to each horn/strobe as follows. Storage area/room: “DO NOT ENTER WHEN LIGHT IS FLASHING - CO2 LEAK DETECTED” Grow cultivation room/area dispensing: “FLASHING LIGHT MEANS CO2 LEAK DETECTED –EVACUATE ROOM” The sign shall have a minimum 1-inch block lettering with a minimum 1∕4 -inch stroke. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. Signage on entrance doors to grow cultivation and storage rooms: Signage shall be provided at entrance doors to each grow cultivation room/area and at each entrance to storage rooms/areas: NFPA 704 placards for simple asphyxiants shall also be provided at the exterior main entrance and at each entrance to storage rooms/areas. 6. CO2 Gas Detection Control Unit shall be: a. Listed or approved. b. Used as the required annunciator panel/unit and silencing switch. c. Connected to building electrical by either hardwiring (requiring a separate electrical permit from the building department) or non-spliced cord and plug connection that is visible from control unit and is labeled and protected from accidental disconnection or damage. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 184 d. Labeled and installed in an approved location outside of the potentially CO2 contaminated areas and shall be secured from unauthorized access. Buildings with a fire department key box can secure the control unit with a lockable cover whereas all other covers shall be secured with an approved breakable tie or wire. Subject to field approval. 7. Wiring shall be: a. Wiring diagrams shall be provided for all initiating devices and notification appliances b. Pathway wiring, cable, and equipment shall be in accordance with 2017 NFPA 70, Article 760 and 770, as applicable c. Gas detection circuits shall be installed in a neat and workmanlike manner. Cables and conductors installed exposed on the surface of ceilings and sidewalls shall be supported by the building structure in such a manner that the cable will not be damaged by normal building use. Such cables shall be supported by straps, staples, cable ties, hangers, or similar fittings designed and installed so as not to damage the cable. The installation shall also comply with Article 300 as well as other referenced articles. d. Design shall account for voltage-drops for notification appliance circuits. 6. A minimum of one portable CO2 meter shall be in use during business hours. 5307.4.5 Transfilling. Filling and transfilling of gases between storage containers, cylinders, tanks, and delivery vehicles shall be performed by qualified personnel using equipment and operating procedures in accordance with CGA P-1. Interior storage containers, cylinders and tanks shall be filled via remote fill ports on the exterior of the building at grade level. Exterior remote fill ports shall be fitted with a vent line to the outside. Delivery personnel shall have access to interior storage areas to inspect valves and piping prior to initiating filling operations. Interior supply containers, cylinders, and tanks shall be filled via a remote fill port on the exterior of the building positioned 3 feet from any man or overhead door and 3 feet above grade and 10 feet from air intakes and stairwells that go below grade. If the interior supply tank exceeds 1,000 pounds the fill connection port shall be positioned 10 feet from exits (man doors and overhead doors), air intakes, and 2 feet from all other openings (windows). 5307.4.6 Inspection and testing. All piping installations shall be visually inspected, calibrated, and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 5307.4.7 Records. A written record of all required inspections, testing, calibration, and maintenance shall be maintained in a log book on the premises containing the three most current years of records and be available for review by fire inspection personnel. 5307.4.8 Required inspections and testing. All piping installations shall be tested and inspected in accordance with Sections 5307.4.8.1 through 5307.4.8.5. 5307.4.8.1 Acceptance testing. Appliances and equipment shall not be placed in operation until after the piping system has been checked for leakage and detectors, notification devices and automatic shutoff valves have been tested by a qualified service company. All piping installations shall be visually inspected and pressure tested prior to initial operation. The test pressure downstream of the pressure regulator shall be not less than 110% of the operating pressure. Joints shall be checked with a bubble-forming solution. Acceptance testing is required to be witnessed by fire and/or building officials. Provide an inspection report to the fire and/or building officials for the piping and joint visual inspection and pressure test. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 185 5307.4.8.2 Daily inspections. All detectors and alarms shall be visibly inspected daily. These inspections are permitted to be conducted by trained employees. 5307.4.8.3 Monthly inspections. All storage vessels, piping, and appurtenances shall be visually inspected monthly. These inspections are permitted to be conducted by trained employees. 5307.4.8.4 Semi-annual inspections. Systems shall be visually inspected, gas detectors calibrated in accordance with manufacturer’s specification, alarms tested, and tested for leaks semi-annually by a qualified service company. 5307.4.8.5 Alterations and repair. In the event alterations, repairs or additions are made, the affected piping shall be retested in accordance with Section 5307.4.8.1. 5307.4.9 Reserved. 5307.4.10 Calibration. Detectors shall be checked for accuracy, calibrated to a reference gas concentration, and span reset. 5307.4.11 Pressure testing. Pipe joints shall be exposed for examination during the test. 5307.4.11.1 Test medium. The test medium shall be air, nitrogen, CO2, or an inert gas. 5307.4.11.2 Section testing. Piping systems shall be permitted to be tested as a complete unit or in sections. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure. 5307.4.11.3 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping systems in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Test records shall be maintained in accordance with Section 5307.4.8.1. 5307.4.11.4 Test preparation. All joints and fittings shall be exposed for examination during and after the test. 5307.4.11.4.1 Pipe clearing. Prior to testing, the interior of the pipe shall be cleared of all foreign material. 5307.4.11.4.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be isolated from the piping by closing the appliance shutoff valve. 5307.4.11.4.3 Test pressure measurement. Test pressure shall be measured with a pressure- measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure. 5307.4.11.4.4 Test pressure. The test pressures shall be as specified in Section 5307.6.6.5. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe or tubing. Pressures shall be adjusted smoothly and slowly to avoid pressure spikes. 5307.4.11.5 Test duration. The test duration shall be not less than 10 minutes. 5307.4.11.6 Visual inspection and cleaning. After testing is complete and the pressure is reduced to at or below operating pressure, all joints shall be cleaned of bubble-forming solution and visually inspected. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 186 5307.4.11.7 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak. 5307.4.11.8 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 5307.4.12 Training. All employees shall receive annual training in hazard identification, physical properties, inspections, and emergency procedures. Training records shall be maintained on site and be available to inspectors upon request. Section 5307.5 Carbon Dioxide (CO2) Gas Enrichment Systems Using a Natural Gas Burner in Plant Growing (Husbandry) Applications is added as follows: 5307.5 Carbon Dioxide (CO2) Gas Enrichment Systems Using a Natural Gas Burner in Plant Growing (Husbandry) Applications. Natural gas burners that are utilized to generate CO2 in plant growing applications shall comply with Sections 5307.5.1 through 5307.5.5. A mechanical exhaust system shall be provided as required by the International Mechanical Code. 5307.5.1 Permits. Permits shall be required in accordance with Section 105. 5307.5.2 Equipment. Natural gas burners shall be listed, labeled and installed in accordance with the manufacturer’s installation instructions. Piping systems, combustion and ventilation air and venting for natural gas appliances shall be designed and installed in accordance with approved standards, the International Fuel Gas Code and manufacturer’s recommendations. 5307.5.3 Required protection. Where natural gas burners are located indoors for CO2 enrichment, grow room/areas shall be provided with a gas detection system in accordance with Section 5307.5.3.1 and carbon monoxide detection in accordance with Section 5307.5.3.2. 5307.5.3.1 Gas detection system. A gas detection system shall comply with all the following: 1. Continuous gas detection shall be provided to monitor areas where CO2 can accumulate. Detection equipment shall be provided to indicate CO2 levels in each grow cultivation area/room. 2. Detectors shall be: a. Listed or approved devices. b. Permanently mounted. c. Installed at a height of no more than 48 inches above the floor or as approved by the fire code official. d. Directly connected to building electrical supply and/or fire alarm systems and protected from accidental disconnection or damage. e. Auto calibrating and self “zeroing” devices are not permitted unless they can be zeroed and spanned. f. Located within manufacturer’s specified detection range for each point of release. 3. Activation of the emergency alarm system shall initiate amber strobes/horns provided in each room/area where CO2 can accumulate. Additional amber strobes and audible horns shall be placed at the entrances to below grade locations. The notification appliance shall be rated a DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 187 minimum of 80cd for a visible and 75 dBA for audibility. Notification appliances shall be mounted per NFPA 72 requirements with the entire lens mounted between 80 inches and 96 inches above finished floor. Notification appliances shall be listed to operate in special environments, such as outdoors, indoors, high or low temperatures, and high humidity. Provide notification appliances at the following locations: ● Inside grow cultivation room/areas. 4. Local alarm set points shall be set at: 5,000 PPM – Latching Alarm ● Visual and audible notification in approved locations at room or area in alarm. ● Activation of the automatic natural gas control valves to each burner to a closed position stopping the generation of CO2. ● Evacuate the room in alarm and contact a qualified service company. ● Reset of emergency alarm to be conducted by qualified personnel. 5. Signage will be required adjacent to each horn/strobe as follows: Entrance to below grade location: “DO NOT ENTER WHEN LIGHT IS FLASHING – CARBON DIOXIDE LEAK DETECTED”. Grow cultivation room/area dispensing: “FLASHING LIGHT MEANS CARBON DIOXIDE LEAK DETECTED – EVACUATE ROOM”. The sign shall have a minimum 1-inch block lettering with a minimum 1∕4 -inch stroke. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. Signage at entrance doors: Signage shall be provided at entrance doors to each grow cultivation room/area: NFPA 704 placards for simple asphyxiants shall also be provided at the exterior main entrance. 6. All CO2 burner systems shall shut down in the event of a loss of electrical power to the CO2 detectors. 7. A minimum of one portable CO2 meter shall be in use during business hours. 5307.5.3.2 Carbon monoxide (CO) gas detection. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 188 1. CO gas detection shall be provided to monitor products of combustion continuously. 2. Detectors shall be: a. Listed or approved devices. b. Permanently mounted. c. Installed per manufacturer’s recommendations and directions. d. Directly connected to building electrical supply and fire alarm systems and protected from accidental disconnection or damage. 3. CO detection shall be at set at 35 PPM and upon activation shall initiate the following: ● Close the automatic valve to each burner. ● Activate the mechanical exhaust system. 4. All CO2 burner systems shall shut down in the event of a loss of electrical power to the CO. 5. A minimum of one portable CO meter shall be in use during business hours. 5307.5.4 Inspection and testing. All detectors, alarms and CO2 burners must be visually inspected, calibrated, and tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 5307.5.4.1 Records. A written record of all required inspections, testing, calibration, and maintenance shall be maintained in a log book on the premises containing the three most current years of records and be available for review by fire inspection personnel. 5307.5.4.2 Required inspections and testing. All detectors, alarms and CO2 burner equipment shall be tested and inspected in accordance with Sections 5307.5.4.2.1 through 5307.5.4.2.6. 5307.5.4.2.1 Acceptance testing. Appliances and equipment shall not be placed in operation until after the detectors, notification appliances automatic gas control valves and mechanical exhaust system have been tested by a qualified service company. Acceptance testing is required to be witnessed by fire code officials. 5307.5.4.2.2 Daily inspections. All detectors and alarms shall be visually inspected daily. These inspections are permitted to be conducted by trained employees. 5307.5.4.2.3 Monthly inspections. All CO2 burners and appurtenances shall be visually inspected monthly. These inspections are permitted to be conducted by trained employees. 5307.5.4.2.4 Semi-annual inspections. Systems shall be visually inspected, and gas detectors calibrated in accordance with manufacturer specification semi-annually by a qualified service company. 5307.5.4.2.5 Annual testing. All detectors, alarms, gas control valves and mechanical exhaust systems shall be tested annually by a qualified service company. 5307.5.4.2.6 Alterations and repair. In the event alterations, repairs or additions are made, the affected equipment shall be retested in accordance with Section 5307.5.4.2.1 5307.5.4.3 Reserved DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 189 5307.5.4.4. Calibration. Detectors shall be checked for accuracy, calibrated to a reference gas concentration, and span reset. 5307.5.5 Training. All employees shall receive annual training in hazard identification, physical properties, inspections, and emergency procedures. Training records shall be maintained on site and be available to inspectors upon request. Section 5307.6 Inert Gas Systems Used in Commercial, Manufacturing or Industrial Applications is added as follows: 5307.6 Inert Gas Systems Used in Commercial, Manufacturing or Industrial Applications. Inert gas systems with more than 100 pounds (45.4 kg) of an inert gas or any system using any amount of an inert gas below grade used in a commercial, manufacturing or industrial application, such as water treatment with pH balancing, food processing or laboratories shall comply with Sections 5307.6.1 through 5307.6.7. Inert gases include but are not limited to argon, helium, nitrogen and carbon dioxide. Provisions of Section 5307 are applicable where CO2 is used. Exceptions: 1. Medical gas systems 2. Gaseous Fire suppression systems 3. Carbon dioxide gas enrichment systems in accordance with Section 5307.4 5307.6.1 Permits. Permits shall be required in accordance with Sections 105 and in accordance with Englewood Fire Marshal policy. 5307.6.2 Equipment. The storage, use, and handling of inert gases shall be in accordance with Chapters 53 and 55 of the International Fire Code, and the applicable requirements of NFPA 55. All equipment utilized in compressed gas systems shall be compatible with the intended gas and use. 5307.6.2.1 Containers, cylinders and tanks. Gas storage containers, cylinders and tanks shall be designed, fabricated, tested and labeled with manufactures’ specifications and shall be maintained in accordance with the regulations of DOTn 49 CFR, Parts 100-185 or the ASME Boiler and Pressure Vessel Code, Section VIII. 5307.6.2.1.1 Location. Location of gas storage containers, cylinders and tanks, inside or outside the building, shall be at an approved location. 5307.6.2.1.2 Security. Gas storage containers, cylinders and tanks shall be secured in an approved manner to prevent overturning. Containers, cylinders and tanks located outside shall be secured and safeguarded against tampering and protected from physical damage if exposed to vehicle traffic. 5307.6.2.1.3 Design and construction. Bulk tank installations over 2,000 pounds will require an engineered foundation and construction permit in accordance with the Englewood Building Code. 5307.6.2.2 Piping systems. Piping, tubing, fittings, valves and pressure regulating devices shall be designed and installed in accordance with approved standards and manufacturers’ recommendations. PVC/ABS and other types of rigid plastic piping are not approved materials. Piping systems shall be marked in accordance with Chapter 53. Valves and controls shall be readily accessible at all times. Normal and emergency shut-off valves shall be clearly identified. Pressure relief valves shall be provided and piped to the outdoors. Each appliance or piece of equipment shall be provided with a shutoff valve within 3 feet of the appliance or piece of equipment. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 190 Automatic system shutoff valves shall be provided as near to the supply pressure regulator or container as possible and designed to fail to a closed condition closing on loss of electrical power to the valve and gas detection. All valves shall be designed or marked to indicate clearly whether it is open or closed. All fittings and joints shall be exposed and located adjacent to the supply source or points of use and shall be protected by a detector. 5307.6.2.3 Venting. Venting of gases shall be directed to an approved location outside the building. Insulated liquid gas systems shall have pressure relief devices vented in accordance with NFPA 55. 5307.6.3 Protection from damage. Inert gas systems shall be installed so the storage tanks, cylinders, piping and fittings are protected from damage by occupants or equipment during normal facility operations. 5307.6.4 Required protection. Where inert gas storage tanks, cylinders, piping and equipment are located indoors, rooms or areas containing inert gas storage tanks, cylinders, piping and fittings and other areas where a leak of an inert gas system can collect shall be provided with either ventilation in accordance with Section 5307.6.4.1 or an emergency alarm system in accordance with Section 5307.6.4.2. Exception: Ventilation for indoor dispensing areas is not required where it can be demonstrated that cryogenic fluids do not create harmful vapors. 5307.6.4.1 Ventilation. Mechanical ventilation shall be in accordance with the International Mechanical Code and shall comply with all of the following: 1. Mechanical ventilation in the room or area shall be at a rate of not less than 1 cubic foot per minute per square foot [0.00508 m3/(s • m2)]. 2. Exhaust ventilation shall be designed to consider the density of the potential vapors released. For vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (305 mm) of the floor. For vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (305 mm) of the highest point of the room. 3. The ventilation system shall be designed to operate at a negative pressure in relation to the surrounding area. 4. Ventilation shall run continuously or be activated by a sensor or detector to maintain an atmosphere of not less than 19.5% oxygen in the room. 5307.6.4.2 Emergency alarm system. An emergency alarm system shall comply with all of the following: 1. Continuous gas detection shall be provided to monitor areas where a leak of an inert gas system can collect and create an oxygen deficient atmosphere. Detection equipment shall be provided at each point of use and in each storage area/room. 2. Detectors shall be: a. listed or approved devices b. permanently mounted c. installed at a height consistent with the vapor density of the gas DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 191 d. directly connected to the building electrical supply and fire alarm system and protected from accidental disconnection or damage e. auto calibrating and self “zeroing” devices are not permitted unless they can be zeroed and spanned f. located within manufactures’ specified detection range for each point of use and storage location 3. Activation of the emergency alarm system shall initiate amber strobes and audible horns provided in the vicinity of each interior storage container, cylinder or tank and at each point of use in accordance with alarm set points. Additional amber strobes and audible horns shall also be placed at the entrances to below grade locations and confined spaces. The notification devices shall be rated a minimum of 80cd for a visible effect and 75 dBA for an audible effect and shall be mounted in accordance with NFPA 72 requirements. 4. Alarm set points shall be set at: a. Oxygen levels below 19.5% – Self re-setting (non-latching) alarm ● Visual notification only in approved locations b. Oxygen levels below 17% – Latching Alarm ● Visual and audible notification in approved locations ● Activation of automatic system shutoff valve ● Evacuate room/area and call 911 ● Alarm signal* *In buildings with a monitored sprinkler or fire alarm/detection system, the inert gas emergency alarm system shall be connected to the building fire alarm control panel. A fire alarm permit is required in accordance with the Englewood Building Code. 5. Signage shall be required adjacent to each horn/strobe as follows. Outside the Storage Area/Room: “DO NOT ENTER WHEN LIGHT IS FLASHING – OXYGEN DEFICIENT ATMOSPHERE DETECTED – CALL 911” Inside the Storage Area/Room or at point of use: “FLASHING LIGHT MEANS OXYGEN DEFICIENT ATMOSPHERE DETECTED – EVACUATE IMMEDIATELY AND CALL 911” The sign shall have a minimum 1-inch block lettering with a minimum ¼-inch stroke. The sign shall be on a contrasting surface of black on yellow and shall be of durable construction. On the door of the Storage Room: Signage shall be provided on each storage area entry door stating: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 192 NFPA 704 placards for simple asphyxiants shall also be provided at the main entrance to storage rooms/areas. 5307.6.5 Transfilling. Filling and transfilling of gases between storage containers, cylinders and tanks and delivery vehicles shall be performed by qualified personnel using equipment and operating procedures in accordance with CGA P-1. Interior storage containers, cylinders and tanks shall be filled via remote fill ports on the exterior of the building at grade level. Exterior remote fill ports shall be fitted with a vent line to the outside. Delivery personnel shall have access to interior storage areas to inspect valves and piping prior to initiating filling operations. 5307.6.6 Inspection and testing. All piping installations shall be visually inspected, calibrated, and pressure tested to determine that the materials, design, fabrication and installation practices comply with the requirements of this code. 5307.6.6.1 Records. A written record of all required inspections, testing, calibration, and maintenance shall be maintained in a log book on the premises containing the three most current years of records and be available for review by fire inspection personnel. 5307.6.6.2 Required inspections and testing. All piping installations shall be tested and inspected in accordance with Sections 5307.6.6.2.1 through 5307.6.6.2.5. 5307.6.6.2.1 Acceptance testing. Appliances and equipment shall not be placed in operation until after the piping system has been checked for leakage and detectors, notification devices and automatic shutoff valves have been tested by a qualified service company. All piping installations shall be visually inspected and pressure tested prior to initial operation. The test pressure downstream of the pressure regulator shall be not less than 1½ times the proposed operating pressure. Joints shall be checked with a bubble-forming solution. Acceptance testing is required to be witnessed by fire and/or building code officials. Provide an inspection report to the fire and/or building officials for the piping and joint visual inspection and pressure test. 5307.6.6.2.2 Daily inspections. All detectors and alarms shall be visibly inspected daily. These inspections are permitted to be conducted by trained employees. 5307.6.6.2.3 Monthly inspections. All storage vessels, piping, and appurtenances shall be visibly inspected monthly. These inspections are permitted to be conducted by trained employees. 5307.6.6.2.4 Semi-annual inspections. Systems shall be visually inspected, gas detectors calibrated in accordance with manufacturer specification, alarms tested, and tested for leaks semi-annually by a qualified service company. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 193 5307.6.6.2.5 Alterations and repair. In the event alterations, repairs or additions are made, the affected piping shall be retested in accordance with Section 5307.6.6.2.1. 5307.6.6.3 Reserved. 5307.6.6.4 Calibration. Detectors shall be checked for accuracy, calibrated to a reference gas concentration, and span reset. 5307.6.6.5 Pressure testing. Pipe joints shall be exposed for examination during the test. 5307.6.6.5.1 Test medium. The test medium shall be air, nitrogen, carbon dioxide, or an inert gas. 5307.6.6.5.2 Section testing. Piping systems shall be permitted to be tested as a complete unit or in sections. A valve shall not be subjected to the test pressure unless it can be determined that the valve, including the valve-closing mechanism, is designed to safely withstand the test pressure. 5307.6.6.5.3 Regulators and valve assemblies. Regulator and valve assemblies fabricated independently of the piping systems in which they are to be installed shall be permitted to be tested with inert gas or air at the time of fabrication. Test records shall be maintained in accordance with Section 5307.6.6.1. 5307.6.6.5.4 Test preparation. All joints and fittings shall be exposed for examination during and after the test. 5307.6.6.5.4.1 Pipe clearing. Prior to testing, the interior of the pipe shall be cleared of all foreign material. 5307.6.6.5.4.2 Appliance and equipment isolation. Appliances and equipment that are not to be included in the test shall be disconnected from the piping by closing the isolation shutoff valve. 5307.6.6.5.4.3 Test pressure measurement. Test pressure shall be measured with a pressure-measuring device designed and calibrated to read, record or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure. 5307.6.6.5.4.4 Test pressure. The test pressures shall be as specified in Section 5307.6.6.2.1. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe or tubing. Pressures shall be adjusted smoothly and slowly to avoid pressure spikes. 5307.6.6.5.5 Test duration. The test duration shall be not less than 1/2 hour for each 500 cubic feet (14 m3) of pipe volume or fraction thereof. When testing a system having a volume less than 10 cubic feet (0.28 m3) the test duration shall be not less than 10 minutes. The duration of the test shall not be required to exceed 24 hours. 5307.6.6.5.6 Visual inspection and cleaning. After testing is complete and the pressure is reduced to at or below operating pressure, all joints shall be cleaned of bubble-forming solution and visually inspected DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 194 5307.6.6.5.7 Detection of leaks and defects. The piping system shall withstand the test pressure specified without showing any evidence of leakage or other defects. Any reduction of test pressures as indicated by pressure gauges shall be deemed to indicate the presence of a leak. 5309.6.6.5.8 Corrections. Where leakage or other defects are located, the affected portion of the piping system shall be repaired or replaced and retested. 5307.6.7 Training. All employees shall receive annual training in hazard identification, physical properties, inspection, and emergency procedures. Training records shall be maintained on site and be available to inspectors upon request. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 195 CHAPTER 56 EXPLOSIVES AND FIREWORKS SECTION 5601 GENERAL Section 5601.1 Scope is amended by deleting all Exceptions. Section 5601.1.3 Fireworks is amended by deleting Exceptions 1, 2, and 4. Section 5601.2.4 Financial responsibility is replaced as follows: 5601.2.4 Financial responsibility. Before a permit is issued, as required by Section 105.6, the applicant shall file with the City of Englewood a surety bond in the principal sum of $2,000,000 or a public liability insurance policy for the same amount, for the purpose of the payment of all damages to persons or property which arise from, or are caused by, the conduct of any act authorized by the permit upon which any judicial judgment results. The fire code official is authorized to specify a greater or lesser amount when, in his or her opinion, conditions at the location of use indicate a greater or lesser amount is required. Government entities shall be exempt from this bond requirement. Section 5601.4 Qualifications is replaced as follows: 5601.4 Qualifications. Persons in charge of magazines, blasting, fireworks display, or pyrotechnic special effect operations shall obtain the appropriate State of Colorado license. For pyrotechnic special effect operations, the license is that required for an outdoor display operator. Persons in charge of magazines, blasting, fireworks display, or pyrotechnic special effect operations shall not be under the influence of alcohol or drugs which impair sensory or motor skills, shall be at least 21 years of age, and shall demonstrate knowledge of all safety precautions related to the storage, handling, or use of explosive, explosive material, or fireworks. Section 5601.5 Supervision is replaced as follows: 5601.5 Supervision. The fire code official is authorized to require operations permitted under the provisions of Section 105.6 to be supervised at any time by the fire code official in order to determine compliance with all safety and fire regulations. The City of Englewood Fire Marshal’s Office personnel shall be retained for fire watch and to inspect all equipment and powder charges. The pyrotechnics firm to which the permit is issued/granted shall be responsible for the cost of this/these personnel. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 196 CHAPTER 57 FLAMMABLE AND COMBUSTIBLE LIQUIDS SECTION 5701 GENERAL Section 5701.2 Nonapplicability is amended by replacing Item 10 and adding Item 12 as follows: 10. The manufacture, storage, dispensing, and handling of alcoholic beverages with 16% or less alcohol by volume and the remainder of the beverage not being flammable. 12. The manufacture, storage, dispensing, and handling of alcohol beverages with greater than 16% alcohol by volume shall be in accordance with Chapter 38. Section 5701.5.1 Altitude correction is added as follows: 5701.5.1 Altitude correction. Altitude has a direct impact on the physical properties of flammable and combustible liquids and shall be accounted in the design considerations of life safety and property protection systems. Flash point and boiling point information for flammable and combustible liquids is referenced to sea level. In Englewood, Colorado, the flash point and boiling point of flammable and combustible liquids will reduce by 8° F and may cause reclassification of flammable and combustible liquids. SECTION 5703 GENERAL REQUIREMENTS Section 5703.6.2.2 Bulk transfer and process transfer piping is added as follows: 5703.6.2.2 Bulk transfer and process transfer piping. Closed double-wall steel piping and leak monitoring shall be required for bulk transfer and process transfer of flammable and combustible liquids inside buildings in the following applications: 1. Piping used for the manual transfer of fuel oil 2. Piping used for the automatic transfer of fuel oil from a stationary supply tank, located inside or outside the building, to fuel-burning equipment with or without a day tank 3. Piping used to transfer Class 1A, 1B and 1C flammable liquids Exception: Single wall metallic piping may be used where: 1. the fuel storage tank and fuel-burning equipment are located in a parking garage 2. the fuel storage tank and fuel-burning equipment are located aboveground exterior to the building 3. fuel is automatically transferred from a tank vehicle to a stationary tank, provided the piping system is exposed and continuously supervised by trained personnel during the transfer operation 4. fuel is manually transferred inside a building from a portable tank not greater than 55 gallons provided the piping system is exposed and continuously supervised by trained personnel during the transfer operation. Section 5703.6.2.3 Piping material is added as follows: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 197 5703.6.2.3 Piping material. Metallic piping and installation shall be in accordance with Table 5703.6.2.3 and ASME B31, Code for Pressure Piping. TABLE 5703.6.2.3 PIPING MATERIAL STANDARDS MATERIAL STANDARDS Copper or copper-alloy pipe ASTM B 42; ASTM B 302 Steel pipe ASTM A 53; ASTM A 106 Section 5703.6.10 Pipe joints is amended by adding Exceptions 1 and 2 as follows: Exceptions: 1. All joints in closed double wall steel piping required by Section 5703.6.2.2 shall be welded. 2. All joints in single wall pipe regulated by Section 5703.6.2.2 shall be welded or threaded. Flanged and other mechanical joints are not permitted. SECTION 5704 STORAGE Section 5704.2.13 Abandonment and status of tanks is replaced as follows: 5704.2.13 Abandonment and status of tanks. Tanks taken out of service shall be removed in accordance with Section 5704.2.14 of the International Fire Code, or where approved by the fire code official safeguarded in accordance with Sections 5704.2.13.1 through 5704.2.13.2.3 of the International Fire Code and American Petroleum Institute Standard API RP 1604. Section 5704.3.8.5 Warehouse hose lines is deleted. Section 5704.4.3 Spill control and secondary containment is by replacing the Exception as follows: Exception: Containers stored on approved containment pallets in accordance with Section 5004.2.3 of the International Fire Code and containers stored in cabinets and lockers with integral spill containment. Storage of liquids classified as a Class III-B Combustible shall not be required to have secondary containment. SECTION 5706 SPECIAL OPERATIONS Section 5706.2.5 Type of tank is replaced as follows: 5706.2.5 Type of tank. Tanks shall be provided with top openings only. Dispensing by use of gravity is prohibited. Section 5706.2.5.2 Tanks for gravity discharge is deleted. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 198 CHAPTER 60 HIGHLY TOXIC AND TOXIC MATERIALS SECTION 6004 HIGHLY TOXIC AND TOXIC COMPRESSED GASES Section 6004.2.2.10.1 Alarms is replaced as follows: 6004.2.2.10.1 Alarms. The gas detection system shall initiate a local alarm and transmit a signal to a constantly attended control station when a short-term hazard condition is detected. The alarm shall be in accordance with Section 916. Signage required by Section 916 shall state; outside the room: “DO NOT ENTER WHEN LIGHT IS FLASHING – [HIGHLY] TOXIC GAS LEAK DETECTED.” And inside the room: “FLASHING LIGHT MEANS [HIGHLY] TOXIC GAS LEAK DETECTED – EVACUATE ROOM AND BUILDING.” Exception: Signal transmission to a constantly attended control station is not required where not more than one cylinder of highly toxic or toxic gas is stored. SECTION 6005 OZONE GAS GENERATORS Section 6005.3.2 Ozone gas generator rooms is replaced as follows: 6005.3.2 Ozone gas generator rooms. Ozone gas generator rooms shall be mechanically ventilated in accordance with the International Mechanical Code with a minimum of six air changes per hour. Ozone gas generator rooms shall be equipped with a continuous gas detection system which will shut off the generator and sound a local alarm when concentrations above the permissible exposure limit occur. The alarm shall be in accordance with Section 916.10. Signage required by Section 916.9 shall state: “DO NOT ENTER WHEN LIGHT IS FLASHING – OZONE CONCENTRATION ABOVE THE PERMISSIBLE EXPOSURE LIMIT DETECTED.” Ozone gas-generator rooms shall not be normally occupied, and such rooms shall be kept free of combustible and hazardous material storage. Room access doors shall display an approved sign stating: “OZONE GAS GENERATOR—HIGHLY TOXIC—OXIDIZER.” DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 199 CHAPTER 61 LIQUEFIED PETROLEUM GASES SECTION 6101 GENERAL Section 6101.2 Permits is replaced as follows: 6101.2 Permits. Permits shall be required as set forth in Section 105. Distributors shall not install or fill an LP-gas container for which a permit is required unless a permit for installation has been issued for that location by the fire code official. Installation of all tanks requires submittal of a site plan depicting proposed location on the property and all rights-of-way, structures, and proposed piping. Section 6101.4 Prohibition is added as follows: 6101.4 Prohibition. The installation of LP-gas containers and use of LP-gas is prohibited where a source of natural gas is within 300 feet of the nearest property line. Exception: 1. LP-gas containers used in accordance with this Section, NFPA 58, and the applicable provisions of Chapters 3, 6, 31, 33 and 61 of the International Fire Code. 2. Dispensing installations and operations in accordance with this Section, NFPA 58 and the applicable provisions of Chapter 23 of the International Fire Code. SECTION 6103 INSTALLATION OF EQUIPMENT Section 6103.2.1.7 Use for food preparation is amended by adding the following sentence to the end of the section: Such containers shall not exceed a water capacity of 2.5 lbs. (1 kg). SECTION 6104 LOCATION OF LP-GAS CONTAINERS Section 6104.2 Maximum capacity within established limits is amended by adding Exceptions 2 and 3 as follows: Exceptions: 2. For dwellings constructed under the International Residential Code, a maximum of 40 pounds of propane [or two (2) 20 -lb. cylinders—one for use and one spare bottle] shall be permitted on the premises. For quantity limits inside the actual dwelling unit, see NFPA 58, 8.3.5. Exception: Live/work units shall comply with Section 419 of the International Building Code. 3. For multi-family dwellings, one (1) 20-lb. propane cylinder is allowed to be stored in each detached garage or detached storage area. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 200 SECTION 6107 SAFETY PRECAUTIONS AND DEVICES Section 6107.4 Protecting containers from vehicles is amended by changing the reference from “NFPA 58” to “Section 312 of the International Fire Code.” SECTION 6109 STORAGE OF PORTABLE LP-GAS CONTAINERS AWAITING USE OR RESALE Section 6109.13 Protection of containers is amended by deleting the Exception. Section 6109.15.1 Automated cylinder exchange stations, Item 1, is replaced as follows: 1. The vending system shall only permit access to a single cylinder not to exceed 20 lbs. (9.07 kg) per individual transaction. Section 6112 Fixed, Mobile, or Temporary Concessions Protections is added as follows: SECTION 6112 FIXED, MOBILE, OR TEMPORARY CONCESSIONS PROTECTIONS 6112.1 Required Installations. Cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, and structures shall be limited to (2) 40 pound cylinders (maximum). All D.O.T. cylinders shall have an overfill protection device (OPD) installed. Properly installed A.S.M.E. tanks do not require an OPD (Overfill Protection Device). Installation shall be completed by May 1, 2018 for new and existing for trucks, buses, trailers, and structures. Exception: Where fixed structures are governed by the International Mechanical Code, International Building Code and International Fuel Gas Code. 6112.1.1 Cooking equipment. Listed and labeled for the intended application. The equipment shall be installed in accordance with NFPA 58 and this chapter. 6112.1.2 Cylinder. Shall be mounted to prevent jarring loose, slipping, rotating, or any damage to the tank. The brackets and fastenings shall be designed and constructed to withstand any movement of the LPG tank. 6112.1.3 Piping. All piping shall be installed, tested and inspected in accordance with NFPA 58 and this chapter. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 201 CHAPTER 80 REFERENCED STANDARDS Chapter 80 REFERENCED STANDARDS is amended as follows: NFPA Standards listed in Chapter 80 are replaced as follows: NFPA Codes and Standards – 2013 Edition Volumes 1 through 18 NFPA 13— 2019 Edition NFPA 13R— 2019 Edition NFPA 13D— 2019 Edition NFPA 14— 2019 Edition NFPA 20— 2019 Edition NFPA 72— 2019 Edition NFPA 70—2017 Edition National Fire Protection Association Battery March Park Quincy, MA 02269 Standard for the Installation of Sprinkler Systems Standard for the Installation of Sprinkler Systems in Low Rise Residential Occupancies Standard for the Installation of Sprinkler Systems in One- and Two- Family Dwellings and Manufactured Homes Standard for the Installation of Standpipe and Hose Standard for the Installation of Stationary Pumps for Fire Protection National Fire Alarm Code National Electrical Code Exception: The following NFPA documents are recommendations and do not serve as standards for the City and County of Englewood. 1000 Fire Service Professional Qualifications Accreditation and Certification System - 2006 1061 Public Safety Telecommunicator Qualifications - 2007 1201 Providing Emergency Services to the Public - 2004 1221 Communications, Emergency Services - 2007 1250 Emergency Service Organization Risk Management - 2004 1500 Fire Department Occupational Safety and Health Program - 2007 1561 Emergency Services Incident Management System - 2008 1581 Fire Department Infection Control Program - 2005 1582 Medical Programs for Fire Departments - 2007 1583 Health-Related Fitness for Fire Department Members - 2008 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 202 1710 Career Fire Departments, Organization and Deployment - 2004 Addition: Reference the following standards: Safety Standard for Conveyors and Related Equipment Standard for Pressure Piping National Chlorine Institute 1300 Wilson Boulevard, Suite 525 Arlington, VA 22209 Addition: Reference the following standard: Addition: Reference the following standards: ANSI American National Standards Institute 25 W 43rd Street, Fourth Floor New York, NY 13045 A10-4 – 2007 Safety Requirements for Personnel Hoists and Employee Elevators ANSI/ASHRAE 15– 2004 Safety for Refrigeration Systems ASCE American Society of Civil Engineers 101 Constitution Avenue NW Washington, D.C. 20001 ASCE 21 Automated People Mover Standards (as adopted by the State of Colorado – Parts 1 through 4, as amended by ASCE) ASME American Society of Mechanical Engineers Three Park Avenue New York, NY 10016-5990 ASME A17.1/CSA B44 Safety Code for Elevators and Escalators (as adopted by the State of Colorado) ASME A17.3 Safety Code for Existing Elevators and Escalators (as adopted by the State of Colorado) ASME A18.1 Safety Standard for Platform Lifts and Stairway Chair Lifts (as adopted by the State of Colorado) ASME A90.1 - 2009 Safety Standard for Belt Manlifts ASME B20.1 - 2012 Safety Standard for Conveyors and Related Equipment ASME B31 Standard for Pressure Piping Chlorine Manual National Chlorine Institute 6th printing — 2000 1300 Wilson Boulevard, Suite 525 Arlington, VA 22209 DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 203 Institute of Makers of Explosives Institute of Makers of Explosives1575 Street N.W., Suite #550 Washington, D.C. 20005 Addition: Reference the following standards: Pamphlet 1 Construction Guide for Storage Magazines - 2006 Pamphlet 3 Suggested Code Regulations - 2003 Handbook for the Transportation and Distribution of Explosive Materials - 2007 Pamphlet 17 Safety in the Transportation, Storage, Handling and Use of Explosives - 2007 Pamphlet 20 Safety Guide for the Prevention of Radio Frequency Radiation Hazards in the Use of Electric Blasting Caps – 2001 Pamphlet 21 Destruction of Commercial Explosives Pamphlet 22(b) IME Standard for the Safe Transportation of Class C Detonators (Blasting Caps) in a Vehicle with Certain Other Explosives (1995) Pamphlet 23 Recommendations for the Transportation of Explosives, Division 1.5, Ammonium Nitrate, Emulsion, Division 5.1, Combustible Liquids, Class 3, and Corrosives, Class 8 in Bulk Packaging - 2007 Deletion: IEC DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 204 APPENDICES APPENDIX ADOPTION STATUS INTERNATIONAL FIRE CODE APPENDICES STATUS OF APPENDICES ON ADOPTION All Chapters and Sections of this Appendix are adopted as part of this Code except for those that are deleted in this summary. Those that are amended or added shall also be adopted as part of this Code. APPENDIX TITLE STATUS A Board of Appeals Delete B Fire-flow Requirements for Buildings Adopted as Amended C Fire Hydrant Locations and Distribution Adopted as Amended D Fire Apparatus Access Roads Delete E Hazard Categories Adopted as Reference F Hazard Ranking Adopted G Cryogenic Fluids—Weight and Volume Equivalents Adopted as Reference H Hazardous Materials Management Plan (HMMP) Adopted as Reference I Fire Protection Systems—Noncompliant Conditions Adopted as Reference J Building Information Sign Delete K Construction Requirements for Existing Ambulatory Care Facilities Delete L Requirements for Fire Fighter air Replenishment systems Delete M High-rise Buildings – Retroactive Automatic sprinkler Requirements Delete N Shop Drawing and System Graphic Requirements for Permit Application Adopted O Tall Wood Buildings Adopted DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 205 APPENDIX B FIRE-FLOW REQUIREMENTS FOR BUILDINGS SECTION B104 FIRE-FLOW CALCULATION AREA Section B104.1 General is replaced as follows: B104.1 General. The fire-flow calculation area shall be the total area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building, except as modified in Section B104.3 of the International Fire Code. In buildings with mixed construction types as defined in the International Building Code, the fire-flow calculations shall follow the method described in the 2018 International Fire Code Commentary. Section B104.4 is added as follows: Section B104.4 Fire Flow Data. For new building construction or addition, each set of construction drawings submitted for permit shall contain the required fire flow calculation as follows: Fire Flow Data Block TOTAL FIRE FLOW REQUIRED FOR THIS SITE IS GPM MINIMUM @ 20 PSI RESIDUAL PRESSURE. THIS FLOW MUST BE PROVIDED FROM A MINIMUM OF FIRE HYDRANTS. EACH FIRE HYDRANT SHALL SUPPLY A MINIMUM OF 1500 GPM @ 20 PSI RESIDUAL PRESSURE AT THE HYDRANT OUTLET TO BE ACCEPTABLE. CODE USED FOR ANALYSIS: 2018 IFC WITH 2019 AMENDMENTS OCCUPANCY GROUP(S): CONSTRUCTION TYPE(S): FIRE FLOW CALCULATION AREA: THIS BUILDING IS/IS NOT FULLY PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. SECTION B105 FIRE-FLOW REQUIREMENTS FOR BUILDINGS Section B105.1 One- and two-family dwellings, Group R-3 and R-4 buildings and townhouses is replaced as follows: B105.1 One-and-two-family dwellings, Group R-3 and R-4 buildings and townhouses. The minimum fire flow and flow duration for one-and-two-family dwellings, Group R-3 and R-4 buildings and townhouses shall be as specified in Table B105.1(2) of the International Fire Code. All hydrants, new and/or existing shall flow no less than 1,500 gpm with a minimum residual pressure of 20 psi. Table B105.1(1) is deleted. Section B105.2 Buildings other than one- and two-family dwellings is replaced as follows: B105.2 Buildings other than one- and two-family dwellings. The minimum fire flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table B105.1(2) of the International Fire Code. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 206 Exception: A reduction in required fire flow of up to 50 percent, as approved, is allowed when the building is protected throughout with an automatic fire sprinkler system installed in accordance with NFPA 13 or NFPA 13R. The resulting fire flow shall not be less than 1,500 gallons per minute (5,678 L/min) for the prescribed duration as specified in Table B105.1(2). All hydrants, new and/or existing shall flow no less than 1,500 gpm with a minimum residual pressure of 20 psi. Table B105.2 is deleted. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 207 APPENDIX C FIRE HYDRANT LOCATIONS AND DISTRIBUTION International Fire Code Appendix C Table C102.1, Footnotes f and g are deleted. Section C106 is added as follows: SECTION C106 WATER MAINS SERVING FIRE HYDRANTS C106.1 Water mains serving fire hydrants. Water mains supplying fire hydrants, fire protection systems, and building fire flows shall be sized to provide fire flows for required fire hydrants. Water mains supplying fire hydrants shall be installed as required by the City of Englewood Utilities Department. Operating Rules and Engineering Standards unless specifically approved by the City of Englewood Utilities Department. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 208 APPENDIX N SHOP DRAWING AND SYSTEM GRAPHIC REQUIREMENTS FOR PERMIT APPLICATION is added as follows: APPENDIX N SHOP DRAWING AND SYSTEM GRAPHIC REQUIREMENTS FOR PERMIT APPLICATION SECTION N101 GENERAL N101.1 Scope. All documents submitted for approval of any permit application shall bear the stamp, signature and registration number of the responsible design professional in accordance with the requirements below or as permitted by City of Englewood Fire Marshal’s Office policy. In all cases, acceptance of any permit application shall be subject to the discretion of the fire code official for further review as necessary. Submitted drawings shall be of a minimum drawing sheet size of 24 inches by 36 inches and of sufficient detail and legibility to affect an adequate review of the scope of the work for which a permit is requested. SECTION N102 – Reserved. SECTION N103 TECHNICAL REQUIREMENTS N103.1 Sprinkler system shop drawings submittal. 1. Working plans shop drawings shall be submitted in accordance with Section N103.2.2, Items 1 through 20, Section 903 of the International Fire Code, and NFPA 13, Chapter 23. Shop drawings shall identify the flow and reduced pressures required by Section 903.3.5 used in the hydraulic calculations. Hydraulic calculations and equipment cut sheets are required. Drawings shall be stamped and signed by a Colorado licensed professional engineer. Englewood Water flow test certificate or hydraulic model letter shall be provided with all submittals. 2. Pre-action sprinkler and clean agent suppression systems shall include the requirements for the suppression and detection system in a single permit application. Separate permits are required for fire detection and sprinkler/clean agent installations. 3. Dry sprinkler system designs shall include water delivery time calculations where required by NFPA 13, 7.2.3. N103.2 Fire Department sprinkler system "walk-through" procedures. Review of the following permit applications shall be provided for the modification of existing wet fire sprinkler systems only. The maximum number of permits reviewed or issued for any single applicant shall be limited to two (2) per day. Applicants shall sign-in at the permit center kiosks and await notification for processing. Hours for application are as posted at the permit counter (City holidays excepted). Where shop drawings are required, they shall be stamped and signed by a Colorado licensed professional engineer responsible for the design and submittals shall be in compliance with the relevant codes adopted by the City of Englewood. N103.2.1 Project requirements for Fire Marshal sprinkler walk-through permits. The walk- through project scope is limited to; relocating, adding and plugging sprinklers in accordance with the following: 1. Tenant finish work on an existing sprinkler system involving both sprinkler relocations and additions in a light hazard occupancy for up to 50 sprinklers. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 209 2. Tenant finish work on an existing sprinkler system involving both sprinkler relocations and additions to Ordinary Group 1 and Group 2 Hazards, up to 10 sprinklers in other than Group H occupancies as defined in the International Fire Code. 3. Tenant finish in warehouses where tenant finish is within the office only, in accordance with Item 2 above. 4. For tenant work on all light hazard existing sprinkler systems involving sprinkler relocations and additions, the contractor shall ensure that not more than two (2) sprinklers are fed from any 1" outlet in the new construction area. A maximum of 20 added sprinklers are permitted per zone or floor level. Where the design requires more than two (2) sprinklers to be fed from a 1" outlet, hydraulic calculations shall be provided to ensure the friction loss permits adequate flow for the required design area demand. Full floor layout showing all sprinkler locations and pipe sizes shall be submitted. N103.2.2 Plan submittal - Required information for sprinkler permit walk-through. Shop drawings showing all floors that are affected shall include the following information: 1. Name of owner and occupant 2. Location, including street address 3. Point of compass 4. Full height cross-section, or schematic diagram, if required for clarity, including ceiling construction and method of protection for nonmetallic piping 5. Location of partitions 6. Location of firewalls 7. Building construction type and occupancy classification 8. Location and size of concealed spaces, closets, attics, and bathrooms 9. Sources of water supply with pressure or elevation 10. Make, type, temperature, coverage characteristics, nominal orifice size and K-factor of sprinkler heads. Method of protection for nonmetallic piping. 11. Location of high-temperature sprinklers 12. Total area protected by each system on each floor 13. Pipe type and schedule of wall thickness 14. Nominal pipe size and cutting lengths of pipe (or center-to-center dimensions) 15. Location and size of riser nipples 16. Type of fittings and joints and location of all welds and bends. The contractor shall specify on drawings any sections to be shop welded and the type of fittings or formations to be used 17. Type and locations of hangers, sleeves, braces and methods of securing sprinklers when applicable 18. Layout identifying sizes and locations of existing piping serving the affected floor or area 19. Pipe schedule system justification where such systems are permitted by NFPA 13, Chapter 23 N103.3 Fire Department Fire alarm system shop drawings submittal. Where shop drawings are required, they shall be stamped and signed by a Colorado licensed professional engineer. Drawings shall be submitted DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 210 for permit application in accordance with this Section with the following information: Upon submission of fire alarm shop drawings for review, an applicant may request issuance of a fire alarm “conduit only rough-in” installation permit without approved submitted plans. The contractor shall be responsible for all changes required by the subsequent plan review. A conduit only rough-in permit may only be issued to a contractor with a valid City of Englewood electrical or electrical signal contractor’s license in accordance with this section. Only back boxes, conduit stubs and fire alarm raceway systems are permitted for installation with a conduit only rough-in permit. Conduit only rough-in permits are subject to payment of all Building Department permit fees associated with the total scope of rough-in work in addition to a Fire fee. Payment is required at the time of permit issuance at the Building Department. Raceway systems shall only be installed by State and City licensed electrical contractors who are also licensed by the City of Englewood. Work under a conduit only rough-in permit is subject to subsequent plan review and field inspection for proper and code compliant installation. Corrections identified in the field or by design plan review shall be the responsibility of the contractor. Permits shall only be issued to contractors with the appropriate licenses. N103.3.1 Fire alarm shop drawings shall contain the following information: 1. Exact address, including building and unit numbers; location of work; name and address of responsible design agency. 2. Building occupancy classifications and occupant loads for each occupancy classification. 3. Manufacturers’ specification sheets for all equipment, equipment, appliances and devices. 4. Code reference used as a basis of design, including any administrative modifications or Board of Appeals decisions. 5. Identification of system as code-required, non-required code-compliant or user-defined. 6. Complete sequence of operation input/output matrix with initiating events (input) as the rows and response events (output) as the columns. a. Initiating events shall include (per zone(s) per floor): 1) Manual initiation of alarm or supervisory features 2) Automatic initiation by detection, e.g., smoke, heat, fire, other emergency alarms; devices activating specific mechanisms or life safety functions, such as individual smoke control components, elevator recall, opening protection, etc., shall be identified separately; devices in elevator shafts, elevator machine rooms, stair enclosures shall be identified separately. 3) Manual initiation of special extinguishing systems; devices shall be identified separately per system per zone. 4) Automatic initiation of fire suppression systems; flow switches and special suppression systems shall be identified separately. 5) Functions monitored by the fire alarm system, including but not limited to: a) Equipment/device/appliance/system trouble b) Equipment/device/appliance/system supervisory shall be listed per zone c) Equipment/systems monitored for integrity; identify each system separately 1. Elevator shunt trip power DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 211 2. RES system power 3. FACP and ancillary equipment power 4. Refuge area communication power 5. Emergency firefighter communication system(s) b. Response events shall include: 1) System alarm and system/component supervisory and trouble. 2) Alarm notification including signal transmission to central station, interior and exterior appliances, voice evacuation, special suppression pre-discharge alarms, etc. 3) Required safety functions including (not limited to): a) Elevator recall (list groups or banks separately) b) Smoke control fan activation (list each fan separately) c) Damper activation (list smoke control and opening protection separately per zone per floor) d) Activation of other opening protection (list separately per zone per floor) e) Activation of all electronic access control functions controlled by the fire alarm (list per zone per floor) f) HVAC system shutdown g) Power shunt; list each component/feature/system separately (entertainment visual and audio features and increasing general illumination levels may be listed together per fire area) 7. Identification of air-handling units with airflow exceeding 2,000 cfm (.94 cu m/s) and 15,000 cfm 7.08cu m/s). 8. Identification of air-handling units used for smoke control. 9. Voltage-drop calculations using either the component-by-component method or aggregating the entire load at the end of the circuit. The calculations shall use the listed UL max for new systems. The voltage on a circuit shall not drop below 16 volts at the last appliance. The “R” values used for conductors shall be in accordance with NFPA 70 (NEC) for uncoated copper conductors. Voltage-drop calculations for additional devices on existing system shall be done in the same manner with the same values, as the original calculations for the system. 10. Battery calculations for control panels and power supplies. Calculation shall include 20% de- rating. 11. Scale drawings of each area where work on the fire alarm system is proposed, including north arrow, building address and local street intersections. The drawings shall show the locations of all equipment, appliances, and devices including existing components and end-of-line resistors, room identification by number and function, attic and ceiling details for areas with automatic detection. 12. Mounting heights of wall-mounted devices. 13. Symbol list with quantities of each device. Symbols shall comply with NFPA 170. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 212 14. Power supply connection details. System single-line riser showing all devices. 15. A separate single line drawing of the power supplies, pre-amps, amplifiers, interconnecting wiring, and methods used to provide survivability of the voice evacuation system. 16. Fire alarm circuit identification, in accordance with NFPA 72, including wire color code. 17. Interconnection wiring. 18. Supervising station designation (Central, Proprietary, Remote). 19. Full-scale drawings of annunciators, zone maps and firefighter’s smoke control panels. 20. Reflected ceiling plan, where full smoke detection is provided. 21. Conduit-fill calculations 22. List of control unit bypass features 23. Amplifier load calculations and audio circuit loading (not to exceed manufacturer's maximum circuit dB loss) 24. Name, address and Englewood Fire Marshal’s license number of supervising station. Facilities monitoring radio communication systems shall meet connectivity requirements of Section 917. 25. Fire and smoke construction ratings of walls and barriers 26. Seal and signature of a Colorado registered professional engineer. N103.4 Fire Department fire alarm system "walk-through" procedures. Review of the following permit applications shall be provided for the modification of existing fire alarm systems only. The maximum number of permits reviewed or issued for any single applicant shall be limited to two (2) per day. Applicants shall sign- in at the permit center kiosks and await notification for processing. Hours for application are as posted at the permit counter (City holidays excepted). Submittals shall be in compliance with the relevant codes adopted by the City of Englewood. Fire alarm permit applications may be eligible for walk-through review in accordance with the following: a. Circumstances under which permit applications may be submitted: 1. New equipment, devices and/or appliances connected to existing fire alarm systems in other than Group H and I occupancies. Installation shall be limited to a maximum of twelve (12) new or relocated notification appliances on a single floor and the addition of six (6) new or relocated initiating devices on an existing circuit. Initiating devices connected to access control systems or installed in battery rooms are not eligible for walk-through review. 2. Transferring existing monitoring companies 3. Removal and reinstallation of a device in the same location 4. Installing a new replacement dialer or communicator, or reprogramming same to new central station. 5. Emergency fire alarm panel replacement for an existing system. An emergency panel replacement permit shall be acquired within one (1) normal business day of the commencement of work. The proposed panel shall be compatible with the fire alarm system. A complete application in accordance with Section 907.1.2 shall be submitted within ten (10) normal business days of the commencement of work. The emergency replacement panel is subsequently subject to the requirements for a planned replacement panel. N103.4.1 Plan submittal - Required Information for fire alarm permit walk-through. A complete set DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 213 of electronic plans shall be submitted through the online portal that includes the following (as applicable): 1. Completed permit application 2. Building code occupancy classification 3. Manufacturers’ specification sheets and equipment listing sheets for new equipment and devices 4. Installation codes and standards used 5. Type of system and reason system is provided (required, non-required) 6. Sequence of operation 7. Identification of duct detectors in air-handling units exceeding 2,000 cfm (0.94cu m/s) (not required in VAV boxes less than 2000cfm (0.94cu m/s) each, but aggregate air flow exceeding 2000cfm (.94cu m/s) boxes served by central fan system) 8. Voltage drop calculations and battery calculations 9. Description of annunciation assignments (complete zone schedule) 10. Shop drawings, drawn to scale, including a drawing for each building level involved, with a north arrow for compass orientation and depicting all control and annunciation panels and peripheral devices. Shop drawings shall bear the seal and signature of a professional engineer licensed by the State of Colorado. 11. Plan for upgrading existing annunciator panel, if applicable 12. One-line diagram showing scope of work and identifying new devices 13. Site address, identification of each room’s usage, and areas having automatic detection 14. Provide building details (i.e., attics, ceiling cavities, etc.) 15. Mounting heights for manual fire alarm boxes and strobes 16. Primary power supply connection details and symbol list N103.5 Building plans for graphic map. Plans shall be of durable construction, easily readable in normal lighting, protected by a smooth, transparent, plastic surface and shall include every building level including mezzanines and roofs. Plans shall contain the following information as applicable: 1. Building name 2. Building address 3. Construction type(s) 4. Scale 5. North orientation arrow 6. “You Are Here” in contrasting and bold font 7. Latest date plans were drawn/revised 8. Floor plans 9. Concealed spaces below floors and above ceilings; e.g., crawl spaces and attics 10. Site plan DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 214 11. Adjacent streets 12. Local fire hydrants 13. Major uses, e.g., kitchens, restaurant, offices, Gymnasium, parking, etc. 14. Areas of emergency function, e.g., areas of refuge, fire command center 15. Utility areas, e.g., electrical/telephone rooms/closets, water entry 16. All stair enclosures with distinct designation for each, matching floor signage 17. All elevators with distinct designation for each and associated machine rooms 18. All trash/linen chutes 19. All utility shafts including HVAC and light wells 20. All interior and exterior utility (communication, electricity, gas, water, etc.) shutoff locations 21. Locations of hazardous materials such as: a. Control areas b. Fuel storage c. Battery rooms d. Medical gas rooms e. Emergency and standby power equipment locations f. Fuel fill location g. Identify fuel type and tank size 22. Sprinkler zones 23. All control valve locations including elevators and paint booths 24. Standpipe outlet locations 25. Special suppression systems; e.g., FM-200; UL-300; pre-action 26. Specialized fire protection equipment; e.g., water tanks 27. Fire pump location 28. Fuel fill location for diesel pumps 29. Identify fuel type and tank size as applicable 30. Fire department connections 31. Pump test headers 32. Wall hydrants as applicable 33. Smoke control zones 34. Fire-resistance-rated construction, fire walls, fire barriers, fire partitions, smoke barriers, smoke partitions 35. All initiating devices including water flow DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 215 36. Fire alarm zones 37. NAC power extender locations 38. Roof plan a. Access b. Vents c. Occupied areas 39. Stamp and signature of a professional engineer licensed by the State of Colorado 40. Control areas in accordance with Section 5003.8.3 of the International Fire Code 41. Other features required by the fire code official N103.6 Shop drawing submittals (deferred submittal) for smoke control systems. Shop drawings shall be electronically submitted bearing the stamp and signature of a professional engineer licensed by the State of Colorado and containing the following:: 1. Code reference used as a basis of design, including any Administrative Modifications or Board of Appeals decisions. 2. Plans identifying each smoke control zone including a listing of smoke control equipment (fans) associated with each respective zone. A combination of vertical (section) and/or horizontal (plan) views may be necessary to clearly depict each zone. 3. Certification of coordination of sprinkler, smoke control and fire alarm/detection zones. 4. Plans identifying control equipment including wiring diagrams and tubing schematics as applicable 5. Manufacturers’ specification sheets for all equipment and devices associated with the smoke control system including, but not limited to, the following: Fans, dampers, louvers, CT switches, end-switches, pressure sensors, control tubing, etc. Fan and damper specifications shall include operating temperature to 250° F., minimum number of fan drive belts required for load and number of belts provided. 1.5 x the minimum drive belts required shall be installed. 6. Detailed description of the required testing criteria in Section 909.10.2. Printed reports must be maintained on site in the fire command center. 7. Final acceptance testing plan indicating systems testing. Refer to Section 909.10.1. N103.6.1 Firefighter’s smoke control panel (FSCP). Firefighter's smoke control panel submission shall bear the stamp and signature of a professional engineer licensed by the State of Colorado and shall incorporate the items below as well as a complete sequence of operation for all activation modes. N103.6.1.1 The following features shall be incorporated and color-coded as follows: 1. General building layout (black lines on white background) 2. Exhaust systems – RED 3. Pressurization systems – GREEN 4. Ducts associated with smoke control elements but not active in smoke control mode – GREY 5. Dampers associated with smoke control elements that serve as containment in smoke mode – GREY DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 216 6. Garage supply and exhaust systems shall be energized manually to purge smoke (ON –AUTO only). System need not be connected to emergency power. 7. The status of smoke control equipment shall be indicated by LED lamps and appropriate legends. Fans, major ducts and dampers within the building that are components of the smoke control systems shall be clearly identified as to purpose (e.g., “STAIR PRESSURIZATION FAN”) on the FSCP. Lettering shall be 16 point Helvetica bold; equipment identification (e.g., “SPF-1”) shall be 12 point Helvetica bold. N103.6.1.2 LED status indicators shall be provided for each component of the smoke control system as follows: 1. Fans operating, dampers open, power on – GREEN 2. Fans off, dampers closed – YELLOW 3. Fans and dampers fault status – YELLOW 4. Containment dampers associated with smoke control elements in closed position. – CLOSED – YELLOW, FAULT – YELLOW 5. Panel switch not in auto position – RED 6. Duct detectors as required in accordance with Section 907.3.1 of the International Fire Code, shall be identified – YELLOW 7. Provide lamp test with momentary contact push button(s) to illuminate all LED’s simultaneously. 8. All status LED’s shall be active all the time and will always indicate true equipment status. N103.6.1.2.1 Monitoring for fault status for pressurization and smoke removal fans shall include: a. Loss of power to the fan or VFD/motor starter. b. Open electrical disconnect at pressurization and smoke removal fan, whether the fire alarm system is in alarm or not. c. Fan fails to move air by program or switch on FSCP. d. VFD/motor start failure N103.6.1.2.2 When the fire alarm system is not in alarm, moving a switch on the firefighters smoke control panel out of the “auto” position shall, in addition to the fault light, cause a supervisory signal to the FACP. N103.6.1.3 The FSCP shall provide control capability over all smoke-control system equipment within the building. Control switches are active only during an alarm condition except through a secured and supervised bypass method approved by the fire code officia 1. ON-AUTO-OFF control over each individual piece of operating smoke control equipment that can also be controlled from other sources within the building. This includes; stairway pressurization fans, smoke exhaust fans, supply, return and exhaust fans, elevator shaft pressurization fans and other operating equipment used or intended for smoke control purposes. 2. OPEN-AUTO-CLOSE control over individual dampers relating to smoke control and that are also controlled from other sources within the building. 3. ON-OFF or OPEN-CLOSE control over smoke control and other critical equipment associated with a fire or smoke emergency and that can only be controlled from the fire-fighter’s control panel. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 217 Exceptions: 1. Complex systems, when approved by the fire code official, where the controls and indicators are combined to control and indicate all elements of a single smoke zone as a unit. 2. Complex systems, when approved by the fire code official, where the control is accomplished by a computer interface using plain English commands. N103.6.2 Control action and priorities. The firefighter’s control panel actions shall be as follows: 1. ON-OFF and OPEN-CLOSE control actions shall have the highest priority of any control point within the building. Once issued from the firefighter’s control panel, no automatic or manual control from any other control point within the building shall contradict the control action. Where automatic means are provided to interrupt normal, non-emergency equipment operation or produce a specific result to safeguard the building or equipment (i.e., duct freeze stats, duct smoke detectors, high-temperature cutouts, temperature-actuated linkage and similar devices), such means shall be capable of being overridden by the firefighter’s control panel. The last control action as indicated by each firefighter’s control panel switch position shall prevail. In no case shall control actions require the smoke control system to assume more than one configuration at any one time. Exception: Power disconnects required by the NFPA 70 (NEC). 2. Only the AUTO position of each three-position fire-fighter’s control panel switch shall allow automatic or manual control action from other control points within the building. The AUTO position shall be the normal, non-emergency, building control position. Where a firefighter’s control panel is in the AUTO position, the actual status of the device (on, off, open, closed) shall continue to be indicated by the status indicator described above. When directed by an automatic signal to assume an emergency condition. All devices and indications shall assume the position required by the sequence of operations. In no case shall control actions require the smoke control system to assume more than one configuration at any one time. 3. Manual operation of any control switch from the "AUTO" position shall command the selected equipment to assume the position/operation required. Indicator lights shall register the appropriate change in state. When returned to the "AUTO" position while still in alarm mode, the equipment shall return to the position required by the smoke control programming. N103.6.3 System response time. Smoke control system activation shall be initiated immediately after receipt of an appropriate automatic or manual activation command. Smoke control systems shall activate individual components (such as dampers and fans) in the sequence necessary to prevent physical damage to the fans, dampers, ducts and other equipment. The total response time for individual smoke control systems to achieve their desired operating mode shall not exceed the following time periods: Fan operating at desired state – 75 seconds Damper position travel – 60 seconds N103.7 Emergency responder radio enhancement system (RES) shop drawings: Shop drawings shall be submitted bearing the stamp and signature of a professional engineer licensed by the State of Colorado and containing the following: 1. Facility address and name where applicable 2. Name and address of system design and installation contractor with installation contractor certification number 3. Stamp and dated signature of a professional engineer licensed by the State of Colorado DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 218 4. Manufacturer cut sheets for all cables, connectors, terminations, amplifiers, UPS, batteries, and antenna 5. Manufacturer’s installation instructions 6. Design calculations, (Link Budget) for signal levels at each terminal point and initial input signal strength 7. Wiring riser and distribution diagrams 8. Grounding details 9. Battery calculations 10. Location of all RES equipment 11. “North” reference arrow 12. Copies of FCC authorizations 13. Grid layout and test readings in accordance with Section 510.2.1.1 Exception: For buildings not classified as a high-rise, RES installation drawings may be processed on a walk-through basis. N103.8 High-piled combustible storage installation drawings. 1. Two complete sets of scaled floor plans and vertical sections (as necessary) of the building showing locations and dimensions of use areas including office, battery storage, show rooms, etc. High-piled storage areas shall be depicted and identified including usable storage height for each area. Walls used to separate piles, rack systems, arrays, etc., shall be identified as well as their functions (e.g., fire wall, fire barrier, etc.) and ratings. 2. Scaled plans of all storage arrays identifying all aisles, cross-aisles, catwalks and similar access features. 3. Means of egress in sufficient detail to substantiate compliance of all components with Chapter 10 of the International Fire Code. Floor plans shall be of sufficient clarity and scale to determine travel distance, dead-end corridors, aisle widths, etc. 4. Location of required fire department access doors. Height above adjacent floors, landings, grade planes, etc. shall be identified. 5. Typical scaled sections of each unique rack showing rack height, storage height, number of tiers within each rack, dimensions and locations of catwalks, bridges, pass-throughs, and transverse and longitudinal flues. 6. Fire sprinkler data sheets providing existing or new fire sprinkler design criteria. 7. Clearance between top of storage and the sprinkler deflectors for each storage arrangement. 8. Maximum pile volume for each storage array. 9. Completed Hazards Material Inventory Statement (HMIS) and Hazardous Material Management Plan. 10. Location and classification of commodities in accordance with Section 3203 of the International Fire Code. 11. Location of commodities which are banded or encapsulated. 12. Type and description of fire suppression and detection systems. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 219 13. Location of all valves controlling the water supply for all standpipes and sprinklers (ceiling, in-rack, etc.). 14. A roof or reflected ceiling plan showing the types, locations and specifications of curtain boards, other draft curtains, and all active and passive smoke removal/exhaust systems. 15. A structural analysis including rack and pile stability under seismic loads shall be submitted. Analysis shall also account for occupancy, wind and snow loading in storage systems exposed to such. Analysis shall be in accordance with Chapters 16 and 22 of the International Building Code noting Technical Assistance in accordance with Section 104.7.2 of the International Fire Code may be required for specialized systems falling outside the applicability of these chapters. Installation and use of manufactured and pre-engineered storage systems shall also be in accordance with the systems listings, where applicable, and manufacturer specifications. 16. Any additional information required by the fire code official regarding required design features, commodities, storage arrangement, fire protection, access, egress, etc., within the high-piled storage areas. N103.9 Fire Department “walk-through” for kitchen hood extinguishing system. Provide engineered plans for the suppression system that include the following information: 1. Systems shall be UL-300 listed and compliant with NFPA 96 2. Product cut sheets (panel, nozzles, cylinders, etc.) 3. All nozzle locations 4. Location of manual pull station l0 ft. from hood and next to the exit door 5. Kitchen hood shall be zoned separately and annunciated separately to the building FACP where provided 6. One duct required for every 12 ft. of hood 7. Nozzle types and flow point calculation 8. Shop drawings signed by professional engineer licensed by the State of Colorado N103.10 Installation or alteration of conveyances submittal procedures. Provide shop drawings for the installation or alteration of any conveyance in accordance with Section 919. All drawing submittals shall include equipment manufacturer’s specification sheets for all components and a copy of the City-approved construction floor plan with the locations of all conveyances identified. Where inclined platform lifts and stairway chair lifts are specified, the City-approved construction plans shall include dimensions of the width of the associated stairway(s). All equipment is listed and labeled for the intended application. Prior to commencing work, a licensed elevator contractor is required to submit plans for approval to the Fire Marshal’s Office. N103.10.1 New Conveyance Installations. The following items must be included in the plan submittal: 1. A completed Conveyance Installation or Alteration Permit Application for the proposed equipment installation. 2. Drawings must be submitted electronically in PDF format containing the following information: a. All drawings must bear the signature and seal of a Colorado registered architect and/or professional engineer responsible for the conveyance design. b. Layout drawings shall be dimensional and indicate that the conveyance meets the DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 220 requirements set out in the currently adopted ASME A17.1 or ASME A18.1. Any drawings not indicating the proper code edition will be returned to the contractor for correction and resubmittal. c. Approved layout drawings are the property of the building owner and shall remain on site at all times. d. Documentation stating that material for the car enclosure, enclosure linings and floor coverings (other than metal or glass) conform to the following: 1) ASTM E 84, ANSI/UL 723, for car enclosure and the enclosure lining with a flame spread rating of 0 to 75, and smoke development of 0 to 450. 2) ASTM E 648 with a critical radiant flux of not less than 0.45 W/cm2 for floor covering and underlayment. If, at the time of application, the interior car material is unknown, FPD may issue an initial Installation Permit to install the conveyance. An Alteration Permit must be obtained before the car interior is installed. e. Layout drawing shall include a page that details the following information in Table format. 1) Applicable code reference (Current adopted code or standard ASME A17.1, A18.1, ASCE 21) 2) Job/Contract number 3) Rated capacity 4) Rated speed 5) Total travel 6) Landings front/rear 7) Suspension means type (wire ropes, coated steel belts) 8) Suspension means size 9) For elevators that travel 60 ft or more a communication system that conforms to ASME A17.1 currently adopted edition. If a Fire Command Center (FCC) is present, this communication system shall be located in the FCC. If an FCC is not provided, the location shall be field approved. 10) Emergency/Standby power (Generator, specify quantity of elevators able to operate simultaneously) 11) Identification if hoistway is pressurized 12) Elevator designated as fire service access elevator 13) Elevator platform sized to accommodate an ambulance stretcher in accordance with Section 3002.4 of the International Building Code. 14) Top of car handrail provided N103.10.2 All Elevators (including LU/LA’s, dumbwaiters/material lifts) layout drawings shall also include the following project information: 1. Building name, address and conveyance State registration number. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 221 2. Required clearances and basic dimensions. 3. Location of the Fire Command Center where required by this code. 4. Layout of the elevator annunciator panel where required by this code. 5. Layout of the car operating panel and hall call stations. 6. Quantity and designations of elevator(s) operational simultaneously on an emergency or standby power generator, where provided. All elevators must be manually transferrable to the emergency or standby power source. 7. Primary and alternate floor locations (as determined by FPD). 8. Conformance of the flashing fire hat signal to Section 907.3.3.5. 9. Conformance of the Fire Emergency Operation to Englewood Building Code for pressurized shafts in accordance with Section 907.3.3.4 Exception. 10. Maximum bracket spacing (see ANSI A17.1 Section 2.23 or 3.23). 11. Estimated maximum vertical forces on the guide rails on application of the safety or other retarding device (see ANSI A17.1 Section 2.23 and 2.19.3 or 3.23). 12. In the case of freight elevators for Class B or C loading (see ANSI A17.1Section 2.16.2.2), the horizontal forces on the guiderail faces during loading and unloading, and the estimated maximum horizontal forces in a post-wise direction on the guiderail faces on the application of the safety device (see ANSI A17.1 Section 2.23 or 3.23). 13. Size and linear weight kg/m (lb/ft) of any rail reinforcement, where provided (see ANSI A17.1 Section 2.23 or 3.23). 14. Total static and impact loads imposed on machinery and sheave beams, supports, and floors or foundations (see ANSI A17.1 Section 2.9). 15. Impact load on buffer supports due to buffer engagement at the maximum permissible speed and load (see ANSI A17.1 Section 8.2.3). 16. Total static and dynamic loads from the governor, ropes, and tension system. 17. Horizontal forces on the building structure stipulated by ANSI A17.1 Sections 2.11.11.8 and 2.11.11.9. 18. Rated speed and operating speed in the down direction. 19. Identification of welding in conjunction with work. Hot work permit is required (other than for tack welds) or may be included in elevator permit when approved; include in elevator permit scope. 20. Identification if hoistway is pressurized. N103.10.2.1 Electric Elevators (including LU/LA’s, dumbwaiters/material lifts): 1. Where compensation tie-down is applied (see ANSI A17.1 Section 2.21.4.2), the load on the compensation tie-down supports 2. Maximum upward movement (see ANSI A17.1 Section 2.4.6) N1013.10.2.2 Hydraulic Elevators (including LU/LA’s, Dumbwaiters/Material Lifts): LU/LA Elevators: DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 222 1. Net vertical load from the elevator system, which includes the total car weight and rated load; plunger, cylinder, and oil; and any structural supports 2. Outside diameter and wall thickness of the cylinder, plunger and piping, and the working pressure 3. Minimum grade of pipe (ASTM or recognized standard) required to fulfill the installation requirements for pressure piping, or in lieu of a specific ‖grade‖ of pipe, the minimum tensile strength of pipe to be used for the installation (see ANSI A17.1 Section 3.19) 4. Length of the plunger and cylinder 5. Clearance between the bottom of the plunger and the bottom head of the cylinder as required by ANSI A17.1 Section 3.18.3.3 N103.10.2.3 Escalators/Moving Walks. Layout drawings shall, in addition to other data, indicate the following: 1. Building name, address and State registration number 2. Whether escalator to be installed indoors or outdoors 3. Maximum speed (escalators 100fpm; moving walks up to 180fpm depending on angle of inclination) 4. Angle of inclination (escalators not to exceed 30degrees; moving walks not to exceed12degrees) 5. Rise and length N103.10.2.4 Vertical Platform Lift (VPL) and Inclined Platform Lift (IPL). Layout drawings shall, in addition to other data, indicate the following: 1. Building name, address and State registration number 2. Number for landings (stops) 3. Whether the lift is to be installed indoors or outdoors 4 Type of drive 5. Total travel (not to exceed 14ft, VPL) 6. Speed (not to exceed 30ft/min) 7. Capacity (not to exceed 750lbs) 8. Clear platform width and length (not to exceed 18sf for VPL and 12sf for IPL) 9. Type of lift controls 10. Power supply N103.10.3 Altered Conveyances (all conveyances): Layout drawings shall contain the following information: 1. A detailed list of the components that are to be altered. 2. A scope of work shall be attached to the permit application form. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 223 3. If the scope of work includes altering of Fire Emergency Operation, the elevator contractor shall provide documentation that the current fire alarm panel is capable of fire recall or that a permit to alter/install a new fire alarm panel has been issued. 4. If the scope of work includes the interior of the car enclosure, documentation as stated above shall be provided. 5. All drawings must bear the signature and seal of a Colorado registered architect and/or professional engineer responsible for the conveyance design. N103.11 Emergency alarm systems and gas detection systems shop drawings submittal. Shop drawings shall be submitted for permit application in accordance with this Section. N103.11.1 Emergency alarm shop drawings shall contain the following information: 1. Exact address, including building and unit numbers; location of work; name and address of responsible design agency. 2. Building code occupancy classification(s) for each area or room. 3. Manufacturers’ specification sheets for all equipment, appliances and devices. 4. Code reference used as a basis of design, including any administrative modifications or Board of Appeals decisions. Type of system and reason system is being provided. 5. Installation codes and standards used. 6. Complete sequence of operation input/output matrix with initiating events (input) as the rows and response events (output) as the columns. 7. Voltage drop calculations for notification circuits and battery calculations for secondary power supply. 8. Scaled drawings of each area where work on the emergency alarm system is proposed, including north arrow, building address and local street intersections. The drawings shall show the locations of all equipment, initiating devices, notification appliances, signage, and room designations. 9. One-line diagram showing scope of work and identifying initiating devices, notification appliance.es, conductors, etc. 10. Symbol list with quantities of each device or equipment. 11. Primary power supply connection details and type of secondary power supply. 12. Description of connection to building fire or sprinkler alarm system. 13. Seal and signature of a Colorado registered professional engineer. N103.12 Area of rescue assistance communication - Required Information for “walk-through.” A complete set of electronic plans shall be submitted though the online portal that includes the following (as applicable): 1. Completed permit application 2. Building code occupancy classification 3. Manufacturers’ specification sheets and equipment listing sheets for new equipment and devices DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 224 4. Installation codes and standards used 5. Type of system and reason system is provided (required, non-required) 6. Sequence of operation 7. Backup battery calculations 8. Shop drawings, drawn to scale, including a drawing for each building level involved, with a north arrow for compass orientation and depicting all call boxes, master stations and power supplies. Shop drawings shall bear the seal and signature of a professional engineer licensed by the State of Colorado. 9. One-line diagram. 10. Site address 11. Mounting heights for call boxes 12. Primary power supply connection details and symbol list N103.13 Emergency and standby (required or optional) power generator shop drawings submittal. Shop drawings shall be submitted for permit application in accordance with this Section. N103.13.1 Emergency and standby (required or optional) power generator shop drawings shall contain the following information: 1. Exact address, including building and unit numbers; location of work; name and address of responsible design agencies. 2. Building code analysis. 3. Code reference used as a basis of design, including any administrative modifications or Board of Appeals decisions. Type of generator system and reason system is being provided. Installation codes and standards used. 4. Manufacturers’ specification sheets for all equipment (i.e., generator, vent piping, fill connection and piping, overfill spill containers, overfill prevention alarms and automatic shut off valve, etc.) including fuel tank(s), where applicable. 5. Provide size of fuel tank (i.e., useable capacity) and load duration calculations for the sizing of the proposed fuel tank. 6. Scaled drawings indicating the location (inside or outside the building) and layout of the proposed generator and supply tanks where applicable. The drawings shall locate the new generator in relation to existing buildings, property lines, street/alley right of way lines and transformers for exterior generators and the room construction for interior generators. 7. Provide engineered foundation plan/details for exterior generator including vehicle impact protection. For interior generators, provide a structural engineers’ report for the floor support. 8. Provide normal and emergency venting with piping diagrams and elevations. 9. Provide fill pipe connection location with piping diagrams and elevations. 10. Provide overfill prevention including spill containers, audible/visual alarms and automatic shut off of the flow of fuel to the tank. 11. Provide engine exhaust systems including the exhaust termination outside the building for inside generators. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 225 12. Provide an identified/labeled remote manual stop station outside the room housing the generator or external to the weatherproof enclosure if located outside. 13. Provide generator remote status panel. Indicate the proposed location of the remote status panel and the safety indicator functions. A graphic map to assist the responding fire fighters shall be provided adjacent to the remote status panel indicating the location of the generator, equipment served by the generator, location of emergency disconnect and remote manual stop station. 14. Seal and signature of a Colorado registered professional engineer or architect. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 226 Appendix O Tall Wood Buildings is added as follows: APPENDIX O TALL WOOD BUILDINGS SECTION O101 GENERAL O101.1 Purpose. The purpose of this appendix is to provide criteria for three new mass timber construction types: Type IV-A, Type IV-B, and Type IV-C. These building types expand the allowable use of mass timber construction to larger areas and greater heights than allowed for Type IV-HT construction. O101.2 Scope. The provisions in this appendix are in addition to or replace the sections in the 2018 International Fire Code where Types IV-A, IV -B, and IV-C construction are used. Where building Types IV- A, IV-B, or IV-C are not used, this appendix does not apply. SECTION O102 AMENDMENTS TO THE INTERNATIONAL FIRE CODE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES 701.6 Owner’s responsibility. The owner shall maintain an inventory of all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707 and Section 602.4.1 and 602.4.2 of the International Building Code. Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Records of inspections and repairs shall be maintained. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space. CHAPTER 33 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION 3308.4 Fire safety requirements for buildings of Types IV-A, IV-B, and IV-C construction. Buildings of Types IV -A, IV -B, and IV -C construction designed to be greater than six stories above grade plane shall comply with the following requirements during construction unless otherwise approved by the fire code official. 1. Standpipes shall be provided in accordance with Section 3313. 2. A water supply for fire department operations, as approved by the fire code official and the fire chief. 3. Where building construction exceeds six stories above grade plane, at least one layer of noncombustible protection where required by Section 602.4 of the International Building Code shall be installed on all building elements more than 4 floor levels, including mezzanines, below active mass timber construction before erecting additional floor levels. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030 Attachment A/EMC 8-2E-2 2020 ENGLEWOOD AMENDMENTS TO THE 2018 INTERNATIONAL FIRE 227 Exception: Shafts and vertical exit enclosures shall not be considered a part of the active mass timber construction. 4. Where building construction exceeds six stories above grade plane required exterior wall coverings shall be installed on all floor levels more than 4 floor levels, including mezzanines, below active mass timber construction before erecting additional floor level. Exception: Shafts and vertical exit enclosures shall not be considered a part of the active mass timber construction. DocuSign Envelope ID: EB38A019-355A-441D-B50D-34508269F030